background image

1.

STOP!

Read the safety information above.

2. Turn off all electrical power to the appliance.

3. Remove the upper front access panel 

4. Turn the power switch on the inside of the cabinet to 

"OFF" position.

5. Set the thermostat to the lowest setting.

6. This appliance is equipped with an ignition device which 

automatically lights the burners.  

DO NOT

try to light 

the burners by hand.

7. Turn the gas control knob on the gas valve clockwise to

the "OFF" position.

FIG. 1   Combination Gas Valve

8. Wait five (5) minutes to clear out any gas.  If you smell 

gas, STOP!  Follow the instructions in the safety
information "What To Do If You Smell Gas".  If you
don't smell gas, go on to the next step.

9. Turn the gas control knob on the gas valve

counterclockwise  to the "ON" position.

10. Set the thermostat to the desired setting.

11. Turn the power switch on the inside of the cabinet to the

“ON” position.

12. Replace control access panel.

13. Turn on all electrical power to the appliance.

14. If the appliance will not operate, follow the instructions

"To Turn Off Gas To Appliance" and call your service
technician or gas supplier.

1. Turn off all electric power to the appliance if service is 

to be performed.

2. Turn the gas control knob on the gas valve clockwise to 

the "OFF" position.  Do not force.

The hot surface ignition module is not repairable.  Any
modification or repairs will invalidate the warranty and
may create hazardous conditions that result in property
damage, personal injury, fire, explosion and/or toxic gases.
A faulty ignition module must be replaced with a new unit.
The hot surface igniter is also the flame sensor.

Call a qualified service technician if service is required on
the hot surface ignition system.

FIG. 2   Water Connections

Inlet and Outlet Connections 

For ease of service, install unions on inlet and outlet of the
appliance.  The connection to the appliance marked "Inlet"
on the header should be used for return from the system.
The connection on the header marked "Outlet" is to be
connected to the supply side of the system.

2

LIGHTING INSTRUCTIONS

TO TURN OFF GAS TO APPLIANCE

WARNING

Should overheating occur or the gas fail to shut
off, do not turn off or disconnect the electric
supply to the pump.  Instead, shut off the gas
supply at a location external to the appliance.

HOT SURFACE IGNITION SYSTEM

WATER CONNECTIONS

 

 

 

Содержание 000 - 300

Страница 1: ...SUMER RETAIN THE USER S INFORMATION MANUAL FOR FUTURE REFERENCE DO NOT Use this appliance if any part has been under water The possible damage to a flooded appliance can be extensive and present numer...

Страница 2: ...our service technician or gas supplier 1 Turn off all electric power to the appliance if service is to be performed 2 Turn the gas control knob on the gas valve clockwise to the OFF position Do not fo...

Страница 3: ...ilation air must be in accordance with Section 5 3 Air for Combustion and Ventilation of the latest edition of the National Fuel Gas Code ANSI Z223 1 in Canada the latest edition of CGA Standard B149...

Страница 4: ...n Listed below are items that must be checked to ensure safe reliable operations Verify proper operation after servicing 1 Examine the venting system at least once a year Check more often in first yea...

Страница 5: ...ts seldom need flue cleaning All gaskets on disassembled components must be replaced with new gaskets on reassembly Gasket kits are available from your distributor a Turn off main power to appliance b...

Страница 6: ...knobs on the temperature control unless your appliance is specified as a boiler only with an outdoor air reset option If your appliance is a boiler only with an outdoor air reset option there are addi...

Страница 7: ...ontrol would prevent the appliance from operating Outdoor Air Max O A Max The O A Max knob allows a reset up to the maximum outdoor air temperature specified by this knob setting At any outdoor air te...

Страница 8: ...2 05 Printed in the U S A...