The Little Giant junction box and alarm kit, Model JBAK, provides 
a junction box for making all electrical connections for Little Giant 
automatic grinder pumps. It includes a UL/CSA listed non-mercury, 
mechanically activated float switch that operates the alarm beacon 
that alerts the user of a high water condition. The alarm does not 
include an audible alarm buzzer. 
These instructions should be read completely before beginning 
the installation and must remain with the unit at all times.

SAFETY GUIDELINES

 1. MAKE SURE ALL POWER IS DISCONNECTED PRIOR TO 

MAKING ANY CONNECTIONS!

 2. VERIFY THAT THE PROPER VOLTAGES ARE AVAILABLE 

FOR THE AUTOMATIC GRINDER PUMP AND THE ALARM 
CIRCUIT. IF UNSURE OF LINE VOLTAGE, PHASE OR 
OTHER SOURCE ELECTRICAL PARAMETERS, CONSULT 
A QUALIFIED ELECTRICIAN BEFORE PROCEEDING WITH 
INSTALLATION.

 3. THIS SYSTEM REQUIRES TWO VOLTAGE SUPPLIES: 

ONE FOR THE PUMP AND ONE FOR THE ALARM, WITH 
A NEUTRAL LINE SUPPLIED WITH THE 120 VOLT (115 
VOLT, NOMINAL) ALARM CIRCUIT SUPPLY. 

 4. ENSURE ALL SYSTEMS ARE PROPERLY GROUNDED. 

THERE SHOULD BE A GROUND WIRE FROM THE 200-208 
VOLT OR 230 VOLT INCOMING PUMP POWER, A GROUND 
WIRE FROM THE 115 VOLT INCOMING ALARM POWER 
AND A GROUND WIRE FROM THE PUMP POWER CORD. 
A GROUNDING LUG IS PROVIDED ON THE BACK PLATE OF 
THE ENCLOSURE AND THE BOTTOM TERMINAL OF THE 
TERMINAL BLOCK IS ALSO CONNECTED TO GROUND.

  5. DO NOT CONNECT THE NEUTRAL TO GROUND.
  6.  ALL TERMINAL BLOCK CONNECTIONS MUST BE CLOSELY 

INSPECTED TO ASSURE THAT THERE IS NO WIRE 
INSULATION IN THE TERMINAL AND THAT THERE ARE 
NO WIRE STRANDS STICKING OUT OF THE TERMINAL.

 7. MAKE ALL CONNECTIONS IN THE JUNCTION BOX PER 

FEDERAL, STATE OR PROVINCIAL AND LOCAL ELECTRICAL, 
BUILDING AND PLUMBING CODES.

INSTALLATION

  1.  Determine a convenient location for mounting the junction box, 

preferably close to the grinder pump installation. The location 
should allow clear visibility of the alarm beacon. Avoid wet 
locations such as beneath sweating pipes or faucets.

  2.  The junction box has four corner-located mounting holes. The 

junction box should be mounted to a wall or secure vertical 
structure. Use the appropriate attachment means, i.e., lock 
washers, anchors for masonry or concrete, etc. to securely 
mount the junction box.

  3.  Connect the incoming pump power, 200-208 VAC or 240 VAC 

(230 volt nominal), to the 25-Amp circuit breaker, CB1.

 4. Connect the pump on/off float switch, FS-1, to the terminals 

marked 1 and T1 on the top of the terminal block. The label 

on the back plate, adjacent to the terminal block, indicates that 

these are the terminals for FS-1.

 5. Connect the black and white pump power cord wires to the 

terminals marked T1 and T2 on the top of the terminal block. 

The label on the back plate indicates that these are the terminals 

for the PUMP.

 6. Connect the mechanically activated alarm float switch that is 

included with the kit to the terminals marked 2 and 3 on the 

top of the terminal block. The label on the back plate indicates 

that these are the terminals for the alarm float, FS-2.

  7.  Connect the 115 VAC alarm power supply to the line (L), neutral 

(N) and ground (G) terminals. The ground terminal of the ter-

minal block has been connected to the screw on the lower left 

corner of the back plate. This leaves the back plate ground lug 

available for connection of the ground wires from the incoming 

pump power supply and the pump power cord.

  8. Switch the CB1 circuit breaker to the ON position and test the 

pump and alarm circuit for proper operation.

F

 INTRODUCTION

La boîte de dérivation et la trousse d’alarme de Little Giant, modèle 

JBAK, permet d’effectuer toutes les connexions électriques pour 

les pompes broyeuses automatiques de Little Giant. Elle comprend 

un interrupteur à flotteur sans mercure, homologué UC/CSA et 

activé mécaniquement, qui fait fonctionner le voyant d’avertisseur 

et signale à l’utilisateur la présence d’un niveau d’eau élevé.  

L’alarme n’inclut pas de sonnerie audible.    
Lire toutes les instructions avant de commencer l’installation et les 

garder avec l’appareil en tout temps.

DIRECTIVES DE SECURITE

 1. S’ASSURER QUE TOUTE SOURCE D’ALIMENTATION 

ÉLECTRIQUE EST DÉBRANCHÉE AVANT D’EFFECTUER 

UNE CONNEXION!

 2. VÉRIFIER QUE LES TENSIONS ADÉQUATES SONT 

DISPONIBLES POUR LA POMPE BROYEUSE AUTOMATIQUE 

ET LE CIRCUIT D’ALARME. S’IL Y A LE MOINDRE DOUTE 

QUANT À LA TENSION, LA PHASE OU D’AUTRES 

PARAMÈTRES ÉLECTRIQUES, CONSULTER UN ÉLECTRICIEN 

QUALIFIÉ AVANT DE COMMENCER L’INSTALLATION.

 3. CE SYSTÈME EXIGE DEUX SOURCES DE TENSION: UNE 

POUR LA POMPE ET UNE POUR L’ALARME, DE MÊME 

QU’UNE LIGNE NEUTRE FOURNIE AVEC L’ALIMENTATION 

DU CIRCUIT D’ALARME DE 120 VOLTS (115 VOLTS 

NOMINAL).   

  4.  VÉRIFIER QUE TOUS LES SYSTÈMES SONT CORRECTEMENT 

MIS À LA TERRE. UN FIL DE MISE À LA TERRE DOIT 

PROVENIR 1) DE LA POMPE D’ENTRÉE DE 200-208 VOLTS 

OU 230 VOLTS, 2) DE L’ALIMENTATION D’ALARME DE 

115 VOLTS ET 3) DU CORDON D’ALIMENTATION DE LA 

POMPE. LA PLAQUE ARRIÈRE DE L’ENCEINTE COMPORTE 

UNE PATTE DE MISE À LA TERRE ET LA BORNE INFÉRIEURE DE 

LA PLAQUE À BORNES EST ÉGALEMENT MISE À LA TERRE.

  5. NE PAS CONNECTER LE NEUTRE À LA TERRE.
  6.  INSPECTER SOIGNEUSEMENT TOUTES LES CONNEXIONS 

DE LA PLAQUE À BORNES POUR S’ASSURER QU’IL N’Y A 

AUCUNE ISOLATION DE FIL DANS LA PLAQUE À BORNES 

ET QU’AUCUN FIL N’EN DÉPASSE.

 7. EFFECTUER TOUS LES BRANCHEMENTS DANS LE 

BOÎTIER DE DÉRIVATION EN RESPECTANT TOUS LES 

RÈGLEMENTS FÉDÉRAUX, PROVINCIAUX ET LOCAUX DE 

PLOMBERIE ET D’ÉLECTRICITÉ.

1

Model • Modèle • Modelo

JBAK

Pump • Pompe • Bomba

Franklin Electric Co., Inc.

P. O. Box 12010

Oklahoma City, OK 73157-2010

405.947.2511 • Fax: 405.947.8720

www.LittleGiantPump.com

[email protected]

Отзывы: