Rear Panel Terminals
*
Note regarding Rate signal input and Count signal input:
The 2000CT is designed to accept a rate signal input and/or a count signal input and these can be supplied by two
different sensors or pulse sources. If only one signal source is to be used for both Rate and Count monitoring, then
simply connect the signal source to IPa (terminal 10) and fit a link from IPa to IPb (terminal 12).
Sensitivity Control
This is located to the right of the terminal block on the rear panel and is factory pre-set. However,
should it be necessary during on-site installation, adjustment is accessible through a hole in the rear
panel itself.
Maximum sensitivity is obtained when the Control is turned fully clockwise. It is recommended that
the sensitivity level is increased only as far as necessary to obtain a steady signal. This minimises
the risk of detecting spurious signals.
Alarm Outputs
The Alarm Output facility is available in the
RATE
mode only. The
HIGH
alarm will be activated when
the value shown on the display is equal to, or greater than, the value programmed into memory. The
LOW
alarm operates on a value equal to, or below, the programmed value.
The alarm outputs automatically reset when the value shown on the display returns to a “no alarm”
value.
Mains Earth
2000CT Counter/Tachometers
are supplied with a three core mains cable. The earth lead from this
cable is connected to terminal 4 ( ) on the Rear Panel terminal block. For most applications this
Earth terminal should be linked to 0V terminal 3 (COMMON) - see also
Exceptions to this are if the COMMON is connected to Earth elsewhere in the system (care must be
taken to avoid Earth loops); or it is found that the mains earth is of poor quality; or when it is essential
that the signal input or the analogue output of the instrument is floating.
2000CT-
MKII
_hb v3.1 01/2020
!
7
AL
Low Alarm
AH
High Alarm
0V
Signal Common
Connected directly to earth wire in mains cable
10V
10 to 13v @ 80mA (unregulated D.C. output for sensors)
Rst
Reset Input for TOTAL
M0
Protection input for Meter Factor
M1
Not used
0V
Common
IPa
Rate Signal input
*
0V
Common
IPb
Count Signal input
*
"