‘Suction Lift’ Condensate Pump

 

The EC-1-DV model is designed to accommodate multiple electrical requirements within one pump. 
The DV suffix indicates that the pump is capable of operating from a wider range of supply voltages 
to maintain consistent performance. Similar to our EC-1 model, this model incudes improved noise 
reduction, reliable solid-state switching technology, and easy to install mounting brackets to create a 
pump that benefits contractors, installers, and end-users. 
 

 

Normally-closed relay rated at 8 A resistive - 250 V 
alarm 

 

21 dB(A) 

 

6 mm pump discharge outlet 

 

Elastomeric mounting grommets on pump housing 
bracket 

 

Elastomeric passive vibration isolator used to 
dampen pump vibration  

 

Separate wall bracket for pump and reservoir 
(included)  

 

Thermal protection: 80 °C 

 

1.5 m power cable 

 

1 m communications cable (pump to reservoir) 

 

Ambient temperature range: 0 °C - 60 °C 

 

Maximum water temperature: 60 °C  

 

Clear reservoir for instant visual inspection of water level, float, and filter  

 

Hall effect on/off level sensors with high water safety sensor feature 

 

Extra-large filter screen for longer intervals between cleaning 

 

Multi-step drain hose adapter (14 mm, 16 mm, 18 mm, and 20 mm)  

 

Simple to open reservoir for easy maintenance  

 

Height: 104mm Length: 46mm Width: 58mm 

Suction Lift: 

1m 

Shut Off:  

10m 

Liquid Temp: 

60°C  

Discharge: 

6. mm 

Electrical: 

230V, 50Hz 

MODEL: 

553502 

 

 

 

NOTE: Use on A/C units up to 6kW… 

No larger! 

IMPORTANT 

INSTALLATION BY HVAC-R 

PROFESSIONALS ONLY 

Содержание EC-1-DV

Страница 1: ...bracket Elastomeric passive vibration isolator used to dampen pump vibration Separate wall bracket for pump and reservoir included Thermal protection 80 C 1 5 m power cable 1 m communications cable pump to reservoir Ambient temperature range 0 C 60 C Maximum water temperature 60 C Clear reservoir for instant visual inspection of water level float and filter Hall effect on off level sensors with hi...

Страница 2: ...ndensate during the most severe temperature conditions See performance curve for typical pump flow rate and maximum amount of condensate that can be removed for any given discharge head Failure to consider this could result in overflowing of water from the condensate pump reservoir The EC 1 consists of two main parts the water collection reservoir and control unit pump The water collection reservo...

Страница 3: ...ght result from an inoperative or leaking pump due to power outages discharge line blockage or any reason a backup system s and or alarm should be used 4 Support pump and piping tubing when assembling and when installed Failure to do so may cause piping tubing to break become disconnected from pump and or cause pump to fail or not operate correctly etc 5 The control unit pump is not submersible an...

Страница 4: ... handler Position reservoir on flat surface near end of drain hose with reservoir inlet facing air handler drain hose Locate the collection reservoir in a suitable position where the reservoir can be gravity fed by condensate water from the air handler s drip tray 2 Use supplied double sided foam tape to secure bottom of reservoir to horizontal surface 3 Installing reservoir outside air handler Us...

Страница 5: ...x 1 26mm deep at each point marked on the wall then insert an anchor fully into each hole 6 Using the supplied screws attach the mounting bracket to the wall Hand tighten the wall anchor screws against rubber grommet being careful so that screw head does not push through rubber grommet 7 Slide pump onto wall bracket by inserting slots of bracket into flanges of black mounting grommets on side of p...

Страница 6: ...d pump life 6 Ensure that there are no kinks twists or breaks in the discharge tubing that could cause blockage If cable ties are used to strap tubing to structures assure that cable ties do not crush or squeeze closed the tubing Vent Tubing 1 Connect the 1 4 ID 6mm tubing to the vent port of the reservoir cover The free end of the vent tubing must be secured above the highest level of the drip tr...

Страница 7: ...ceptable for the air conditioner in the application 3 If acceptable confirm which thermostat wire is to be interrupted 4 This connection can also be used with central control systems to control the air conditioner operation 5 NOTE When connected in this manner if a high water condition occurs the air conditioner should not run until the high water condition is fixed This method should not be used ...

Страница 8: ... carefully remove the reservoir assembly from its installed position 2 Depress the latch on the side of reservoir top and tilt upward to remove being careful not to damage the reservoir gasket 3 Remove the mesh screen and rinse thoroughly under running water 4 Use a damp towel to remove dust or debris from the reservoir 5 The float should stay in place on the reservoir top however if it has signs ...