Stove Installation
(for qualified installers only)
13
© Travis Industries
100-01177
4060802
Chimney Termination Requirements
•
Must have an approved cap (to prevent water from entering)
•
Must not be located where it will become plugged by snow or other material
•
Must terminate at least 3' above the roof
and
at least 2' above any portion of the roof within 10' (see
Figure 8)
Slanted Roofs
Flat Roofs
AA
A
A
A
Chimney must
extend 3'
above the roof
AAAAAAAAAAAAAAA
Chimney must extend 2'
above any portion of the roof
within 10' of the chimney
AA
AA
A
AA
AA
Chimney must
extend 3'
above the roof
Chimney must extend 2'
above any portion of the roof
within 10' of the chimney
Figure 8
Outside Air Requirements
•
Required for mobile homes and in certain localities (check with building officials)
•
Must not be drawn from an enclosed space (garage, unventilated crawl space)
•
Requires 3” aluminum duct (do not use plastic “dryer-vent”) and a hose-clamp for securing to the
stove. Maximum 4’ length. NOTE: A 10’ length is allowed if using 4” diameter duct (use a 3” to 4”
converter).
•
If using the optional blower, you may need to “ovalize” the duct to route it under the blower box.
AAAAA
3” Air Duct (max. 4’ length)
A screen is required to prevent
rodents from entering.
Outside air entrance must be placed so it
does not become blocked by snow.
Air may be drawn from a ventilated crawl space.