Assembly instructions | LK Electric Portable Boiler

Technical data

Article no. 

241 84 64

Output

9 kW in two stages at 4.5 kW

Voltage

3 N~ 400V AC, connection via 

3-phase electric plug

Boiler must be protected using 

3 x 16 A fuses (max. current 

13.5 A)

Electrical cartridge

9 kW/6-tube 400 V, stainless 

steel SS2353, connection 2”

Pump

Grundfos UPM3 Auto 15-70  1 

phase 230V AC (factory fitted 

to control box)

Protection class

IP 44

Input power circulator

5-52 W

Operating thermostat

Max 60 ºC

Safety thermostat

80 ºC

Expansion tank

12 litres

Safety valve

1,5 bar

Max. glycol solution

30%

Boiler volume

2,8 litres

PS max. pressure for 

boiler jacket

1,5 bar

Dimensions (L x W x H) 710 x 430 x 650 mm
Weight

23 kg

Condensing boiler

No

Low-temperature boiler No
B1 boiler

No

Cogeneration space 

heater

No

Rated heat output

P

märk

 9 kW

Useful heat output 

P

märk

 9 kW

Energy class

D

Seasonal space heating  

energy efficiency

η

s

 36%

Useful efficiency

η

s

 39.4%

Auxiliary electricity  

consumption

On standby P

SB

 0.025 kW

Standing loss

P

stby

 0.101 kW

Recycling

The boiler should be recycled after dismantling. 

Insulation is removed and sorted as insulation. 

The boiler body and stand should be sorted as 

scrap steel. Electronics and electronic compo-

nents should be sorted as electrical scrap.

Safety valve

The safety valve must be tested at start-up and 

then at set intervals 2-3 times per year. CAU-

TION: Take care when testing as the out-flowing 

water/steam can cause scald injuries.

Pump graph

Electric connection diagram

LK Systems AB, Box 66, 161 26 Bromma, Sweden | www.lksystems.se