Constant pressure curve
For under floor heating it is recommended that
the pump is set to constant pressure control. Se-
lect the constant pressure curve that best matches
the needs of the system, see capacity chart below.
Proportional pressure curve
Proportional pressure setting is normally not
used for floor heating.
Automatic venting routine
When the floor heating system is filled, flushed
and vented the circulation pump can be started.
At start up, use the pump´s automatic venting
routine to remove accumulated air in the pump´s
rotor chamber. The automatic venting routine
start after 3 seconds and lasts for 10 minutes.
Venting routine indicated by a fast flashing green
diode light. After complete venting, choose the
constant pressure curve that best matches the re-
quirements of the system, see capacity chart be-
low. If no choice is made, the pump operation au-
tomatically to switches to constant pressure with
max capacity.
Capacity chart
0,025 0,05 0,075 0,10 0,125 0,15 0,17 0,20 0,225 0,25 0,275 Q [l/s]
P
[kPa]
60
50
40
30
20
10
0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0 Q [m³/h]
H
[m]
6
5
4
3
2
1
Δp - c
6
5
4
3
1
2
Capacity chart LK Minishunt M60 with Wilo Yonos Para RSB 15/6-RKA.