Assembly instructions | LK Room Temperature Control ICS.2

Settings/functions

Setback (central temperature reduction)

The LK Receiver 8 ICS.2 is fitted with a setback 

input. Enabled contact (closed contact) gives 

a temperature setback for the entire system. 

 

The setback temperature is pre-set to 12 °C. The 

temperature can be changed for individual room 

thermostats as follows:

1.  Press 

Set

 until   flashes, confirm with 

Set

.

2.  Press the right arrow until 

SET

 (Setback) 

appears in the display, confirm with 

Set

.

3.  Select the temperature using the left /right 

arrow, confirm with 

Set

Repeat the above for the oth-

er room thermostats in the system. 

Holiday function – set the temperature

The room thermostat is fitted with a 'holiday func-

tion' which means that you can activate a general 

temperature reduction for the system for 1-99 days 

from any room thermostat. The temperature setback 

is factory pre-set to 12 °C room temperature.
The temperature can be changed for individual 

room thermostats as follows:

1.  Press 

Set

 until   flashes, confirm with 

Set

.

2.  Press the right arrow until 

Holi

 (Holiday) 

appears in the display, confirm with 

Set

.

3.  Set the required temperature using the 

right/left arrow, confirm with 

Set.

Repeat the above for the other room thermostats 

in the system. 

NOTE:

Following an activated function, the risk of freezing must 

be considered for the vulnerable zones of the underfloor 

heating system, such as inside the garage door or other 

weather exposed edge zones. 

Holiday function – enable

The function is enabled from any room thermo-

stat as follows:

1.  Press 

Set

 until   flashes, confirm with 

Set.

2.  Select   using the right arrow, confirm 

with 

Set

.

3.  Select 

ON

, confirm with 

Set

.

4.  Select the number of days using the left /

right arrow, confirm with 

Set

.

The room thermostat now displays how many 

days are left. The days count down accordingly. 

When the days are set at zero, the room thermo-

stats return to normal operation.

NOTE:

Note that the countdown starts when the activation was 

made which means the countdown takes place the next 

day at the same time. 

Holiday function – disable

The function is disabled from any room thermo-

stat as follows: 

1.  Press 

Set

 once.

2.  Select 

OFF

, confirm with 

Set

.

3.  The room thermostat switches to normal view. 

Other room thermostats automatically switch to 

normal view within about five minutes.

Содержание ICS.2

Страница 1: ...CS 2 is a control system designed for LK Floor Heating The sys tem is suitable for small medium or large build ing installations LK ICS 2 has been designed to provide high levels of comfort and energy ef ficient heating systems thanks to its advanced self modulation technique The system consists of LK Receiver ICS 2 LK Room Thermostat ICS 2 and LK Actuators 24 V Communications between the room the...

Страница 2: ...alve actuator symbol NOTE Maximum of two LK Actuators per terminal and a maximum of twelve LK Ac tuators per receiver 8 and five LK Actuators per receiver 1 6 Run the actuator cables in the strain relief grooves Install the room thermostat s back plate about 1 5 m above the floor Note the arrow on the back plate indicating which way is up For the wired room thermostat the cable is connected from t...

Страница 3: ...on once This turns off all the lights on the unit and confirms exits the learning sequence for the Master unit It is important to check that all lights are off be fore continuing with the rest of the installation steps This is to avoid conflicts during the ongo ing installation process Remember to mark the unit as Master unit on the sticker in the unit s cover Note Steps 5 to 8 are only performed ...

Страница 4: ... in the system Remember to ensure that the Master unit s L light lights green con tinuously during the learning phase for all Slave units When all slave units have been programmed the learning is completed by pressing once on the Master unit s L button All the lights on the Master unit should now turn off Check that all lights are off on all units to en sure that nothing can interfere with the con...

Страница 5: ...hange to green Choose the channel channels that the room thermostat is to control by pressing the corre sponding channel button 1 8 The selected channels flashes green Channels already occupied have a solid orange light The selected channels are displayed in the room thermostat display 1 8 Once all the required channels have finished the learning process you confirm by pressing the SET button once...

Страница 6: ... appears as a digit 1 8 inside the figure of a house Repeat steps 11 to 15 for each thermostat to un dergo learning for this receiver Ensure that the selected receiver s L light remains lit for the learning of all room thermostats When all the room thermostats have finished learning for the receiver in question the learn ing process is completed by pressing the L but ton Ensure that the L light go...

Страница 7: ...er ICS 2 Using LK Webserver ICS 2 you can easily con trol your heating system remotely via a mobile phone tablet or computer The webserver s user interface is easy to manage and provides a good overview of the underfloor heating system It is easy to make all the system settings using the user interface Any alarms are displayed via the alarm icon and you receive information about the alarm in clear...

Страница 8: ...provides a centralised setback of all room thermostats in the system When activated all room thermostats show EXT in the display and the temperature setbacks to 12 C for all rooms zones The temperature can be adjusted read more under the heading Set tings Functions LK Receiver 8 ICS 2 LK Receiver 8 ICS 2 Functional description The LK Receiver 8 ICS 2 has 8 channels which means that up to 8 LK Room...

Страница 9: ...ctuator 24V max 2 actuators per output 7 Power supply The unit is connected to 230 V AC via a factory installed cable 8 Fuse Fuse 230 V AC T200mA Cut the power supply before changing fuse 9 Pump relay Potential free relay contact for control of the circulation pump 10 Relay for heat source Potential free relay contact for control of the heat source 11 Strain relief Groove for strain relief of cabl...

Страница 10: ...the pump from jamming during long periods of downtime e g summertime 8 8 230VAC FUSE BOILER PUMP 7 M 8 M L N P The wiring diagram for connecting the pump to receiver 8 Relay for heat source It is possible to control the system s heat source via the receiver s relay for the heat source The relay is located under the cover on the high voltage side of the receiver NOTE Cut all incoming power to the u...

Страница 11: ...n combination with other buttons to enable alternative functions 2 L button Enables disables learning mode 3 Button 1 Button 1 is used to select the required channel for learning 4 Thermostat input Thermostat input for connecting one wired room thermostat W ICS 2 min cable size 2 x 0 5 mm2 5 Actuator output For connection of LK Actuator 24V NO max 2 actuators per output and 5 per receiver 1 6 Powe...

Страница 12: ...etween the room thermostats the wireless room thermostat is marked with RF and the wired ver sion with W It is possible to combine both wireless and wired communications in LK Receiver 8 ICS 2 The room thermostat is installed in the room zone it is to control The room thermostat display shows the current room temperature in the nor mal view Set required temperature is displayed when you press the ...

Страница 13: ...Number on receiver and error code 3 Room temperature measurement enabled 4 Indicates constantly disconnected week program 5 Temperature indication 6 Setup menu 7 Holiday function 8 OFF ON option 9 Local general setting 10 Controlled channel weekday 11 Mode of operation 12 Button lock symbol 13 Communications symbol 14 Battery indicator Applies to wireless communications ...

Страница 14: ...system SYSD System date system cal endar Sets year month and day Set value applies to all units in the system SENM Sensor mode setting sensors For the connected external sensor you can specify the function the external sensor is to have Select from only room temperature only floor temperature room temperature combined with minimum floor temperature and room tem perature in combination with maximum...

Страница 15: ... right arrow until Holi Holiday appears in the display confirm with Set 3 Set the required temperature using the right left arrow confirm with Set Repeat the above for the other room thermostats in the system NOTE Following an activated function the risk of freezing must be considered for the vulnerable zones of the underfloor heating system such as inside the garage door or other weather exposed ...

Страница 16: ...right left arrow confirm with Set The above setting applies to the individual room thermostat Week program temperature The units are supplied with the following values as default Comfort 20 C Economy 18 C Change temperatures as follows 1 Press Set until flashes confirm with Set 2 Select Eco for night setback temperature confirm with Set 3 The temperature flashes change the tem perature using the r...

Страница 17: ...e is enabled when the temperature stops flashing 4 The display shows neither Comfort or Econ omy when the temporary increase decrease is enabled The temporary disconnection of the week pro gram disappears when the program switches be tween Economy Comfort next time Alternatively press Set for 5 seconds to return to the week program System clock The unit is fitted with a system clock In order for t...

Страница 18: ...n disappears and the room thermostat reopens Checking signal strength Before the system is put into operation the first time the signal strength should be controlled to ensure that all thermostats are within transmis sion range Follow these steps to check the signal strength 1 Press Set until flashes confirm with Set 2 Press the right arrow until RFST Radio Sig nal Strength appears in the display ...

Страница 19: ...Depending on the required function you can ei ther choose time controlled bypass or a bypass that is constantly activated until some other cir cuit opens Time controlled bypass keeps the bypass circuit open for 22 minutes then turns the circuit off The By pass function is enabled as follows 1 Press Set until flashes confirm with Set 2 Press the right arrow until BYPS By pass appears in the display...

Страница 20: ...llows 1 Press Set until flashes confirm with Set 2 Press the right arrow until SENM Sensor Mode appears in the display confirm with Set 3 The display s symbol to the left flashes Select from the following operating modes Only thermometer flashing only room temper ature Confirm with Set The external sensor is inactive Thermometer and MAX flashing room temper ature with the floor at maximum limit Co...

Страница 21: ...or heat ing installation so that it is pointing towards the nearest short side At the short side cut a jack approximately 1 metres long in the EPS board measured from the short side The conduit is positioned in this jack Insert the re mote sensor in the conduit before laying the floor and connect to the thermostat as described above LK Clip Rail 8 LK Clip Rail 12 Position a conduit along the long ...

Страница 22: ...oubleshooting resetting Typically a floor heating system from LK is ex tremely reliable However as with any other equipment problems may arise that make it nec essary to troubleshoot or reset all or part of the system Basic troubleshooting for the Room Thermostat If a fault occurs in the room thermostat the room thermostat display shows Err while an error code is displayed The meaning and possible...

Страница 23: ...dergone learning for the unit must be reset Things to consider A system that consists of multiple receivers in a single network is affected if a unit is deleted reset The net work stops working if a unit is deleted Following a reset the receiver can be re pro grammed to the network Note If the reset unit was a Master unit in the network all Slave units and all the room thermo stats in the system m...

Страница 24: ...r Red light flashing for current channel 09 ERR Reset the error by cutting power supply Check the actuator if error recurs R sends error code to RT 10 Total voltage for actua tor outputs too high Red light on R L light 10 ERR Error occurs when too many actuators connect ed either per output or total for entire R Check the number of actuators Reset error by cutting the power supply R sends error co...

Страница 25: ...ique Measuring accuracy 0 2 C Radio frequency 868 MHz Dimensions 100 x 100 x 20 mm Protection class IP20 Working temperature 1 50 C Storage temperature 20 70 C Maximum humidity during storage No condensation Article name LK Room Thermostat W ICS 2 Setting range 7 40 C Supply voltage 5 V Control function Self modulation technique Measuring accuracy 0 2 C Dimensions 100 x 100 x 20 mm Protection clas...

Отзывы: