background image

 

5

2  

Pre-installation

1.  The installation must conform to the instructions 
 

in this manual and all applicable local, state, 

 

provincial, and national codes, laws, regulations, and 

 

ordinances.  Installations in Canada must conform to 

 

B149.2 Installation Code.

2.  Be certain the domestic water supply to the tank has 
 

physical and chemical characteristics that fall within 

 

the limits shown in Table 2A. Where questions exist 

 

as to the composition of the water on the job, a 

 

qualified water treatment expert should be consulted.

Water with characteristics outside the 
limits shown in Table 2A may severely 
shorten the life of the tank due to 
corrosion.  Damage to tanks in such 
cases is not covered under warranty.

3.  Read and understand all installation requirements in 
 this 

manual.

Table 2A

Water Chemistry Requirements

Water used in the tank must have characteristics falling 
within the following limits:

Characteristic

Min.

Max.

Ph

6.0

8.0

Chloride (PPM)

--

80

 

CAUTION

Locating the Tank

1.  Choose a location for your water heater centralized to the 
 

piping system.  You must also locate the SDT/SET water 

 

heater where it will not be exposed to freezing temperatures. 

 

Additionally, you will need to place the water heater so that 

 

the controls, drain, and inlet/outlets are easily accessible. 

 

This appliance must not be installed outdoors, as it is 

 

certified as an indoor appliance, and must also be kept 

 

vertical on a level surface.

2.  Keep distance between boiler and water heater to a 
 minimum 

to:

 

a.  reduce piping heat loss

 

b.  provide minimal friction loss

3.  Figure 1-1 on page 4 shows the weights of all the tanks filled 
 

with water.  Make sure that the location chosen for the tank 

 

is capable of supporting it.

This appliance must be placed where leakage 
from the relief valve, leakage from the 
related piping, or leakage from the tank or 
connections, will not result in damage to the 
surrounding areas, or to the lower floors of 
the building.  A water heater should always 
be located in an area with a floor drain or 
installed in a drain pan suitable for water 
heaters.  Lochinvar shall not be held liable for 
any such water damage.

 

CAUTION

Failure to properly support the tank could 
result in property damage or personal injury.

 WARNING

4.  The tank may be located some distance from the boiler 
 

provided the pump is designed to provide the flow called 

 

for in Table 3B (page 7)- 

Pressure Drop Values

, through the 

 

coil. The further the tank is from the boiler, the longer the 

 

response of the boiler will be to a call from the tank zone.  

 

Insulate piping between the boiler and the tank.

Recommended Clearances

The installation location must provide adequate clearances for 
servicing and proper operation of the water heater.  A 12 inch 
vertical clearance is recommended from the top of the water 
heater.  A zero clearance is allowed for the sides of the water 
heater.  However, boiler, electrical, and servicing clearances 
must be figured when locating the water heater.

Minimum Clearance to the Element Cover

See FIG 2-1. Clearances must be a minimum of 24 inches to 
allow for element removal and replacement on SET model. 

        

SDT/SET

 

Installation & Operation Manual

24” MIN CLEARANCE FROM 

ELEMENT COVER

(SET Models)

Figure 2-1 Element Cover Clearances

Содержание SET080

Страница 1: ...al injury death or substantial property damage WARNING Save this manual for future reference SDT SET I O Rev D SDT Solar Dual Coil Tank SET Solar Electric Tank CAUTION The heat transfer medium must be water or other nontoxic fluid having a toxicity rating or class of 1 as listed in Clinical Toxicology of Commercial Products 5th edition The pressure of the heat transfer medium must be limited to a ...

Страница 2: ...ating Restrictions 4 Single Wall Heat Exchanger 4 2 PRE INSTALLATION Locating the Tank 5 Recommended Clearances 5 3 BOILER SIDE PIPING SDT MODELS Zone with Circulator to Aquastat 6 Zone with Valve to Aquastat 6 DHW Prioritization 6 Multiple Tank Connections Boiler Side 6 Table 3A 3B Pressure Drop Charts 7 Table 3C Pressure Drop Values 7 Piping Diagrams 8 11 4 DOMESTIC SIDE TANK PIPING Basic Domest...

Страница 3: ...ELL GAS Do not try to light any appliance Do not touch any electric switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified installer service agency or the gas supplier WARNING NOTICE WARNING ...

Страница 4: ... 16 60 1 8 60 1 8 59 7 8 69 3 8 59 7 8 68 3 16 69 3 8 68 3 16 59 7 8 59 7 8 59 7 8 N A N A N A 24 24 28 24 24 28 921 820 1268 921 820 1268 1 RELIEF VALVE CONNECTION 2 HOT WATER OUTLET 3 BOILER WATER IN 4 BOILER WATER OUT 5 DRAIN COLD WATER INLET 6 SOLAR WATER IN 7 SOLAR WATER OUT 8 ELEMENT I I 22 5 o 45 o SOLAR ELECTRIC SOLAR DUAL COIL 2 5 7 6 8 1 5 7 6 8 3 1 2 1 1 2 FPT 1 1 2 FPT 1 1 2 MPT 1 1 2 ...

Страница 5: ... provide minimal friction loss 3 Figure 1 1 on page 4 shows the weights of all the tanks filled with water Make sure that the location chosen for the tank is capable of supporting it This appliance must be placed where leakage from the relief valve leakage from the related piping or leakage from the tank or connections will not result in damage to the surrounding areas or to the lower floors of th...

Страница 6: ...traight heat job except that one of the zones goes to the tank instead of radiation As on any circulator zone system check valves should be installed in each zone to prevent unwanted circulation through zones which are not calling for heat Figure 3 1 on page 8 illustrates typical circulator zone piping Zone with Valve to Aquastat As with the circulator zone system this system is just like a standa...

Страница 7: ... GPM 8 GPM 12 GPM 16 GPM 20 GPM SDT065 1 41 5 13 5 0 61 1 57 3 53 6 27 9 8 28 9 2 0 4 1 03 2 31 4 1 6 41 SDT080 1 41 5 13 5 0 61 1 57 3 53 6 27 9 8 28 9 2 0 4 1 03 2 31 4 1 6 41 SDT119 1 67 3 22 0 73 1 87 4 22 7 5 11 71 48 5 16 0 61 1 57 3 53 6 27 9 8 SET065 1 41 5 13 5 0 61 1 57 3 53 6 27 9 8 SET080 1 41 5 13 5 0 61 1 57 3 53 6 27 9 8 SET119 1 67 3 22 0 73 1 87 4 22 7 5 11 71 3 Boiler Side Piping...

Страница 8: ... SCALD MIXING VALVE RECIRCULATION PUMP TEMPERATURE PRESSURE RELIEF VALVE TEMPERATURE PRESSURE GAUGE TYPICAL GAS SUPPLY CHECK VALVE BOILER TANK SENSOR AQUASTAT SOLAR SENSOR AUXILIARY CATCH PAN CHECK VALVE DRAIN FROM SOLAR TO SOLAR SOLAR HEAT EXCHANGER BOILER BACKUP HEAT EXCHANGER SDT MODELS ONLY ZONE 2 ZONE 3 ZONE 4 Figure 3 1 Piping Diagram Zoned with Circulators Please note that these illustratio...

Страница 9: ...ERATURE PRESSURE RELIEF VALVE TEMPERATURE PRESSURE GAUGE TYPICAL SOLAR HEAT EXCHANGER GAS SUPPLY CHECK VALVE BOILER TANK SENSOR AQUASTAT SOLAR SENSOR AUXILIARY CATCH PAN CHECK VALVE DRAIN FROM SOLAR TO SOLAR ZONE VALVES TYPICAL DIFFERENTIAL PRESSURE BYPASS VALVE IF USED SYSTEM CIRCULATOR BOILER BACKUP HEAT EXCHANGER SDT MODELS ONLY Figure 3 2 Piping Diagram Zoned with Valves Please note that these...

Страница 10: ...TEM CIRCULATOR TO SYSTEM SYSTEM SUPPLY SENSOR DRAIN DRAIN FIELD SUPPLY RECIRCULATION PUMP BOILER TANK SENSOR AQUASTAT Y STRAINER RECOMMENDED HOT WATER OUT CHECK VALVE SQUIRE SOLAR SENSOR FROM SOLAR TO SOLAR TEMPERATURE PRESSURE RELIEF VALVE CHECK VALVE SOLAR HEAT EXCHANGER TEMPERATURE PRESSURE GAUGE TYPICAL BOILER BACKUP HEAT EXCHANGER SDT MODELS ONLY Figure 3 3 Knight Boiler Primary Secondary Pip...

Страница 11: ... TYPICAL RECIRCULATION PUMP TO SOLAR FROM SOLAR TEMPERATURE PRESSURE GAUGE TYPICAL SOLAR SENSOR CHECK VALVE BOILER TANK SENSOR AQUASTAT TEMPERATURE PRESSURE RELIEF VALVE COLD WATER IN ANTI SCALD MIXING VALVE HOT WATER OUT DOMESTIC HOT WATER CIRCULATOR BOILER CIRCULATOR Y STRAINER RECOMMENDED NOT TO EXCEED 4 PIPE DIA OR A MAXIMUM OF 12 APART FROM SYSTEM Figure 3 4 Multiple Tank Connections Please n...

Страница 12: ...verse return piping layout see FIG 3 4 Each tank must have its own T P valve It is recommended that each tank be equipped with its own isolation valves unions and drains so that one tank may be removed from the system If local codes require a backflow preventer check with the appropriate authority to find out whether one backflow preventer may be used for tanks or each tank must be equipped with i...

Страница 13: ...es used with water heaters are also called tempering valves or mixing valves An anti scald valve mixes cold water in with the outgoing hot water to assure that hot water reaching a building fixture is at a temperature low enough to be safe ASSE1017 and ASSE1070 certified valves are recommended Usually the maximum temperature of the outlet water will stay near the setting of the tank control In som...

Страница 14: ...sing more than two 2 elbows or 15 feet of piping can reduce discharge capacity directly connected to a drain Refer to local codes subject to freezing WARNING Do not install any valve between the T P relief valve and the tank connection or on the T P relief valve discharge piping Improper placement and piping of T P relief valve can cause severe personal injury death or substantial property damage ...

Страница 15: ... TEMPERATURE PRESSURE GAUGE TYPICAL CHECK VALVE DRAIN FROM SOLAR TO SOLAR SOLAR SENSOR SOLAR HEAT EXCHANGER BOILER BACKUP HEAT EXCHANGER SDT MODELS ONLY SDT MODELS ONLY NOTE UPPER COIL REPLACED WITH ELEMENT ON SET MODELS Figure 4 2 Recommended Domestic Water Piping SDT SET models Please note that these illustrations are meant to show system piping concept only the installer is responsible for all ...

Страница 16: ...t The 4500 watt heating element in the Squire SET is wired to the junction box on top of the heater and it requires 240 volt A C electrical service The voltage requirement and wattage load for the heater is also specified on the heater identification plate A 1 2 E M T opening located on top of the unit is provided for a field wiring connection Consult an electrician to determine if your electrical...

Страница 17: ...RMOSTAT LINE VOLTAGE FIELD SUPPLIED FACTORY INSTALLED SET Wiring Single Element Model Volts Phase Watts AMPS Breaker Type Wire Gage SET065 240 VAC 1 Ph 4500 18 3 25 AMP DPDT 12 ga THHW SET080 240 VAC 1 Ph 4500 18 3 25 AMP DPDT 12 ga THHW SET119 240 VAC 1 Ph 4500 18 3 25 AMP DPDT 12 ga THHW Rated for 90 C Table 5A Wiring SET065 SET119 SDT SET Installation Operation Manual ...

Страница 18: ...ank sensor inside the tank as depicted in FIG 5 3 2 Connect the wire leads to the DHW tank sensor AUX connection point on the Knight boiler connection board see FIG 5 3 3 The Knight boiler will automatically read the sensor and default the tank temperature settings to 125 F 4 Adjust the tank set point program Reference the Knight Installation and Operation manual for a detailed explanation of the ...

Страница 19: ...ROL BOX OR ZONE VALVE OR ZONE CIRCULATOR WIRE CONNECTIONS SOLAR SENSOR FIELD SUPPLIED BOILER AQUASTAT CONTROL TST20016 Figure 5 4 Wiring for Zone Control 1 Install Aquastat to tank Aquastat control TST20016 can be ordered from your local Lochinvar distributor 2 Connect Aquastat to the zone controller for the Indirect Water Heater Zone 3 Adjust Aquastat to the desired temperature ...

Страница 20: ...used for an extended period of time after installation Flush the indirect water heater by drawing at least three times its volume from the tank 3 Make sure that all electrical connections are made correctly and that no high voltage wiring is exposed 4 Make sure that each zone valve or circulator operates only when its thermostat calls for heat Let each zone operate long enough to purge any remaini...

Страница 21: ...o allow air to escape from the system 4 When a steady stream of water flows from the faucets the water heater is filled Close the faucets and check for water leaks at the water heater drain valve combination temperature and pressure relief valve and the hot and cold water connections DANGER Plugging the T P relief valve or discharge piping can cause excessive pressure in the water heater resulting...

Страница 22: ...uired FHR This will also determine the flow needed between the indirect water heater and boiler Table 8A SET Backup Recovery Performance Model Heat Exchanger Volume Gallons Heated Water Volume Gallons Recovery Back Up Minutes First Draw Gallons Solar 65 F Rise 90 F Rise 115 F 140 F SET065 2 2 28 78 108 34 26 SET080 2 2 35 89 123 44 31 SET119 3 2 44 120 166 55 42 Model Heat Exchanger Volume Gallons...

Страница 23: ...385 288 413 308 475 351 260 000 295 218 306 227 475 351 295 000 475 351 MAX BTU INPUT 90256 106525 118352 131827 139966 90257 106525 118352 131827 139967 123218 148780 171607 185675 217372 Boiler Heating Capacity Model SDT065 SDT080 SDT119 23 8 Performance Data continued Table 8C First Hour Rating 180 F Boiler Loop Water Knight and Wall Mount Boilers Upper Coil SDT Models First Hour Rating 180 F B...

Страница 24: ...252 193 252 193 252 193 252 193 270 208 243 187 243 187 268 210 268 210 268 210 140 000 265 203 283 216 283 216 283 216 283 216 270 208 286 220 286 220 286 220 315 245 315 245 315 245 315 245 165 000 265 203 305 232 328 249 328 249 328 249 270 208 310 237 333 254 333 254 333 254 357 276 362 279 362 279 362 279 362 279 195 000 265 203 305 232 334 253 349 265 369 279 270 208 310 237 339 258 367 279 ...

Страница 25: ... the boiler water OUT and the solar water IN are connected This will join the boiler and soiler coils together The return water is piped from the solar return to the solar boiler supply See FIG 9 1 on page 26 NOTICE For tank operation use the lower bulbwell to turn the tank on and off Parallel Piping With this style of installation both heat exchanger are used at the same time Solar boiler supply ...

Страница 26: ...L TEMPERATURE PRESSURE GAUGE DRAIN PRESSURE RELIEF VALVE KNIGHT BOILER SQUIRE SOLAR HEAT EXCHANGER DRAIN FIELD SUPPLY CHECK VALVE RECIRCULATION PUMP Figure 9 1 Indirect Boiler with Series Piping Please note that these illustrations are meant to show system piping concept only the installer is responsible for all equipment and detailing required by local codes NOTICE Table 9A Series Configuration M...

Страница 27: ...N POINT TYPICAL EXPANSION TANK SYSTEM CIRCULATOR BALL VALVE TYPICAL Figure 9 2 Indirect Boiler with Parallel Piping Please note that these illustrations are meant to show system piping concept only the installer is responsible for all equipment and detailing required by local codes NOTICE Table 9D SDT Parallel Friction Loss Table 9C Parallel Configuration Model Boiler Flow GPM Boiler Loop Temperat...

Страница 28: ...rallel on pages 26 and 27 Revision C ECO C06300 reflects the update of tank images and additional CSA cautions on manual cover Connect tank sensor section added to Wiring section on page 18 and tank temperature statement with correction of piping diagram headers and table 9A and 9C on pages 26 and 27 Revision D ECO C10301 reflects the update of series and parallel piping information on pages 26 an...

Отзывы: