background image

27

        

Installation & Operation Manual

5  

Hydronic piping 

(continued)

    

Please note that these illustrations are meant to show system piping concept only, the installer is responsible 
for all equipment and detailing required by local codes.

 NOTICE

Figure 5-2 Single Boiler - Recommended - Primary / Secondary Piping with a Hot Water Generator

HOT WATER

GENERATOR

WATER

GENERATOR

CIRCULATOR

BOILER PUMP

FLOW CHECK
VALVE (TYPICAL)

Y-STRAINER
(RECOMMENDED)

RELIEF

VALVE

BALL VALVE
(TYPICAL)

AIR SEPERATOR

DRAIN PORT
(TYPICAL)

SYSTEM
CIRCULATOR

BACK FLOW
PREVENTER

PRESSURE 
REDUCING VALVE

PRESSURE
GAUGE

EXPANSION

TANK

12"

MAX

FROM SYSTEM

TO SYSTEM

MAKE UP
WATER

BOILER

DRAIN

SYSTEM RETURN
SENSOR

SYSTEM SUPPLY
SENSOR

System flow should always remain higher than the required flow for the boiler(s) when the boiler(s) is in 
operation to prevent short cycling and high limit issues.

 NOTICE

Содержание Crest 1.5

Страница 1: ...luding this manual and the Crest Service Manual before installing Perform steps in the order given Failure to comply could result in severe personal injury death or substantial property damage WARNING Save this manual for future reference FB I O Rev I Installation Operation Manual Models 1 5 2 0 2 5 3 0 3 5 ...

Страница 2: ...ng Options Vertical Vent 14 Direct Venting Options Vert Vent Opt Rm Air 14 Direct Venting Options Vert Vent Sidewall Air 14 Install Vent and Combustion Air Piping 15 Air Inlet Pipe Materials 15 Requirements for Installation in Canada 15 Vent and Air Piping 16 Air Intake Vent Connections 16 Min Max Combustion Air Vent Piping Lengths 17 Vent and Air Piping 17 Common Venting 18 3 VERTICAL DIRECT VENT...

Страница 3: ...tantial property damage Do not use homemade cures or boiler patent medicines Serious damage to the boiler personnel and or property may result Continual fresh make up water will reduce boiler life Mineral buildup in the heat exchanger reduces heat transfer overheats the stainless steel heat exchanger and causes failure Addition of oxygen carried in by makeup water can cause internal corrosion in s...

Страница 4: ...rs allowing gas to flow only if the gas valves are powered and combustion air is flowing 18 Blower proving switches Prove adequate airflow during prepurge 19 High limit devices primary and backup The high limit devices are used to monitor the outlet water temperature if either device senses the water temperature exceeding the predetermined setting the boiler will shut down 20 Ignition electrode An...

Страница 5: ...nside unit The Crest How it works continued 5 Installation Operation Manual Models 1 5 2 0 2 5 3 0 3 5 2 11 1 39 Front View 7 36 6 35 9 29 5 19 10 Rear View 33 12 13 17 34 3 37 25 26 21 22 29 20 12 27 14 32 4 15 16 23 19 28 31 30 34 18 ...

Страница 6: ...sed on a piping and pickup allowance of 1 15 3 Crest boilers require special gas venting Use only the vent materials and methods specified in the Crest Installation and Operation Manual 4 Standard Crest boilers are equipped to operate from sea level to 4 500 feet only with no adjustments 5 High altitude Crest boilers are equipped to operate from 3 000 to 12 000 feet High altitude models are manufa...

Страница 7: ...damage in connection with this appliance or any of its components 3 Check area around the boiler Remove any combustible materials gasoline and other flammable liquids This appliance requires a special venting system Use only the vent materials specified in this manual Failure to follow all instructions can result in flue gas spillage and carbon monoxide emissions causing severe personal injury or ...

Страница 8: ...ng The Crest requires a special gas vent system designed for pressurized venting The boiler is to be used for either direct vent installation or for installation using indoor combustion air When room air is considered see page 23 of this manual Note prevention of combustion air contamination below when considering vent air termination Vent and air must terminate near one another and may be vented ...

Страница 9: ...iance see Section 2 General Venting Table 2A For stainless steel venting an adapter of the same manufacturer Table 2B may be used at the flue collar connection Size To ensure proper pipe size is in place see Table 2C Check to see that this size is used throughout the vent system Manufacturer Only use the listed manufacturers and their type product listed in Table 2A for CAT IV positive pressure ve...

Страница 10: ...ust fan Close fireplace dampers DANGER WARNING At the time of removal of an existing boiler the following steps shall be followed with each appliance remaining connected to the common venting system placed in operation while the other appliances remaining connected to the common venting system are not in operation d Place in operation the appliance being inspected Follow the lighting instructions ...

Страница 11: ... tools required Do not drop the boiler or bump the jacket on the floor or pallet Damage to the boiler can result REAR FRONT BOLT WASHERS LOCKNUT 3X LAG BOLTS TABS 3X Figure 1 2 Boiler Mounted on Shipping Pallet NOTICE Maintain minimum specified clearances for adequate operation All installations must allow sufficient space for servicing the vent connections water pipe connections piping and other ...

Страница 12: ...OT be of Tight Construction 3 A combination of indoor and outdoor combustion air may be utilized by applying a ratio of available volume to required volume times the required outdoor air opening s size s This must be done in accordance with the National Fuel Gas Code NFPA 54 ANSI Z223 1 Figure 1 5_Combustion Air Through Ducts 2 If combustion and ventilation air is taken from the outdoors using a d...

Страница 13: ...air supply and or cause a downdraft in the venting system Spillage of flue products from the venting system into an occupied living space can cause a very hazardous condition that must be corrected immediately The combustion air supply must be completely free of any flammable vapors that may ignite or chemical fumes which may be corrosive to the appliance Common corrosive chemical fumes which must...

Страница 14: ...14 Installation Operation Manual Vertical 2 General venting Sidewall Direct venting Vertical Vent Sidewall Air Sidewall Vertical Optional room air ...

Страница 15: ... s instructions can result in personal injury death or property damage Mixing of venting materials will void the warranty and certification of the appliance NOTICE The use of double wall vent or insulated material for the combustion air inlet pipe is recommended in cold climates to prevent the condensation of airborne moisture in the incoming combustion air Sealing of Type B double wall vent mater...

Страница 16: ...d carbon monoxide emissions causing severe personal injury or death The Crest uses model specific combustion air intake and vent piping sizes as detailed in Tables 2B and 2C on page 17 Increasing or decreasing combustion air or vent piping to sizes not specified in this manual is not authorized NOTICE 2 General venting Use only the materials vent systems and terminations listed in Table 2A DO NOT ...

Страница 17: ...tructions in Section 1 page 10 of this manual when removing a boiler from an existing vent system Vent and air piping Vent and air system Installation must comply with local requirements and with the National Fuel Gas Code NFPA 54 ANSI Z223 1 for U S installations or CSA B149 1 for Canadian installations You must also install air piping from outside to the boiler air intake adapter The resultant i...

Страница 18: ...ay be used when common venting Crest boilers Sidewall venting is not allowed 5 Crest boilers in a common vent must be connected and controlled with the integral Crest SMART TOUCH Cascade The Leader may be controlled through the Crest SMART TOUCH control through BMS external 0 10V signal ModBus or its own internally calculated set point For approved common vent sizing contact the factory WARNING Wh...

Страница 19: ...ubstantial property damage Installation must comply with local requirements and with the National Fuel Gas Code NFPA 54 ANSI Z223 1 latest edition for U S installations or CSA B149 1 Installation Code for Canadian installations WARNING NOTICE WARNING Do not connect any other appliance to the vent pipe or multiple boilers to a common vent pipe except as noted in Section 2 on page 18 Failure to comp...

Страница 20: ...ection It is not classified as a forced air intake with regard to spacing from adjacent boiler vents 36 914 MM 36 914 MM 12 305 MM 12 305 MM 12 305 MM 12 305 MM 12 305 MM 12 305 MM Figure 3 3 Vertical Terminations with Multiple Boilers 36 914 MM 12 305 MM 36 914 MM 12 305 MM Figure 3 4 Alternate Vertical Terminations with Multiple Boilers WARNING 3 The vent piping must terminate in an up turned co...

Страница 21: ...or substantial property damage Installation must comply with local requirements and with the National Fuel Gas Code NFPA 54 ANSI Z223 1 for U S installations or CSA B149 1 for Canadian installations Determine location Locate the vent air terminations using the following guidelines 1 The total length of piping for vent or air must not exceed the limits given in the General Venting Section on page 1...

Страница 22: ... air connection as described in this manual FIG 4 4 WARNING 22 Installation Operation Manual 4 Sidewall direct venting Vent air termination sidewall 4 4 Figure 4 2 Clearance to Doors and Windows VENT TERMINATION IF LESS THAN 10 36 MIN FORCED AIR INLET AIR TERMINATION Figure 4 3 Clearance to Forced Air Inlets Prepare wall penetrations 1 Air pipe penetration a Cut a hole for the air pipe Size the ai...

Страница 23: ...itered 23 Elbow Figure 4 5 Direct Vent Terminations ROOM AIR DIRECT EXHAUST TERMINATIONS Vent Termination 23 Elbow 45 Elbow 90 Elbow Figure 4 6 Room Air Direct Exhaust Terminations Room air AIR INLET COVER Figure 4 7 Room Air Installation The Crest boiler may be installed with a single pipe carrying the flue products to the outside while using combustion air from the equipment room Follow the requ...

Страница 24: ...n of the Crest 5 2 thru 5 5 1 Connect the system return to the 4 flanged connection marked Inlet make sure to install with a suitable gasket between flanges 2 Connect the system supply to the 4 flanged connection marked Outlet make sure to install with a suitable gasket between flanges 3 Install purge and balance valve or shutoff valve and drain on system return to purge air out of each zone 4 Ins...

Страница 25: ...TURE RISE APPLICATIONS Model BOILER CONNECTION SIZE 20 F 40 F 60 F GPM FT HD GPM FT HD GPM FT HD FB 1500 4 138 3 4 69 1 5 46 1 0 FB 2000 4 184 4 1 92 1 6 61 1 0 FB 2500 4 230 4 6 115 1 3 77 0 7 FB 3000 4 277 5 6 138 1 2 92 0 7 FB 3500 4 323 7 5 161 1 2 108 0 7 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 0 50 100 150 200 250 300 350 FBN1500 FBN2000 FBN2500 FBN3000 FBN3500 Flow Rate GPM Pressure Drop F...

Страница 26: ...is recommended when storing domestic hot water above 115 F 46 C 8 Pressure relief valve Factory supplied The pressure relief valve is sized to ASME specifications 9 System temperature sensor Lochinvar supplies a system temperature sensor The sensor is to be installed in the heating loop downstream from the boiler hot water piping and heating loop junction The sensor should be located far enough do...

Страница 27: ...T WATER GENERATOR WATER GENERATOR CIRCULATOR BOILER PUMP FLOW CHECK VALVE TYPICAL Y STRAINER RECOMMENDED RELIEF VALVE BALL VALVE TYPICAL AIR SEPERATOR DRAIN PORT TYPICAL SYSTEM CIRCULATOR BACK FLOW PREVENTER PRESSURE REDUCING VALVE PRESSURE GAUGE EXPANSION TANK 12 MAX FROM SYSTEM TO SYSTEM MAKE UP WATER BOILER DRAIN SYSTEM RETURN SENSOR SYSTEM SUPPLY SENSOR System flow should always remain higher ...

Страница 28: ... SYSTEM MAKE UP WATER BOILER DRAIN TYPICAL SYSTEM RETURN SENSOR SYSTEM SUPPLY SENSOR Figure 5 3 Multiple Boilers Common Header Recommended Primary Secondary Flow Model Number of Units 2 3 4 5 6 7 8 Recommended Common Header Pipe Sizes in Inches FB 1500 4 4 5 5 6 6 7 FB 2000 4 5 5 6 7 7 8 FB 2500 5 5 6 7 7 8 10 FB 3000 5 6 7 7 8 10 10 FB 3500 5 6 7 8 10 10 10 NOTICE A system supply sensor factory s...

Страница 29: ... for all equipment and detailing required by local codes NOTICE Y STRAINER RECOMMENDED RELIEF VALVE BALL VALVE TYPICAL AIR SEPERATOR DRAIN PORT TYPICAL SYSTEM CIRCULATOR BACK FLOW PREVENTER PRESSURE REDUCING VALVE PRESSURE GAUGE EXPANSION TANK FROM SYSTEM TO SYSTEM MAKE UP WATER BOILER DRAIN Figure 5 4 Single Boiler Alternate Fixed or Variable Flow Primary System Piping ...

Страница 30: ...AL AIR SEPERATOR DRAIN PORT TYPICAL SYSTEM CIRCULATOR BACK FLOW PREVENTER PRESSURE REDUCING VALVE PRESSURE GAUGE EXPANSION TANK FROM SYSTEM TO SYSTEM MAKE UP WATER BOILER DRAIN TYPICAL SYSTEM RETURN SENSOR SYSTEM SUPPLY SENSOR Figure 5 5 Multiple Boilers Alternate Common Header Fixed or Variable Flow Primary When installing multiple Crest boilers in fixed or variable flow primary applications util...

Страница 31: ...g system by closing a manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1 2 PSIG 3 5 kPa c The appliance and its gas connection must be leak tested before placing it in operation The gas valve and blower will not support the weight of the piping Do not attempt to support the weight of the piping with the boiler or its accessori...

Страница 32: ...during boiler startup Maximum inlet gas pressure must not exceed the value specified Minimum value listed is for the purposes of input adjustment WARNING WARNING NOTICE WARNING Ensure that the high gas pressure regulator is at least 10 feet 3 m upstream of the appliance FIG 6 3 Check boiler rating plate to determine which fuel the boiler is set for Crest boilers CAN NOT be field converted Failure ...

Страница 33: ...djustments are needed proceed on to Step 11 10 If the gas pressure is out of range contact the gas utility gas supplier qualified installer or service agency to determine the necessary steps to provide proper gas pressure to the control 11 Turn the power switch to the OFF position 12 Shut off the gas supply at the manual gas valve in the gas piping to the appliance 13 Remove the manometer from the...

Страница 34: ...for LP gas during standby static mode and while in operating dynamic mode If an in line regulator is used it must be a minimum of 10 feet 3 m from the Crest boiler It is very important that the gas line is properly purged by the gas supplier or utility company Failure to properly purge the lines or improper line sizing will result in ignition failure Ignition problems are especially noticeable in ...

Страница 35: ...voltage terminal strip in the junction box as shown in FIG 7 1 2 Provide and install a fused disconnect or service switch sized per the boiler amp draw shown on the boiler rating plate as required by the code see FIG 7 1 3 When connecting the boiler system and hot water generator pumps connect the wiring to the line voltage terminal strip as shown in FIG 7 1 Maximum current is 1 5 amps Install a f...

Страница 36: ...inals Use shielded 2 wire twisted pair cable If desired the shield can be connected to ground by installing a jumper wire between terminals 1 and 3 on connector X5 on the ModBus interface module Hot Water Generator HWG thermostat 1 Connect the HWG tank thermostat to the Tank Thermostat terminals on the connection board FIG 7 3 Hot Water Generator HWG tank sensor 1 By installing a HWG tank sensor t...

Страница 37: ...FIG s 5 5 and 5 6 The system supply sensor should be wired to the Low Voltage Connection Board at the terminals marked for the system supply sensor see FIG 7 3 The Leader control will use the water temperature at the system supply sensor to control the operation of the Cascade If outdoor air reset is desired the outdoor air sensor should be wired to the Low Voltage Connection Board at the terminal...

Страница 38: ...R SENSOR SENSOR SENSOR TANK SYSTEM SUPPLY SYSTEM RETURN BOILER PUMP OUT OUT RATE MODBUS SHIELD SHIELD B A SHIELD SHIELD B A BUILDING MANAGEMENT SYSTEM TANK THERMOSTAT ENABLING DEVICE LOUVER PROVING SWITCH LOUVER RELAY AUX SWITCH 1 AUX SWITCH 2 FROM PREVIOUS BOILER TO NEXT BOILER A B B A SHIELD SHIELD 0 10V INPUT SYSTEM PUMP OUTDOOR SENSOR TANK SENSOR SYSTEM SUPPLY SENSOR SYSTEM RETURN SENSOR 0 10V...

Страница 39: ...e neutralizer kit must be placed on a surface that is a minimum of 3 inches lower than the condensate trap with field supplied piping vacuum break installed between the condensate trap and the neutralizer kit Use materials approved by the authority having jurisdiction In the absence of other authority PVC and CPVC pipe must comply with ASTM D1785 or D2845 Cement and primer must comply with ASME D2...

Страница 40: ...quire a backflow preventer or actual disconnect from city water supply 3 When using freeze protection fluid with automatic fill install a water meter to monitor water makeup Freeze protection fluid may leak before the water begins to leak causing concentration to drop reducing the freeze protection level Fill and test water system 1 Fill system only after ensuring the water meets the requirements ...

Страница 41: ...and the gas may no longer have an odor Before startup and periodically thereafter have the propane supplier verify the correct odorant level in the gas Check thermostat circuit s 1 Disconnect the two external wires connected to the enable terminals on the connection board 2 Connect a voltmeter across these two incoming wires Close each thermostat zone valve and relay in the external circuit one at...

Страница 42: ...ter piping 1 Check system piping for leaks If found shut down the boiler and repair immediately See WARNINGS on pages 40 and 41 startup regarding failure to repair leaks 2 Vent any remaining air from the system using manual vents Air in the system will interfere with circulation and cause heat distribution problems and noise Check vent piping and air piping 1 Check for gastight seal at every conne...

Страница 43: ...o inspect the appliance and to replace any part of the control system and any gas control which has been under water OPERATING INSTRUCTIONS 1 STOP Read the safety information above on this label 2 Set the thermostat to lowest setting 3 Turn off all electric power to the appliance 4 This appliance is equipped with an ignition device which automatically lights the burner Do not try to light the burn...

Страница 44: ...e Set Points Menu Press the following buttons to navigate to the Set Points Menu from the Home Screen After pressing SETUP the Password Screen will appear Entering the correct password will allow access to all Installer Level adjustable parameters Press ENTER without a password to access the User Level parameters 1 To change a set point use the arrows to highlight a user set point parameter and pr...

Страница 45: ...evel adjustable parameters Press ENTER without a password to access the User Level parameters The SMART TOUCH control has a built in clock that it uses for its night setback feature and for logging events This clock must be set when the boiler is installed and anytime the boiler has been powered off for more than one day Use the following procedure to set the clock 1 To set the clock highlight Clo...

Страница 46: ... HW thermostat or sensor to the low voltage connection board When the HW thermostat or sensor calls for heat the control module activates the HW pump shuts down the boiler pump and immediately sets the target outlet water temperature to 180 F 82 2 C This provides automatic priority heat allocation to the HW Generator for maximum response and recovery The HW pump continues for 60 seconds after the ...

Страница 47: ...ailable This output may be connected to a Building Management System BMS to allow it to monitor the actual firing rate Connect the terminal to the COM or terminal on the BMS and connect the terminal to the 0 10V or terminal on the BMS Ramp Delay For systems with lower flow the SMART TOUCH can limit the firing rate when enabled when a space heating call for heat starts or when switching from a DHW ...

Страница 48: ... is not installed Target temperature is calculated as described under Outdoor Reset Operation and Target Temperature Boost when the outdoor sensor is connected High limit operations The Crest SMART TOUCH control has two 2 integral limits one auto reset and one manual reset The Crest also has one auxiliary manual reset high limit The integral and auxiliary high limits are UL353 certified When the o...

Страница 49: ...time at a lower rate thus more efficient This Cascade is also required when cascading boilers in a common vent application Lead Lag The Lead Lag method is chosen when the application requires firing as few boilers at a time as possible This method will not bring on another boiler until the current number of boilers cannot meet the demand This Cascade is NOT allowed in a common vent application The...

Страница 50: ...o the desired set point temperature 9 If the current call for heat is for space heating and a HW call for heat becomes active the control will turn on the HW pump relay output then turn off the boiler pump It will then modulate the blower speed in order to maintain the outlet temperature to the desired HW outlet set point temperature 10 If the first combustion system in the boiler is unable to mai...

Страница 51: ...his screen Main Menu button Pressing this button brings up the Main Menu Screen From this screen navigation to nine 9 other screens is possible Reference the Main Menu Screen section on page 52 of this manual for more information regarding this screen Modulation button Pressing this button brings up the Modulation Screen This screen shows overall boiler modulation individual fan speeds and flame c...

Страница 52: ...12 other screens for the adjustment of the control parameters Cascade Shows the status of multiple boilers connected together in a cascade arrangement Leader only Modulation Shows the status of the two 2 gas train systems used in the boiler BMS Shows the information from a Building Integration System Pumps Allows the installer to configure the boiler system and DHW pumps History Shows the operatin...

Страница 53: ...out and performance verification per Section 9 Flame inspection stable uniform Check both flame signals at least 10 microamps at high fire Clean the heat exchanger Test low water cutoff reference the Crest Service Manual If combustion or performance indicate need Clean heat exchanger Remove and clean burner using compressed air only Clean the blower wheels ANNUAL START UP Owner maintenance see the...

Страница 54: ...ed in Section 1 of this manual If any of these are present in the boiler intake air vicinity they must be removed If they cannot be removed reinstall the air and vent lines per this manual Inspect boiler interior 1 Remove the front access covers and inspect the interior of the boiler 2 Vacuum any sediment from inside the boiler and components Remove any obstructions Clean condensate trap 1 Inspect...

Страница 55: ...iping before proceeding further Safety relief valves should be re inspected AT LEAST ONCE EVERY THREE YEARS by a licensed plumbing contractor or authorized inspection agency to ensure that the product has not been affected by corrosive water conditions and to ensure that the valve and discharge line have not been altered or tampered with illegally Certain naturally occurring conditions may corrode...

Страница 56: ...remove and clean the burner Clean the burner thoroughly using a vacuum cleaner or compressed air Do not use compressed air to clean the burner if cleaning is performed inside a building Shut down the boiler Follow the To Turn Off Gas to Appliance instructions for the boiler in Section 9 Startup Do not drain the boiler unless it will be exposed to freezing temperatures If using freeze prevention fl...

Страница 57: ...n in this appliance contains ceramic fiber material Ceramic fibers can be converted to cristobalite in very high temperature applications The International Agency for Research on Cancer IARC has concluded Crystalline silica in the form of quartz or cristobalite from occupational sources is carcinogenic to humans Group 1 Normal operating temperatures in this appliance are below the level to convert...

Страница 58: ...ENSOR 0 10V 0 10V BMS IN SYSTEM PUMP IN SHIELD SHIELD A B CASCADE LARGE CONNECTION BOARD CN6 1 CN3 6 CN3 7 CN3 14 CN3 13 CN3 11 CN3 9 CN3 8 CN3 1 CN3 2 CN3 3 CN3 4 CN6 2 CN6 3 CN3 10 CN3 12 MODBUS BOARD X4 1 X4 2 X4 3 X6 3 X6 1 X6 2 X8 20 X8 10 X7 8 X8 13 X8 14 X8 12 INTEGRATED CONTROL CN3 4 X8 15 X7 7 X8 11 X8 6 X8 16 X8 7 X8 17 X8 1 T T T T T T T T T INLET SENSOR OUTLET SENSOR S9 OUTLET SENSOR S...

Страница 59: ... SWITCH 2 SHIELD SHIELD A B MODBUS OPTION RATE OUT BOILER PUMP OUT SYSTEM RETURN SENSOR SYSTEM SUPPLY SENSOR 0 10V 0 10V TANK SENSOR OUTDOOR SENSOR 0 10V 0 10V BMS IN SYSTEM PUMP IN SHIELD SHIELD A B CASCADE R R R O R O L B K B R B R Y R O HIGH LIMIT SWITCH R R X6 1 X6 2 X6 3 Y G R R P MODBUS BOARD L B R L B R R B W R O OR W P W L B K B J3 5 J3 4 J3 6 LWCO BOARD J3 3 J3 2 J2 1 J2 2 X6 3 R O OR BK ...

Страница 60: ...tion added to the humidity warning on page 7 along with references to the Dual Fuel Supplemental Manual Revision F ECO C09629 reflects the update of the AHRI and ASME logos on page 6 and the update of condensate disposal information and Figure 8 1 on page 39 Revision G ECO C10325 reflects a kit number correction Neutralizer kit and the addition of version 4 software update pg 49 Revision H ECO C10...

Отзывы: