Installation
(for qualified installers only)
9
© Travis Industries
100-01280
4141215
Insert Placement Requirements
The insert must be placed so that no combustibles are within, or can swing within (e.g. drapes,
doors), 915mm of the front of the insert.
Insert and hearth must be installed on a level, secure floor.
The minimum clearances, facing, and hearth requirements in Figure 3 must be met.
Minimum Clearances
Masonry Fireplace
a Mantel
(combustible)
with Flue Shield
775mm
572mm
b Top Facing
(non-combustible)
with Flue Shield
724mm
521mm
c Side Facing
(non-combustible)
330mm
d Sidewall
381mm
Figure 3
Masonry Fireplace Requirements
Chimney must have a clay tile liner or a stainless steel liner (positive connection)
Entire fireplace, including chimney, must be clean and undamaged. Any damage must be repaired
prior to installation of the insert
Chimney height: 4.5m minimum; 10m maximum (measured from the base of the insert).
Entire fireplace, including chimney, must meet local building requirements
Drafting Performance
This appliance relies upon natural draft to operate. External forces, such as wind, barometric pressure,
topography, or factors of the home (negative pressure from exhaust fans, chimneys, air infiltration, etc.),
may adversely affect draft. Travis Industries cannot be responsible for external forces leading to less
than optimal performance.