Additional Information 

Electromagnetic Precautions

 

Logitech

 

have  designed  in  a  great  deal  of  noise  immunity  into  the  product  in  accordance  with 

EN5001-2 and EN5002-2 (radiated emissions, conducted emissions, ESD, radiated susceptibility and 
fast burst transient testing)  

However it is still vital to use good EMC (Electromagnetic Compatibility) techniques on installation of 
both  this  and  other  associated  electronic  equipment  and  sensors  in  order  to  ensure  reliable 
operation. 

It is important to note that if used with systems that radiate high levels of harmonic noise such as DC 
Drives, AC  Inverters  and  Servo  Drives  then  the  levels  of  imposed  interference  can  greatly  exceed 
that of the European Standards.   

In such cases it is important to ensure that mains leads are routed as far as possible from all cables 
carrying power to such equipment and that the supply should, if viable, be taken from a clean source.   

Where this is not possible, it is advisable to use a good quality mains filter mounted as close to the 
instrument as possible, ensuring that the cable between the filter and the instrument is kept separate 
from any cables carrying high levels of current or any fast switching transients. 

All  signal  connections  to  the  instrument  should  be  made  using  screened  lead  with  the  screen 
connected to mains earth at one end only.   

Wherever possible, it is advisable to connect the 0V terminal to mains earth, unless it is found that 
the mains earth is of poor quality or when it is essential that the signal input is floating — see 

Mains 

Earth 

on page 7. 

Low Voltage Directive

 

It is essential that the mains supply to the instrument is fused externally to no more than 1A and that 
the cabling supplying power to the instrument is rated for at least 3A.   

Low voltage signal cables should not be run in the same conduit or twisted or tied to cables carrying 
voltages in excess of 50V (AC or DC). 

If the instrument is not installed fully in accordance with the instructions in this User Guide it may not 
comply with the requirements of the Low Voltage Directive.

 

2000CT-

MKII

_hb v3.1  01/2020 

 

 

 

 

!

16

Содержание 2000 MKII Series

Страница 1: ...2000 MKII SERIES Counter Tachometer Model 2000CT User Guide...

Страница 2: ...arameters 8 FACTOR 9 TOTAL Scaling Value 9 TOTAL Decimal Point Position 10 RATE Scaling Value 10 RATE Decimal Point Position 10 LOW Alarm 10 HIGH Alarm 10 Analogue Output Settings if O P module ordere...

Страница 3: ...al Signal Inputs Signal B count up Control Inputs Factor protection external Reset Control inputs Opto isolated requires sink to 0V of 220W maximum Outputs DC Voltage 10V nominal unregulated 80mA max...

Страница 4: ...of the total display and the rate display so that rate may be displayed as units per second units per minute units per hour milli units per second etc and total can be displayed as units milli units...

Страница 5: ...black Connect the brown wire to the terminal marked with the letter L or coloured red The mains supply to this instrument must be protected with a 1 Amp fuse Transformer Connections 2000 MKII SERIES...

Страница 6: ...RATE in which case the display will show NO SIG DP Decimal Point Switch This is located under the FUNC switch and is used to set the position of the decimal point as required A single depression of t...

Страница 7: ...hown on the display is equal to or greater than the value programmed into memory The LOW alarm operates on a value equal to or below the programmed value The alarm outputs automatically reset when the...

Страница 8: ...ion Other parameters that may need to be programmed are vi Low Alarm limit vii High alarm limit And if the analogue output option has been specified viii Reference ix Full Scale In order to program th...

Страница 9: ...ues that have been programmed prior to returning the instrument to the RUN mode Otherwise when the required values have been programmed press the RUN SET button once to switch the instrument to the RU...

Страница 10: ...ace to the left on each depression of the lower right hand button This sets the position of the decimal point in the display when RATE is being displayed see iii above vi Low Alarm ALA L When the calc...

Страница 11: ...from rate display to total display The unit will display TOTAL for one second followed by the current total count Note RATE is displayed using a maximum of six digits TOTAL is displayed using up to th...

Страница 12: ...reset prior to using the instrument with the revised programming to avoid the possibility of an incorrectly displayed value which has been held in memory from use with the previous settings Protection...

Страница 13: ...ams Front Panel Layout Note On instruments with the SINGLE switch set option only the FUNC switch is accessible unless the bezel and front panel are removed Rear panel layout 2000CT MKII_hb v3 1 01 20...

Страница 14: ...Connection Diagrams Typical Applications Variable reluctance Magnetic Pickups Single input operation Dual input operation 2000CT MKII_hb v3 1 01 2020 14...

Страница 15: ...Alarm Output Connections Alarm connections with external power supply 2000CT MKII_hb v3 1 01 2020 15...

Страница 16: ...advisable to use a good quality mains filter mounted as close to the instrument as possible ensuring that the cable between the filter and the instrument is kept separate from any cables carrying hig...

Страница 17: ...he warranty only extends to the original user Copyright Logitech Electronics Limited 1994 to 2017 Document No 2000CT MKII_hb v3 0 July 2017 2000CT MKII_hb v3 1 01 2020 17 Design and Manufacture of Ele...

Отзывы: