background image

Service Manual

19

1  

Service 

(continued)

Viewable and changeable control parameters

A: General

Date and Time 

The control uses an internal clock for the night setback
feature and for logging of events.  For these features to work
correctly, the clock must be set when the boiler is first
installed or anytime the boiler has been powered off for more
than four (4) hours.  To set the clock, parameter 

A1 

must be

accessed.  

Software Version

The software version allows the user to view the software
version in use by the control.  This software controls the
operation of the boiler.  When a new software version
becomes available, the existing control can be replaced with a
new control to update the software.

Software version is read only.

Temperature units (°C / °F)

The control can be configured to display temperature in
either °C or °F.  This parameter can be changed by the user or
the installer by accessing parameter 

A3

.  The default is °F.

Space Heating (SH)  and Domestic Hot Water (DHW)
Night Setback Offset

The unit’s internal clock can be set up to run at a lower set
point temperature during unoccupied times.  Both the space
heating and DHW can be programmed for night setback.
When in night setback, the control reduces the set point by a
fixed amount.  For space heating, it subtracts the space
heating night setback offset from each of the SH user set
points (parameters 

B1

B6

, and 

B9

), or the calculated outdoor

reset set point (if lower).  For DHW, it subtracts the DHW
night setback offset from the tank set point (parameter 

E2

).  

NOTE:  

The DHW night setback will not work without a tank

sensor installed.  

The installer may adjust the space heating night setback offset
by accessing 

A4

and the DHW night setback offset by

accessing parameter 

A7

.  The minimum setting is 0°F (0°C)

and the maximum setting is 90°F (50°C).

Space Heating (SH) and Domestic Hot Water (DHW)
Night Setback On Times

This is the time in which the SH Night Setback Offset becomes
active.  There are 7 start times and 7 stop times each for the
space heating and DHW night setback features.  Both may be set
to any time within a 7-day week.  These settings are referred to
as triggers.  Multiple start or stop triggers may be set within a
single day, if desired.  When a start trigger and a stop trigger are
set to the same time, the stop trigger has priority.  The installer
may adjust the space heating night setback start triggers by
accessing parameter 

A5

.  The DHW start triggers in parameter

A8

.  This screen shows the start trigger number, the day of the

week, and the time of day.  

1.

When the screen is first accessed, start trigger number 1 
is shown.  If a different trigger number is desired, the 
installer can rotate the NAVIGATION dial until the desired 
trigger number is displayed.  Once the desired trigger 
number is selected, the installer can press the SCROLL 
knob and the day of the week will start to flash.  

2.

The installer can adjust the day of the week to the one he 
wishes to set.  Once the day is set, the installer can press the 
NAVIGATION dial and the hour will begin to flash.  

3.

After setting the hour, the installer can press the SCROLL 
knob and the minutes will flash. Once all settings have been 
made, the installer can press the RIGHT SELECT [SAVE] 
key.  The installer can now select a different trigger and 
adjust the settings for that trigger.

4.

Once all adjustments are made, the installer can press the 
RIGHT SELECT [SAVE] key to save all of the new settings 
and return to the 

A

menu, or press the LEFT SELECT 

[EXIT] key to return to the 

A

menu without saving the 

changes. 

Space Heating (SH) and Domestic Hot Water (DHW)
Night Setback Off Times

The corresponding space heating night setback stop triggers are
set by accessing parameter 

A6

.  The stop triggers for the DHW

night setback feature can be adjusted by accessing parameter 

A9

.

The adjustment procedure for these parameters is identical to
the space heating start triggers described above.

CAUTION

Before changing parameters, note the
settings so that the unit can be returned to
its original operating parameters.

NOTICE

The internal clock does not adjust for
Daylight Savings Time and therefore,
will require a manual adjustment.

Please note that the brackets ([]) denote
screen status.

NOTICE

Содержание Knight 151 - 211

Страница 1: ...Read all instructions including this manual and the Knight Wall Mount Installation and Operation Manual before installing Perform steps in the order given Failure to comply could result in severe per...

Страница 2: ...t not related to personal injury or property damage CONTENTS 2 Hazard Definitions 2 PLEASE READ BEFORE PROCEEDING 3 Handling Ceramic Fiber Materials 3 When servicing boiler 4 Boiler operation 4 Boiler...

Страница 3: ...Cancer IARC has concluded Crystalline silica in the form of quartz or cristobalite from occupational sources is carcinogenic to humans Group 1 Normal operating temperatures in this appliance are below...

Страница 4: ...ve sediment The high efficiency heat exchanger can be damaged by build up or corrosion due to sediment Do not use petroleum based cleaning or sealing compounds in the boiler system Gaskets and seals i...

Страница 5: ...l mount boiler operation A General B Temperature Setting C Data Logging D Functions E DHW Settings F Outdoor Reset G Anti cycling H Control Modes I Circulation Pumps J Building Management System BMS K...

Страница 6: ...T WATER TANK TO FLOOR DRAIN AIR SEPARATOR EXPANSION TANK SYSTEM SENSOR Near boiler piping This piping reference is included to specify the Near Boiler Piping specific to the Knight wall mount boiler T...

Страница 7: ...IAL The Knight wall mount display The information on the bottom of the display shows the functions of the two SELECT keys on either corner and the NAVIGATION dial in the center MENU Left SELECT Key SE...

Страница 8: ...TEM SENSOR OUTDOOR SENSOR BUILDING MANAGEMENT SYSTEM LOW VOLTAGE CONNECTION BOARD INLET TEMPERATURE SENSOR OUTLET TEMPERATURE HIGH LIMIT SENSOR FLUE GAS SENSOR FLAME SENSOR LOW WATER CUTOFF BLOCKED DR...

Страница 9: ...e continued LOW VOLTAGE CONNECTION BOARD SMART CONTROL MODULE ALARM BELL AUX DEVICE RELAY RUN TIME CONTACTS BUILDING MANAGEMENT SYSTEM BOILER PUMP SYSTEM PUMP DHW PUMP IGNITOR BLOWER GAS VALVE DISPLAY...

Страница 10: ...r return water temperature or system supply temperature depending on the parameter setting Sequence of operation Table 1 1 shows control module normal sequences of operation for space heating and DHW...

Страница 11: ...itch must close 4 The control starts a 15 second prepurge cycle by initiating the blower 5 The control starts a 4 second trial for ignition by firing the spark electrode and opening the gas valve 6 If...

Страница 12: ...ill then modulate to maintain the outlet 9 If the boiler is not part of a Cascade and both the space heating and DHW calls for heat remain active long enough the boiler will switch back and forth betw...

Страница 13: ...the LEFT SELECT soft key MENU for five 5 seconds Rotate the NAVIGATION dial clockwise until 5 is displayed first digit on the left Press the NAVIGATION dial to select the next digit Rotate the NAVIGAT...

Страница 14: ...of the menu listings after entering the installer access code Rotate the NAVIGATION dial counterclockwise until the arrow is next to TEMPERATURE SETTINGS Press the NAVIGATION dial one time Rotate the...

Страница 15: ...Times 19 No No Yes Yes 10 Display Timeout 20 No No Yes Yes B 1 SH1 Set Point 20 Yes Yes No No 2 Minimum SH Set Point 20 No No Yes Yes 3 Maximum SH Set Point 20 No No Yes Yes 4 SH1 Offset Set Point 20...

Страница 16: ...ing for Indirect DHW Tank 21 No No Yes Yes F 1 Low Outdoor Temperature 22 No No Yes Yes 2 High Outdoor Temperature 22 No No Yes Yes 3 SH1 Set Point at Low Outdoor Temp 22 No No Yes Yes 4 SH1 Set Point...

Страница 17: ...7 Cascade Type L L EFF 25 No No Yes Yes 8 Max Cascade Outlet Set Point 25 No No Yes Yes 9 Cascade Offset 25 No No Yes Yes 10 Cascade Off On Differential 25 No No Yes Yes 11 Min On Off Time 25 No No Ye...

Страница 18: ...No No Yes Yes 7 Set Point at Max Volts 27 No No Yes Yes 8 On Volts 27 No No Yes Yes 9 Off Differential Volts 27 No No Yes Yes K 1 Service Notification Months 27 No No Yes Yes 2 Service Notification R...

Страница 19: ...ating and DHW night setback features Both may be set to any time within a 7 day week These settings are referred to as triggers Multiple start or stop triggers may be set within a single day if desire...

Страница 20: ...er turns back off The installer can adjust this differential by accessing parameter D4 The minimum setting is 0 F and the maximum is 20 F The default setting is 5 F 2 8 C Display Timeout This is the t...

Страница 21: ...to the DHW demand The installer can adjust the length of time the boiler will service the space heating demand by accessing parameter E6 The minimum setting is 0 minutes and the maximum setting is 200...

Страница 22: ...lue is 70 F 21 C SH1 SH3 Set Point at Low Outdoor Temperature When the outdoor air temperature drops below this point the water temperature will be at this setting FIG 1 1 However if the user set poin...

Страница 23: ...temperature range of this parameter is 0 F 0 C to 90 F 50 C The default value is 10 F 6 C Shift Reset Curve SH1 SH3 There is a shift reset curve for each outdoor reset The shift reset curve parameter...

Страница 24: ...put in the case of 0 10V BMS control or the 0 10V input value received through ModBus The default value is INACTIVE Figure 1 2 Ramp Delay Interval When finished the installer can press the RIGHT SELEC...

Страница 25: ...the first boiler reaches a certain rate default 90 it lowers its rate to 45 and turns on the next boiler at 45 The two 2 boilers then modulate at the same rate As the calculated load increases furthe...

Страница 26: ...imum is 100 The default value is 100 I Circulation pumps System Pump Delay The system pump delay parameter sets the length of time the system pump if connected will run after a SH demand has been sati...

Страница 27: ...adjustable by the installer by accessing parameter K2 The time range for this parameter is 0 hours to 100 000 hours The default time is 8 760 hours Service Notification Cycles When the boiler control...

Страница 28: ...t Installation and Operation Manual Flame inspection stable uniform Flame signal at least 10 microamps at high fire Clean the heat exchanger if flue temperature is more than 54 F above return water te...

Страница 29: ...1 of the Knight Wall Mount Installation and Operation Manual If any of these are present in the boiler intake air vicinity they must be removed If they cannot be removed reinstall the air and vent lin...

Страница 30: ...night Wall Mount Installation and Operation Manual before proceeding further Safety relief valves should be re inspected AT LEAST ONCE EVERY THREE YEARS by a licensed plumbing contractor or authorized...

Страница 31: ...edures 2 Check settings of external limit controls if any and adjust if necessary Perform start up and checks 1 Start boiler and perform checks and tests specified in Section 10 Start up of the Knight...

Страница 32: ...hanger Cleaning Kits Model Kit Number Part Number Component Description 51 106 KIT30062 CTN20005 Rear Refractory Cover MSC20083 Nylon 4 Wheel Brush MSC20085 1 4 x 12 Drill Extension 151 211 KIT30063 C...

Страница 33: ...lockup or with boiler on Minimum 4 inches w c natural 8 inches w c LP with gas flowing verify during boiler startup Check control module fuses ALWAYS check control module fuses before replacing contro...

Страница 34: ...e thermostat satisfied Review remote thermostat setting Outside air temperature above Warm Weather Shutdown WWSD set point for main control board Check location of outside air sensor Check resistance...

Страница 35: ...mportant to note that the flue and outlet water sensors have two temperature sensing devices in one housing These devices are designated as S1a S1b outlet sensor and S3a S3b flue sensor Please referen...

Страница 36: ...Clean or replace the burner as necessary Low water flow through the heat exchanger Refer to Section 6 Hydronic Piping of the Knight Wall Mount Boiler Installation and Operation Manual for minimum flow...

Страница 37: ...k for loose or misplaced jumpers if flow switch or LWCO is not installed Blown fuse Replace fuse F3 on the control board see page 33 of this manual Blocked Drain SW will require a manual reset once co...

Страница 38: ...ly Verify that the plastic hose from the gas valve to the air inlet is connected and is not damaged Verify that the vent air intake pipes are correctly installed and that there are no obstructions Che...

Страница 39: ...voltage is not present check wiring back to the main control board Replace the main control board if necessary If 120 vac is present on a call for heat and the boiler pump is not operating replace the...

Страница 40: ...in control board Replace the fan Replace the main control board Sensor Open will require a manual reset once the condition has been corrected Press the RESET button on the SMART SYSTEM display to rese...

Страница 41: ...Manual for the proper piping methods for the Knight wall mount boiler Check for 120 vac to the boiler pump motor on a call for heat If voltage is not present check the wiring back to the main control...

Страница 42: ...rs from a laptop the main control board must be reset Press the ENTER RESET button on the SMART SYSTEM display panel Service Blk While the unit is in Service Mode the outlet temperature has exceeded 1...

Страница 43: ...ections at the low voltage terminal strip Check the wire size length to remote devices Replace the transformer Watch Dog Error The main control board has detected an internal fault Replace the main co...

Страница 44: ...CTION Vent Air Intake Length or Obstruction Refer to Section 3 General Venting of the Knight Wall Mount Installation and Operation Manual for the proper venting and air intake methods for the Knight w...

Страница 45: ...1 4 turn counterclockwise to decrease CO2 levels After performing one adjustment on the valve follow the Combustion Analysis Procedure on page 44 of this manual to measure the combustion If combustion...

Страница 46: ...46 NOTES...

Страница 47: ...47 NOTES...

Страница 48: ...otes Revision A ECO C05747 initial release Reflects the new model numbers for the Knight Wall Mount upgrade Revision B ECO C06234 reflects changes made to the Service Notification parameter WBII SER R...

Отзывы: