–    The thresholds used during IP operation and the corresponding delays are displayed in a dedicated video page:

FRONT BUTTON FUNCTIONS

MENU button

- Used to enter or exit the various display and setup menus.

Buttons

s

and 

-  Used to scroll between screens, select from available options on the display and change (increase/decrease) settings.

Button

- Used to scroll sub-pages, confirm selected options and switch between display modes.

DISPLAYING MEASUREMENTS 

–    The 

s

and

t

buttons allow the measurement display pages to be scrolled one at a time. The current page is shown on the title bar.

–    The first page displayed (main page) contains all the most important information in both numerical and graphical form. The limit thresholds are indicated by a small marker above the graphic bar, while the arrows

under the graphic bar indicate the measurement range (HI – LO).

–    The next page displays an overview of the state of the Interface Protection System, showing both the state of the outputs to the IS and backup and the state of the control inputs. The black arrows indicate an active

state, the grey ones an inactive state.

–    Three pages with trip protection counters follow, divided into total trip count, voltage threshold trip count and frequency threshold trip count.The counters can be reset through the Commands Menu.

–    Some measurements may not be displayed, depending on the programming and the connection for the device (for example, if programmed for a system without neutral, the measurements relating to neutral are

not displayed).

Содержание PMVF 80

Страница 1: ...den Vor jedem Eingriff am Instrument die Spannungszufuhr zu den Messeing ngen trennen und die Stromwandler kurzschlie en Bei zweckwidrigem Gebrauch der Vorrichtung bernimmt der Hersteller keine Haftun...

Страница 2: ...ol OUT1 IS Interface Switch coil control OUT2 backup device control 4 contact digital inputs for INP1 IS feedback input INP2 R O C O F and Vector Shift monitoring function inhibition INP3 interface pr...

Страница 3: ...ant information in both numerical and graphical form The limit thresholds are indicated by a small marker above the graphic bar while the arrows under the graphic bar indicate the measurement range HI...

Страница 4: ...ACTIVE VOLTAGE THRESHOLDS AND DELAYS CURRENTLY ACTIVE R O C O F VECTOR SHIFT 4 IP TRIP COUNTER IS TRIP CNT BACKUP TRIP CNT REMOTE TRIP CNT POWER ON CNT IS OFF TIME 5 VOLTAGE THRESHOLD TRIP COUNTERS U...

Страница 5: ...he settings In the normal measurements display press MENU to recall the main menu then select the password icon and press The password setting window shown below will appear Press the s t buttons to c...

Страница 6: ...are used P01 05 Current of CT secondary winding P01 06 Type of connection and type of voltage control Program in line with the wiring P01 07 Rated active power of system If set to AUT the value is ca...

Страница 7: ...Threshold 115 P 50kW OFF 100 130 125 P 50kW P04 02 UMAX U Threshold 110 OFF 100 120 P04 03 UMIN U Threshold 80 OFF 20 100 P04 04 UMIN U Threshold OFF P 50kW OFF 5 100 45 P 50kW P04 05 UMAX U Delay s 0...

Страница 8: ...Alarm A03 enable ON ON OFF P06 04 Alarm A04 enable ON ON OFF P06 05 Alarm A05 enable ON ON OFF P06 06 Alarm A06 enable ON ON OFF COMMANDS MENU The Commands Menu is used to perform occasional operation...

Страница 9: ...A04 INCORRECT MODULE HW CONFIGURATION PMVF 80 has not found the required expansion modules Check that they are configured correctly at the side A05 LSP1 TRIP PRESS s t TO RESTORE Power Imbalance Limi...

Страница 10: ...connection of all the ISs auxiliary contacts In single phase wiring connect terminal V3 to VN Class 1 current transformers are recommended ATTENTION terminals A1 and A1 of EXM modules are connected in...

Страница 11: ...s selected Backup output mirrors the IS output See parameter P01 16 M01 GENERAL MENU on page 6 TERMINAL LAYOUT MECHANICAL DIMENSIONS MM MOUNTING INSTRUCTION DEMOUNTING INSTRUCTION DEVICE SYMBOLS Warni...

Страница 12: ...st be used with the same voltage source TECHNICAL CHARACTERISTICS Auxiliary supply Rated voltage Us 100 240V 110 250V Operating range 85 264V 93 5 300V Frequency 45 55Hz Power consumption dissipation...