Receiving and Inspection

Carefully inspect the unit and accessories for any dam-

age and shortage immediately upon receipt of the unit.

• Turn the propeller by hand to ensure it turns freely and

does not bind.

• Record on the 

Delivery Receipt

 any visible sign of damage.

Handling

Lift the fan by the outside housing and support leg.

NOTICE! Never lift by the shaft, motor or housing.

Storage

If the fan is stored for any length of time prior to installa-

tion, store it in its original shipping crate and protect it from 

dust, debris and weather.

CV

Centri-Vane

®

 Aluminum Inline and Roof Fans

INSTALLATION, OPERATION AND MAINTENANCE MANUAL

CVB

Rotating Parts & Electrical Shock Hazard:

Fans should be installed and serviced by qualified person

-

nel only.
Disconnect electric power before working on unit (prior to 

removal of guards or entry into access doors).
Follow proper lockout/tagout procedures to ensure the unit 

cannot be energized while being installed or serviced.
A disconnect switch should be placed near the fan in order 

that the power can be swiftly cut off, in case of an emergen-

cy and in order that maintenance personnel are provided 

complete control of the power source.

Grounding  is  required.  All  field-installed  wiring  must  be 

completed by qualified personnel. All field installed wiring 

must comply with National Electric Code (NFPA 70) and all 

applicable local codes.
Fans and blowers create pressure at the discharge and 

vacuum at the inlet. This may cause objects to get pulled 

into the unit and objects to be propelled rapidly from the 

discharge. The discharge should always be directed in a 

safe direction and inlets should not be left unguarded. Any 

object pulled into the inlet will become a projectile capable 

of causing serious injury or death.
When air is allowed to move through a non-powered fan, 

the impeller can rotate, which is referred to as windmill-

ing. Windmilling will cause hazardous conditions due to 

unexpected rotation of components. Impellers should be 

blocked in position or air passages blocked to prevent draft 

when working on fans.
Friction and power loss inside rotating components will 

cause them to be a potential burn hazard. All components 

should be approached with caution and/or allowed to cool 

before contacting them for maintenance.
Under certain lighting conditions, rotating components may 

appear  stationary.  Components  should  be  verified  to  be 

stationary in a safe manner, before they come into contact 

with personnel, tools or clothing.
Failure to follow these instructions could result in death or 

serious injury.
The attachment of roof mounted fans to the roof curb as 

well as the attachment of roof curbs to the building struc-

ture must exceed the structural requirements based on the 

environmental loading derived from the applicable building 

code for the site. The local code official may require varia

-

tions from the recognized code based on local data. The 

licensed engineer of record will be responsible for prescrib-

ing the correct attachment based on construction materi-

als, code requirements and environmental effects specific 

to the installation.

®

This publication contains the installation, operation 

and maintenance instructions for standard units of the  

CV: Centri-Vane

®

 Aluminum Inline and Roof Fans

.

• CVD

• CVB

• CVR

• CVR-S

• CV/UCV-S 

•  CVS

Carefully read this publication and any

supplemental documents prior to any 

installation or maintenance procedure.

Loren Cook catalog, 

CV

, provides additional information 

describing the equipment, fan performance, available 

accessories and specification data.

For additional safety information, refer to AMCA Publica-

tion 410-96, 

Safety Practices for Users and Installers of 

Industrial and Commercial Fans

.

All of the publications listed above can be obtained from:

• lorencook.com

• [email protected]

• 417-869-6474 ext. 166

For information and instructions on special equipment, 

contact Loren Cook Company at 417-869-6474.

Содержание Centri-Vane CV Series

Страница 1: ...h is referred to as windmill ing Windmilling will cause hazardous conditions due to unexpected rotation of components Impellers should be blocked in position or air passages blocked to prevent draft w...

Страница 2: ...irt and moisture in the housing Periodically rotate the wheel and operate dampers if supplied to keep a coating of grease on all internal bearing parts Installation To prevent damage to the fan during...

Страница 3: ...n In variable speed units set the fan to its lowest speed Inspect for the following Direction of rotation Excessive vibration Unusual noise Bearing noise Improper belt alignment or tension listen for...

Страница 4: ...compatible grease such as Exxon Mobil Polyrex EM and Chevron SRI The above intervals should be reduced to half for vertical shaft installations Inspection Inspection of the fan should be conducted at...

Страница 5: ...l Puller This puller is available at most automotive parts retail outlets Motor Services Should the motor prove defective within a one year pe riod contact your local Loren Cook representative or your...

Страница 6: ...sure the fan rotates in same direction as the arrows on the motor or belt drive assembly Poor fan inlet conditions There should be a straight clear duct at the inlet Improper wheel alignment Excessive...

Страница 7: ...or Plate Saddle 9 Wheel Assembly 10 Bearing Plate 11 Outer Inlet Housing 12 Bearings CVR S 1 2 3 4 5 6 7 8 9 10 11 12 Air Flow Part No Part Description Sizes 10 36 1 Topcap Assembly 2 Post 3 Wheel Ass...

Страница 8: ...in worn condition or if the fan has been used other than for the uses described in the company manual This warranty does not cover defects resulting from normal wear and tear To make a warranty claim...

Отзывы: