background image

LOFA EP250 Operation and Troubleshooting

463-3000-01 Rev C.1 - 28-Feb-2007

1

Introduction

This document provides general information on LOFA Industries EP250 control systems operation and

troubleshooting. EP250 control systems are a very flexible platform for diesel engine control, monitoring,

and protection, featuring LOFA’s powerful First Fault Diagnostics (FFD). After pinpointing the initial failure,
FFD stores it in memory and alerts the end user via a single bright LED. FFD monitors battery charge, low oil

pressure, high temperature, overspeed and up to three additional contact closure inputs. The field

configurable, expandable microprocessor-based solid-state design uses high-power semiconductors instead

of outdated electromechanical relays to ensure reliable high-current switching.

The EP250 features LOFA’s new modular Function Enhancement Packs (FEP). The plug-and-play FEP

modules allow various feature upgrades to be easily added to the standard platform. FEPs include:

Diagnostic Program Gauge (DPG)

Auto-Start with Real-time Clock

Data Logging

Closed Loop Speed Control

Precision Actuator Control

Custom OEM Solutions

The Diagnostic Program Gauge (DPG) features a backlit LCD display with three push buttons all in a

compact 2 inch gauge. The LCD is clearly readable in both bright sunlight as well as total darkness. The

DPG provides a complete user interface for other Function Enhancement Packs and allows each system to

be field configured to suit the customer's unique requirements. After configuring, the DPG can be removed
in cost-sensitive applications.

Some of the EP250 configurable features include:

Automatic preheat duration

Afterglow duration

Failure indication with shutdown or indication only

Over-speed shutdown

Normally open or normally closed shutdown switches

All standard panels include feature a 12 inch wiring harness terminating into a sealed weather proof plug.

This robust universal wiring connection performs well in harsh environments and allows interchanging a

number of different panels and harnesses. This design allows for simplified installation as well as a flexible

means to incorporate custom plug-and-play engine wiring harnesses and standard harness extension

Note

The engine harness is not included with the panel.

A number of standard engine harnesses are available or

LOFA can develop a custom harness for you exact needs.

Generic harnesses in various lengths are available for field customization.

Содержание EP250

Страница 1: ...ions The Diagnostic Program Gauge DPG features a backlit LCD display with three push buttons all in a compact 2 inch gauge The LCD is clearly readable in both bright sunlight as well as total darkness...

Страница 2: ...tions should be followed with any tool work method or operating procedure Improper procedures tools and materials may cause damage or make the equipment unsafe to operate Only persons with appropriate...

Страница 3: ...ngine is not started within 10 seconds of turning on the system the fuel run stop solenoid output is turned off to prevent battery discharge when the key switch is left in the run position The fuel ru...

Страница 4: ...e cold starting aids may require multiple relays Optional or additional components may allow preheat time to be modified by sensing ambient temperature Depending on specific configuration this output...

Страница 5: ...m typically senses high temperature from a ground contact switch on the engine When a sender switch combination is used on the engine the marking WK or W generally indicates the switch terminal This i...

Страница 6: ...n this indicates a problem with the solenoid circuit A battery voltage reading of approximately 14 volts on a 12 volt system 28 volts on a 24 volt system while the engine is running indicates the batt...

Страница 7: ...auge to read full scale pegged When using sender switch combinations swapping the WK and G terminal prevents the gauge from working and may cause unintended shutdowns Warning If the temperature sensor...

Страница 8: ...re removed Unsealed Connectors For unsealed connectors exposed to the elements LOFA recommends using dielectric grease to protect contacts Warning LOFA does not recommend using sealant with unsealed c...

Страница 9: ...exposed to high temperatures Warning Disconnecting the battery while the engine is running may damage electrical components When using a battery disconnect switch LOFA recommends using a 2 pole switc...

Страница 10: ...nded electrical environment practices Inductive devices such as relays solenoids and motors generate voltage transients and noise in electrical circuits Unsuppressed voltage transients can exceed SAE...

Страница 11: ...round the welder to electrical components such as the control ground or sensors Improper grounding can cause damage to electrical components Clamp the ground cable from the welder to the component bei...

Страница 12: ...se Possible Remedy Shutdown switch input active Verify shutdown source exists correct condition or correct faulty circuit Battery not charging Verify alternator charging see Alternator not charging ba...

Страница 13: ...ble Cause Possible Remedy Empty fuel tank Fuel engine Clogged filter Replace filter Air in fuel lines Bleed fuel lines Low fuel pressure Replace faulty fuel pump and or clogged filter Faulty fuel pump...

Страница 14: ...i e v belt coolant level or faulty switch correct wiring fault All normally closed shutdowns illuminate for one second control system reset Add suppressor diodes protect from nearby lightening strike...

Страница 15: ...and Troubleshooting 463 3000 01 Rev C 1 28 Feb 2007 15 Typical Schematics The following pages show typical schematics Details vary from installation to installation See the specific schematics for ins...

Страница 16: ...6 AWG Black MSS200 INTERFACE 1 2 3 4 5 6 7 8 9 10 11 12 13 14 1 2 3 4 5 6 2 3 X10 1 X6 X7 X8 30 31 31 30 50f 58 K1 30 K1 87a 31 K1 87 k1 87 K1 85 K4 87 K4 87a D W G 19 17 Sol2 Sol X9 X4 X3 X5 D Altern...

Страница 17: ...d Wiring Diagram Kubota Alternator Wiring Diagram Delco Alternator Wiring Diagram 14 AWG Purple To P1 H Note WK Switch G Gauge SW1 Aux 1 Shutdown J2 8 Pos White 1 2 3 4 5 6 7 8 J1 8 Pos Yellow 1 2 3 4...

Страница 18: ...9 10 11 12 13 14 50 50 Sol Temp PSI W Solenoid Aux Switch 1 Temp Switch Aux Switch 2 Pressure Switch Ground Ground Starter 50 Accessory 15 Tachometer Preheat Control Pressure Gauge Temp Gauge D Alter...

Страница 19: ...ram Note WK Switch G Gauge SW1 Aux 1 Shutdown SW2 Aux 2 Shutdown Indicator Only THE INFORMATION CONTAINED IN THIS DRAWING IS CONFIDENTIAL AND THE SOLE PROPERTY OF LOFA INDUSTRIES INC Reproduction or d...