background image

 

 

SB6100 Industrial Shock Block

 

Page 19 

    Rev. 1-I-071520 

 

 

 

7.  Technical Specifications 

7.1  SB6100 

Voltage, Current, and Power Ratings

(1)

:

 

Option 0: 

Voltage ........................................... 3 PH, 3 wire (no neutral),  

     

50/60 Hz

(2)

,

 208 Vac 

     

(+10, -15%) 

Current: 

  AC-1 ................................................... 100 A 

  AC-3 ................................................... 75 A 

    Breaking Capacity ........................ 8 x 75 A 

    Making Capacity .......................... 10 x 75 A 

  Power (AC-3) .................................... 25 hp 

 

Option 1: 

  Voltage ....................................... 3 PH, 3 wire (no neutral), 

     

50/60 Hz

(2)

, 240 Vac  

     

(+10, -15%) 

Current: 

  AC-1 ................................................... 100 A 

  AC-3 ................................................... 75 A 

    Breaking Capacity ........................ 8 x 75 A 

    Making Capacity .......................... 10 x 75 A 

  Power (AC-3) .................................... 30 hp 

 

Option 2: 

Voltage ........................................... 3 PH, 3 wire (no neutral), 

     

50/60 Hz

(2)

, 480 Vac 

     

(+10, -15%) 

Current: 

  AC-1 ................................................... 100 A 

  AC-3 ................................................... 66 A 

    Breaking Capacity ........................ 8 x 66 A 

    Making Capacity .......................... 10 x 66 A 

  Power (AC-3) .................................... 60 hp 

 

Option 3: 

Voltage ........................................... 3 PH, 3 wire (no neutral), 

     

50/60 Hz

(2)

, 600 Vac 

     

(+10, -15%) 

Current: 

  AC-1 ................................................... 100 A 

  AC-3 ................................................... 55 A 

    Breaking Capacity ........................ 8 x 55 A 

    Making Capacity .......................... 10 x 55 A 

  Power (AC-3) .................................... 75 hp 

 

Trip Level Settings: 

  GFCI Class A ........................... Fixed 6 mA 

  GFCI Class C and Class D ....... Fixed 20 mA 

  EGFPD..................................... 6, 10, 20, 30, 40, 50, 60 

     

70, 80, 90, and 100 mA 

Trip Time ..................................... Defined by: 

     

 

     

or minimum 20 ms. 

     

See Section 4.1. 

Wiring and Torque Requirements: 

Input Terminals: 

  Conductor Size ..................... 14 to 2/0 AWG  

   

(2.08 to 67.4 mm

2

)

 

Torque: 

  14 to 2/0 AWG 

  (2.08 to 67.4 mm

2

) ............. 275 lbf

in (31.1 N

m)  

 

  Output Terminals: 

    Conductor Size ..................... 14 to 2/0 AWG 

     

(2.08 to 67.4 mm

2

)

 

    Torque: 

      6 to 2/0 AWG 

      (13.3 to 67.4 mm

2

) ............. 120 lbf

in (13.6 N

m) 

      14 to 8 AWG 

       (2.08 to 8.36 mm

2

) ............. 40 lbf

in (4.5 N

m) 

 

Ground Terminals: 

  Conductor Size ......................... 14 to 1/0 AWG 

     

(2.08 to 53.5 mm

2

  Torque: 

    14 to 10 AWG 

    (2.08 to 5.26 mm

2

) ................ 35 lbf

in (4.0 N

m) 

    8 AWG 

    (8.36 mm

2

) ............................ 40 lbf

in (4.5 N

m) 

    6 to 4 AWG 

     (13.3 to 21.1 mm

2

) ................ 45 lbf

in (5.1 N

m) 

    3 to 1/0 AWG 

    (26.7 to 53.5 mm

2

) ................ 50 lbf

in (5.6 N

m) 

 

Ground-Check and Auxiliary Terminals: 

  Conductor Size ......................... 22 to 12 AWG  

 

(0.33 to 3.3 mm

2

 

PWB Conformal Coating ............. MIL-1-46058 qualified 

     

UL QMJU2 recognized 

 

Ground-Check Circuit: 

  Open-Circuit Voltage ............... 12 Vdc 

  Output Impedance .................... 20

0 Ω

 

  Nominal Loop Current ............. 30 mA 

  Induced ac Withstand ............... 25 Vac  

  GC-Loop Trip Resistance ........ 38 ± 2 

 

 

Auxiliary Contact: 

  Contact Configuration .............. Normally Open (N.O.) 

  UL Rating 

    4 A Resistive ........................ 220/240 Vac 

    0.3 A Resistive ..................... 250 Vdc 

 

Содержание Industrial Shock Block SB6100

Страница 1: ...1 800 832 3873 E mail relays littelfuse com Littelfuse com SB6100 SB6100 MANUAL INDUSTRIAL SHOCK BLOCK REVISION 1 I 071520 Copyright 2020 by Littelfuse Inc All rights reserved Document Number PM 1500...

Страница 2: ...nical Specifications 19 7 1 SB6100 19 7 2 AC6000 Cart 21 7 3 AC6000 MNT 21 8 Ordering Information 21 Appendix A SB6100 Revision History 22 LIST OF FIGURES FIGURE PAGE 1 UL GFCI Classes 1 2 Three Phase...

Страница 3: ...r 1 1 1 SB6100 GFCI GFCI models are permanently connected GFCIs that meet the requirements of the UL 943 definition for Class A devices with a fixed 6 mA trip level It is available only for 208 Vac sy...

Страница 4: ...equired voltage and current ratings necessary for the application SB6100 installation should be performed by a qualified person 2 1 Mounting 2 1 1 Open Chassis Models SB6100 XX0 0 Open chassis models...

Страница 5: ...ons and can be implemented if desired for Class A GFCI or EGFPD models Use only a Littelfuse termination device as others may not meet performance requirements Each SB6100 GFCI is supplied with a 1N53...

Страница 6: ...SB6100 Industrial Shock Block Page 4 Rev 1 I 071520 FIGURE 2 Three Phase Connection Diagram GFCI Configuration Shown...

Страница 7: ...SB6100 Industrial Shock Block Page 5 Rev 1 I 071520 FIGURE 3 SB6100 311 0 Enclosed Model Lid not shown...

Страница 8: ...SB6100 Industrial Shock Block Page 6 Rev 1 I 071520 FIGURE 4 Open Chassis Model SB6100 310 0 Outline and Mounting Details...

Страница 9: ...SB6100 Industrial Shock Block Page 7 Rev 1 I 071520 FIGURE 5 Enclosed Model SB6100 311 0 Outline and Mounting Details...

Страница 10: ...SB6100 Industrial Shock Block Page 8 Rev 1 I 071520 FIGURE 6 SB6100 Operator Interface AC6000 OPI 00 Outline and Mounting Details FIGURE 7 SB6100 Operator Interface AC6000 OPI 00 Faceplate...

Страница 11: ...SB6100 Industrial Shock Block Page 9 Rev 1 I 071520 FIGURE 8 Enclosed Model SB6100 XX1 0 Bottom View Terminal Block Locations FIGURE 9 1N5339B Zener Diode and SE TA6 SM Termination Devices...

Страница 12: ...SB6100 Industrial Shock Block Page 10 Rev 1 I 071520 FIGURE 10 SE TA6 Termination Assembly FIGURE 11 SE TA6ASF WL Small Format Termination Assembly with Wire Leads...

Страница 13: ...and 100 of the trip level For an EGFPD the trip level can be selected from 6 to 100 mA For a GFCI the trip level is fixed at 6 mA Class A or 20 mA Class C and D Table 1 describes the operation of the...

Страница 14: ...When supply voltage to the SB6100 is removed the contactor will open and the green PWR and EN LEDs will turn off For a short supply outage of approximately 20 seconds the SB6100 will remain powered u...

Страница 15: ...the above formula UL 943 also defines a limit to the formula with a minimum required trip time or fastest trip speed of 20 ms which occurs at about 300 mA of ground fault current I per the formula Cla...

Страница 16: ...erruption of the circuit under both of the following conditions a An open grounding circuit and b Impedance in the grounding circuit that would allow more than a 150 volt drop in the grounding circuit...

Страница 17: ...priority over undervoltage i e if both conditions occur at the same time the INP LED will stay on indicating a miswire until the connection is fixed then it will flash if the undervoltage condition st...

Страница 18: ...SB6100 Industrial Shock Block Page 16 Rev 1 I 071520 FIGURE 16 AC6000 CART 00 Outline...

Страница 19: ...SB6100 Industrial Shock Block Page 17 Rev 1 I 071520 FIGURE 17 AC6000 MNT 00 Outline...

Страница 20: ...SB6100 Industrial Shock Block Page 18 Rev 1 I 071520 FIGURE 18 AC6000 CART with SB6100 Installed...

Страница 21: ...10 20 30 40 50 60 70 80 90 and 100 mA Trip Time Defined by or minimum 20 ms See Section 4 1 Wiring and Torque Requirements Input Terminals Conductor Size 14 to 2 0 AWG 2 08 to 67 4 mm2 Torque 14 to 2...

Страница 22: ...hipping Dimensions SB6100 XX0 0 Open Chassis Models Height 508 mm 20 0 in Width 406 mm 16 0 in Depth 203 mm 8 0 in SB6100 XX1 0 Enclosed Models Height 550 mm 21 6 in Width 490 mm 19 2 in Depth 240 mm...

Страница 23: ...and any cable and accessories 2 Includes the AC6000 MNT 00 7 3 AC6000 MNT Maximum Holding Weight 1 40 kg 90 lb Dimensions Height 705 mm 28 0 in Width 648 mm 25 5 in Depth 152 mm 6 0 in Shipping Dimens...

Страница 24: ...SECTION 7 SECTION 8 Class A GFCI models added REVISION 1 H 032618 SECTION 2 Section 2 2 1 removed Fig 3 removed all other Figures renumbered GENERAL SB6100 enclosure has been changed to grey REVISION...

Страница 25: ...ION 2 AC6000 CART 00 and AC6000 MNT 00 figures added SECTION 7 AC6000 CART 00 Section 7 2 and AC6000 MNT 00 Section 7 3 specifications added SECTION 8 AC6000 CART 00 AC6000 OPI 00 and AC6000 MNT 00 ad...

Отзывы: