32
HARMONY SPECIFICATIONS
Input Voltage
.......................................................................120VAC
Power Consumption
...............................................................30VA
Lead Stage Rotation
Manual
First On/First Off
Automatically ................................Every hour to every 7 days
Output Types
...................................................................4-20mA, or
Voltage....................................... 0-5V, 0-10V, 1-5V, or 2-10V
Stage Modes
..............................Off, Auto, On, Standby, Manual
Output Contacts
...............................................................5 SPST
Output Rating
..............................................6A resistive, 1/3HP
Operating Ambient Temperature
..................................20 to 120°F
Enclosure
...................................................................NEMA -1
Dimensions
............................................12-3/4” x 12-3/4” x 4-5/8"
Temperature Accuracy
...................................................
±
1°F (1°C)
Temperature Display
..........................................Field select °F or °C
Temperature Range
................................ -30 to 250°F (-35 to 120°C)
Ignition Start Point
............................................................ 1 to 50%
Modulation Start Point
...................................................... 50 to 100%
Operating Mode
.................................................. Normal or Process
Purge Delay
....................................................... 1.0 to 10.0 minutes
Lag Stage Delay
...................................................... 0 to 60 minutes
System Run On Delay
............................................. 0 to 30 minutes
Standby Time
........................................................... 0 to 60 minutes
Setback
.............................................................0 to 75°F (0 to 42°C)
Last Stage Hold
............................................... 0 to 30°F (0 to 30°C)
Shutdown Input
....................................................... Dry Contact Only
System Prove Input
................................................. Dry Contact Only
Boiler Active Inputs
.................................................. Dry Contact Only
4-20mA External Input
Only Available on Temperature Units
Harmony can source or sink current