background image

>

 Low Voltage Terminal Strip

 

>

 24 VAC Auxiliary Device Relay 

 

>

 Auxiliary Proving Switch Contacts

 

>

 Flow Switch Contacts

 

>

 Alarm on Any Failure Contacts

 

>

 Runtime Contacts

 

>

 DHW Thermostat Contacts

 

>

 Room Thermostat Contacts

 

>

 System Sensor Contacts

 

>

 DHW Tank Sensor Contacts

 

>

 Outdoor Air Sensor Contacts

 

>

 Cascade Contacts

 

>

 0-10 VDC BMS External Control Contact

Optional Equipment 

>

 

Alarm Bell on Any Failure

>

 

Condensate Neutralization Kit

>

 

High & Low Gas Pressure Switches w/ Manual

   Reset (KB500-KB800)

>

 

Low Water Cutoff w/Manual Reset & Test

>

 

SMART SYSTEM PC Software

>

 

Stainless Steel Vent Kits (KB700-KB800)

>

 

Multi-Stack Frame

Firing Codes 

>

 

M9 Standard 

Construction

>

 

M7 California 

Code

>

 

M13 

CSD1 / FM / GE Gap (KB500-KB800)

Standard Features

>

 Up to 94.6% Thermal Efficiency

>

 Modulating Burner with 5:1 Turndown

 

>

 Direct-Spark Ignition

 

>

 Low NOx Operation

 

>

 Sealed Combustion

 

>

 Low Gas Pressure Operation

>

 Vertical & Horizontal Direct-Vent

 

 

>

 Category IV venting up to 100 feet

 

>

 PVC, CPVC or AL29-4C Venting up to 100 Feet

 

>

 Factory Supplied Sidewall Vent Termination

>

 ASME Stainless Steel Heat Exchanger

 

>

 ASME Certified, ”H” Stamped

 

>

 Gasketless Heat Exchanger

 

>

 160 psi Working Pressure

 

>

 Highly efficient, condensing design

>

 On/Off Switch

>

 Adjustable High Limit w/ Manual Reset

>

 Flow Switch

>

 Inlet & Outlet Temperature Sensors

>

 Flue Temperature Sensor

>

 Low Air Pressure Switch

>

 50 psi ASME Relief Valve

>

 Temperature & Pressure Gauge

>

 Adjustable Leveling Legs

>

 Condensate Trap

>

 Zero Clearances to Combustible Material

>

 10 Year Limited Warranty

  (See Warranty for Details)

Smart System Features

>

 SMART SYSTEM Digital Operating Control

 

>

 2 line, 16 Character Display

 

>

 Dual Level Password Security  

 

>

 Domestic Hot Water Prioritization    

 

>

 Built in Cascading Sequencer for up to 8 Boilers

 

>

 Building Management System Integration

     with 0-10 VDC Input
 

>

 Outdoor Reset Control with Outdoor Air Sensor

 

>

 Low Water Flow Safety Control & Indication

 

>

 Inlet & Outlet Temperature Readout

 

>

 Freeze Protection   

 

>

 Service Reminder   

 

>

 Time Clock

>

 Data Logging

 

>

 Hours Running, Space Heating

 

>

 Hours Running, Domestic Hot Water

 

>

 Ignition Attempts

 

>

 Last 10 Lockouts

>

 Programmable System Efficiency Optimizers

 

>

 Night Setback 

 

>

 Anti-Cycling

 

>

 Outdoor Air Reset Curve

 

>

 Ramp Delay

 

>

 Boost Temperature & Time

>

 Three Pump Control

 

 

>

 System Pump

 

>

 Boiler Pump

 

>

 Domestic Hot Water Pump

>

 High Voltage Terminal Strip

 

>

 120 VAC / 50-60 Hertz / 1 Phase Power Supply

 

>

 Three sets of Pump Contacts with Pump Relays

KBX-

03

  (Replaces KBX-02  6/08)

5M-4/09-Printed in U.S.A.

3 0 0   M a d d o x   S i m p s o n   P a r k w a y,   L e b a n o n,   T N     3 7 0 9 0       |       6 1 5 - 8 8 9 - 8 9 0 0       |       f a x :   6 1 5 - 5 4 7 - 1 0 0 0       |       w w w . l o c h i n v a r .c o m

Knight

®

 XL Boiler Dimensions and Specifications

Model Number Guide

KB         N       700         M13

Model

Firing Controls

Natural Gas

Btu/hr Input

  

Input 

  

 

Net

 Model 

Min  

Max 

Thermal 

Output I=B=R

Number MBH  MBH Efficiency 

MBH 

MBH

KBN399 80 399 93.3% 

372 

324

KBN500 100 500  93.3% 

467 

406

KBN600 120 600  94.6% 

567 

493

KBN700 140 700  94.3% 

660 

574

KBN800 160 800  94.0% 

752 

654

 

 

 

 

 

 

 

 

 

 

 

 

 A 

D  E 

F  G  H 

K  Gas 

Water Air Vent 

Shipping

 

 

 

 

 

 

 

 

 

 

 

  

Conn.  Conn.   Inlet  Size    Wt. (lbs.)

  42-1/2” 

15-1/2” 

27-3/4”      3-3/4”  20-3/4”      21” 

14”      34”     

34”     

2”     

18-3/4” 

1”      1-1/2”  4” 

4” 

280

  42-1/2” 

15-1/2” 

31-1/4”  3-3/4”  25-1/2”      21”      14”      32-1/2”  36”    

2”     

18”     

1”      1-1/2”  4” 

4” 

310

  42-1/2” 

15-1/2” 

36-1/4”  3-3/4”  25”     

21”      14”      36”     

32-3/4”  5-1/2”  19-1/2” 

1” 

2”     

4” 

4” 

340

  42-1/2” 

15-1/2” 

40-1/4”  3-3/4”    29”     

23”      17”      36”     

32-3/4”  3-1/4”  23-1/2” 

1” 

2”     

4” 

6” 

370

  42-1/2” 

15-1/2” 

45-1/4”  3-3/4”  33-1/4”      23” 

17”      36”     

32-3/4”  3-1/4”  27-3/4” 

1” 

2”     

4” 

6” 

405

Notes: Change ‘N’ to ‘L’ for L.P. Gas Model.  No deration on L.P. models.     Performance data based on manufacturer test results.     120 VAC /15 AMP circuit required. 

All dimensions shown in inches. 

Knight XL Heating Boiler

Dimensions and Specifications

K

night 

XL

 

B

oiler, 

N

atural Gas,

700

,000 Btu/hr input,

M13

 firing controls

>

 Mo

>

Di

>

Lo

>

Se

>

Lo

>

 Ver

>

Ca

>

PV

>

Fa

>

 ASM

>

AS

>

Ga

>

16

>

Hi

>

 On/

>

 Adj

>

 Flow

>

 Inle

>

 Flue

>

 Low

>

 50 

>

 Tem

>

 Adj

>

 Con

>

 Zer

>

 10 

  (Se

KBX-

0

3 0 0  

  

Input 

  

 

Net

nput

et

 Model Min  

Max Thermal 

Output I=B=R

odel

a

e al

Output

Number MBH

MBH Efficiency

MBH

MBH

 A 

B C D 

E F G H I J 

 

Knight XL Heating Boiler

Dimensions and Specifications

LEFT SIDE

FRONT

BACK

8"

39-1/2"

13-3/4"

18-3/4"

H

K

D

G

F

E

C

9"

A

1-1/4"

1/4" - 

ADJUSTABLE

AIR INLET

FLUE

LOW VOLTAGE

ELECTRICAL

CONNECTIONS

GAS

INLET

OUTLET

HEAT

EXCHANGER

DRAIN

3/4" NPT

CONDENSATE

DRAIN

FLUE

B

I

J

HIGH VOLTAGE

ELECTRICAL

CONNECTIONS

38-3/4"

3-1/2"

Patent # 7,506,617

Отзывы: