background image

 

Maintenance Service and Trouble Shooting   

 

refrigerating effect is due to the accumulation of refrigerating oil left in the 

 

evaporator tubing in case no other troubles have been found . To clear off 

 

refrigerating oil left in the evaporator ,dismantle the evaporator ,purge it 

 

thoroughly and then dry it .In case it is difficult    to    dismantle    it    ,charge 

 

refrigerant from the evaporator inlet to wash it several times ,then purge 

 

and dry it with nitrogen . 

 

7)      Flowing obstructed in refrigerating system 

 

Analysis of Trouble 

 

Because the refrigerating system was originally not purged 

 

thoroughly ,some of the filter screen meshes have been clogged by dirt 

 

accumulated in the filter after using it for a certain time of period ,thus 

 

resulting in a decrease in flow rate ,and hence a poorer refrigerating effect . 

 

The abnormal phenomena caused by this kind of slight clogging in the 

 

system are as follows: the gas discharge pressure is lower ,the 

 

temperature of discharged gas drops down ,the position clogged has a 

 

temperature lower than that in normal conditions ,and for a severe 

 

clogging ,even dew condensation as frosting may appear . 

 

Remedy 

 

Purge the tubing , and after replacing the dry filter with a new one or 

 

clearing it thoroughly ,recharge the system with refrigerant and seal the 

 

charging port . 

 

B.        No Refrigerating 

 

The phenomenon that the compressor runs normally , but no frost (or 

 

only a little frost ) appears on the evaporator ,and the refrigerator 

 

temperature does not drop down is called "no refrigerating". There are 

 

many causes for this trouble and it is relatively complicated , too . In 

 

servicing ,special attention to finding direct causes for this 

 

phenomenon .Three main potential causes for this trouble are analyzed 

 

below : 

 

1)    All refrigerant in the system has leaked out 

 

Analysis of Trouble 

 

Leak points in the refrigerating system have not been found and 

 

repaired timely ,thus resulting in the total escape of refrigerant .There are 

 

two kinds of leakage :I)

 slow leakage

 for instance ,when we want to use a 

 

refrigerator that has been put out of quite a long time ,we find the leakage 

 

of refrigerant ,or in the course of its operation ,we have found that the 

 

refrigerator is gradually becoming not so cold and finally no refrigerating 

 

cab be achieved ; ii)

    fast leakage

 in that case ,all the refrigerant will 

 

escape swiftly due to abrupt rupture of system tubing . 

 

Symptoms of total leakage of refrigerant are mainly asfollows : the 

 

compressor can be started easily (if there is no damage to the compressor 

 

parts) and its operating current becomes low ,its gas suction pressure is 

 

high and discharge pressure is lower ,the gas discharge tube feels rather 

 

cold ,no sound of gas eruption from the liquid in the evaporator can be 

 

 

20 

 

Содержание L200CFW14

Страница 1: ...Refrigerator Service Manual Models L200CFW14 Features Energy efficiency Micro foam technology Low noise operation Thick insulation for energy efficiency Latest No 2 micro biological technology 0...

Страница 2: ...code illumination and Series Introduction 2 3 Specifications 3 4 Safety precautions 4 5 Function Schedule 7 6 System Flow Chart 8 7 Circuit Diagram 9 8 Maintenance Service and Trouble Shooting 10 9 E...

Страница 3: ...CFW14 198 Color White Power Supply V Hz 220 240V 50HZ Rated Input Power W 90 Power Consumption kW h Y 219 Net Weight kg 35 Gross Weight kg Unit Dimension D W H mm Packing Dimension D W H mm Container...

Страница 4: ...Safety precautions Safety precautions 4...

Страница 5: ...Safety precautions 5...

Страница 6: ...Safety precautions 6...

Страница 7: ...Function Schedule Function Schedule Energy efficiency Micro foam technology Low noise operation Thick insulation for energy efficiency 7...

Страница 8: ...System Flow Chart System Flow Chart 1 Schematic diagram of System Flow Chart Flows in the sequence 1 2 3 4 5 1 8...

Страница 9: ...Circuit Diagram Circuit Diagram 1 Schematic Circuit Diagram 9...

Страница 10: ...ower NO Check and repair according to the section of the compessor doesn t work YES If compressor can run naturally and temperature raising of condenser is very low YES NO Refrigerant leak check and r...

Страница 11: ...capacity insufficient NO Check and repair according to the section of Cooling capacity is insuffcient YES 1 The thermostat was set at the coldest position 2 The ambient temperature is very high or th...

Страница 12: ...ing 3 Cooling capacity is insufficient Cooling capacity is insufficient Is the ambient YES temperature low than 16 C Check the therostat is correct YES NO Does the refrigerant leak siowly Adjust and i...

Страница 13: ...he power source and power cord NO Repair YES YES Is the ambient temperature low than 16 YES Check the therostat is correct Adjust and instruct consumer how to use Does the control panel has 220V power...

Страница 14: ...the pressure difference is still greater after the compressor has just stopped running the refrigerant will flow for a certain time therefore this sound is a normal phenomenon 2 A click sound can oft...

Страница 15: ...efrigerator locations and natures of troubles should be determined according to their respective features therefore experience in servicing is very important to troubleshooting Service technicians wit...

Страница 16: ...d by a sound similar to water flowing this is the sound produced by the normal circulation of refrigerant within the evaporator In case only the gas flowing sound can be heard and there is no water fl...

Страница 17: ...y due to a certain trouble With this method you can reject some suspicious troubles and finally make a correct judgment 7 Analysis of Troubles and Troubleshooting A Poor Refrigerating Effect The so ca...

Страница 18: ...essive refrigerant has been charged the liquid refrigerant that cannot evaporates in the evaporator will return to the compressor and thus a phenomenon of liquid striking will occur The liquid refrige...

Страница 19: ...ator regularly if you fail to do so the frost layer on the evaporator tubing will become thicker and thicker Heat conduction will be severely affected when the whole tubing is wrapped with a transpare...

Страница 20: ...rant and seal the charging port B No Refrigerating The phenomenon that the compressor runs normally but no frost or only a little frost appears on the evaporator and the refrigerator temperature does...

Страница 21: ...t these phenomena will appear intermittently sometimes the refrigerator works well and sometimes not well In order to determine whether it is clogged with ice heat the suspicious points with hot water...

Страница 22: ...gging with dirt 3 Troubles of Compressor a Breakage of gas suction and discharge valve blocks Analysis of Trouble The compressor works by means of the opening and closing of gas suction valve and disc...

Страница 23: ...he system Analysis of Trouble The residual air in the system will circulate together with the refrigerant in the system The major symptoms caused by this residual air is higher gas discharge pressure...

Страница 24: ...er supply c Abnormal thermal protection Analysis of Trouble The compressor current is within its normal range but the thermal protector actuates repeatedly Remedy Replace the thermal protector with a...

Страница 25: ...he user for buying a stabilizer so as to step up the voltage thus normal operation can be achieved 3 Check the thermal relay to see whether its contacts are closed Analysis of Trouble The contacts of...

Страница 26: ...caused mostly by poor lubrication such ad insufficient quantity of lubricant clogging in the lubricant oil line or intermittent lubricant oil supply Dirt and other impurities in the lubricant oil will...

Страница 27: ...rated value the thermostat won t work thus the compressor runs continuously When the evaporation temperature in the system is too high the temperature sensing agent in the temperature sensor is also h...

Страница 28: ...up intensively measure the resistance between the power cord plug and the case body with an avometer the reading will be zero 0 in the worst case the fuse will be blown Check the 3 prong outlet to se...

Страница 29: ...tion becomes weake or vanishes If the refrigerator has not been levelly placed put a level meter on its top table and adjust the leveling screws on its legs In case noise occurs from the compressor st...

Отзывы: