Password dimenticata o persa 

Se la password viene dimenticata o persa, dopo tre tentativi consecutivi di 
inserimento password non corretta, il display visualizza un codice di sblocco di 
6 cifre. Contattare il customer service Lovato electric comunicando il codice di 
sblocco. Verrà restituita la password per l’accesso. L’utente è poi libero di re-
impostarla a piacimento (tramite il parametro P.01). 

Lost or forgotten password  

If password is lost or forgotten, after three consecutive faulty attempts to 
enter the password, the display shows a 6-digit unlock code. Please contact 
Lovato electric customer service reporting this unlock code. The right 
password will be provided. The user is then free to change setting it as 
desired in the usual way (parameter P.01).  

 

Impostazione parametri (setup) 

x

Con il display che indica 

SETUP

, premere 

.  

x

Il display indica il codice del primo parametro  

P-01. 

 

x

Per selezionare 

 

i parametri successivi

  P-02, P-03 

… usare 

x

Quando il display indica il codice del parametro che si desidera modificare, 

premere  

o

Se si tratta di un parametro numerico (password, soglie, ritardi), il 
display indica il valore attuale dell’impostazione del parametro. Le 
singole cifre lampeggiano a rotazione. Premendo 

 mentre una 

cifra sta lampeggiando, essa viene incrementata. Attendendo, 
comincia a lampeggiare la cifra successiva.  

o

Se invece il parametro prevede la scelta fra diverse opzioni (funzione 
uscita, misura) premendo 

 

si può selezionare a rotazione la 

funzione voluta.  

o

Confermando con 

 

si può tornare alla selezione parametri.  

x

Dopo l’ultimo codice parametro il display visualizza 

--ESC--

. Premendo il 

tasto 

 

in questo momento, i parametri vengono salvati e si torna al 

funzionamento normale.  

 
 
 
 
 
 

 

 

Parameters setting (setup) 

x

While display is showing 

SETUP

, press  

.  

x

The display shows the first parameter code 

P-01

x

Short-click to move to next parameters 

P-02, P-03

… etc use 

x

When the display indicates the code of the parameter that needs to be 

modified, press 

.  

o

If it is a numeric parameter (password, thresholds, delays) the 
display shows its present value. The single digits are flashing 
sequentially. Pushing 

 while a digit is flashing, that digit is 

incremented. Waiting for some seconds, the selection moves to 
the next digit.   

o

If instead the parameters provides selection among different 
functions (e.g. output functions, measure etc), pressing 

 it is 

possible to sequentially select the desired one.  

o

Confirm with 

 

to go back to parameter code selection. 

x

After last parameter code, display shows 

--ESC--

.. Pressing button 

 

in this moment, parameters are saved and system goes back to normal 
operation.  

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

Содержание LAWN DME D121

Страница 1: ...correct wiring indication 3 Navigation with front key 3 Advanced functions 3 Parameter setting setup 4 Setup parameter table 5 Modbus addresses table 5 Mechanical dimensions mm 6 Wiring diagrams 6 Tec...

Страница 2: ...D colour and intensity are compliant with the reference standards that define its utilization in order to verify the accuracy of the energy meter Indicazione flusso di energia x Quando lo strumento st...

Страница 3: ...nella seguente lista Per passare da una scelta alla successiva premere x CLEAR P azzeramento contatori di energia parziali x CLEAR h azzeramento contaore parziale se abilitato x CLEAR d azzeramento ma...

Страница 4: ...le cifre lampeggiano a rotazione Premendo mentre una cifra sta lampeggiando essa viene incrementata Attendendo comincia a lampeggiare la cifra successiva o Se invece il parametro prevede la scelta fra...

Страница 5: ...ritardo per attivazione uscita Nota le misure vengono aggiornate ed integrate 1 volta al secondo quindi questo ritardo ha una variabilit da 0 a 1 secondo P 06 e P 07 Come sopra per disattivazione usci...

Страница 6: ...e device the measures listed in the following table Address Measure Word UoM 1A20h Total active energy 2 Wh 1A2Ah Partial active energy 2 Wh 1A24h Total reactive energy 2 Varh 1A2Eh Partial reactive e...

Страница 7: ...urti 10g IEC EN 60068 2 27 Shock resistance 10g IEC EN 60068 2 27 Resistenza alle vibrazioni 0 7g IEC EN 60068 2 6 Vibration resistance 0 7g IEC EN 60068 2 6 Ambiente meccanico Classe M1 Mechanical en...

Отзывы: