Littelfuse Industrial Shock Block SB5000 Series Скачать руководство пользователя страница 6

 

SB5000 Industrial Shock Block

 Page 

  Rev. 

1-B-101821 

 

 

1.1.3  SB5000 EGFPD 

  EGFPD 

models 

can 

be 

set 

to 

trip 

at  

6 mA or from 10 to 100 mA in increments of 10 mA, and 
meet 

the 

requirements 

of 

UL 

943 

and  

UL  1053.    The  adjustable  trip  level  can  help  prevent 
nuisance tripping in some applications.  
  If  required  by  the  application,  a  load-ground-
connection  monitor  feature  can  be  enabled  for  EGFPD 
models. See Section 2.5. 

1.2  F

EATURES 

 

UL 943 inverse time curve reduces the probability of 
nuisance tripping. 

 

UL  943  fixed  trip  level  (Class  A  GFCI  models) 
provides  protection  meeting  NEC  210.8  (B)  for 
commercial  kitchens,  wet  areas,  and  other 
applications. 

 

UL  943C  fixed  trip  level  (GFCI  models)  provides 
protection  for  systems  with  leakage  current  higher 
than the 6-mA trip level required by Class A GFCIs. 

 

Selectable  trip  levels  (EGFPD  models)  help  reduce 
nuisance tripping by allowing users to adjust the trip 
level in systems that have leakage current higher than 
UL 943 Class A 6-mA trip level

,

 or UL 943C Class C 

or D 20-mA trip level. 

 

UL  943C  ground-connection  monitoring  ensures 
continuity of the load ground. 

 

Undervoltage,  brown-out  and  chatter  detection 
prolong the internal contactor lifetime. 

 

Meets UL 1998 requirements. 

 

Self-test  feature  continuously  monitors  hardware  to 
ensure safe operation. 

 

Conformally coated circuit boards. 

1.3   O

PERATOR 

I

NTERFACE

 

   The  operator  interface  includes  LED  status  indication 
including the following: 

-

 

POWER 

-

 

ENABLE 

-

 

GF TRIP 

-

 

GC STATUS 

-

 

TEST and RESET buttons 
 

2.  I

NSTALLATION 

  The SB5000 is considered to be a permanently mounted 
GFCI/EGFPD and should be attached to a wall or other 
suitable mounting surface. 
  The  connection  diagram  for  three-phase  systems  is 
shown  in  Fig.  2.  Ensure  that  all  conductors  have  the 
required  voltage  and  current  ratings  necessary  for  the 
application.  SB5000 installation should be performed by 
a qualified person. 

 

 

 

2.1  M

OUNTING

 

  Install  SB5000  models  in  the  correct  orientation  as 
shown  in  Fig.  5,  and  refer  to  the  ‘This  Side  Up’  label 
attached to the side of the enclosure.   
  Enclosed  models  ship  with  no  cable  entry  points 
predrilled.    Appropriate  holes  must  be  made  in  the 
enclosure  and  fitted  with  NEMA-4X-rated  (and  IP69K-
rated  when  required)  fittings  for  the  installation  of  all 
conductors.  Space is left near the bottom or lower sides 
of the enclosure to install the wiring.  See Figs. 3 and 6. 

2.2  S

UPPLY 

C

ONNECTIONS

 

  The supply phases are marked Input A, B, and C on the 
base of the chassis as shown in Fig. 3.  Use a flat-blade 
screwdriver to tighten the input connections.  Torque the 
input  terminals  as  described  in  Section  6.    The  input 
terminals  will  accept  4  to  18  AWG  copper  wire 
conductors. 

2.3  L

OAD 

P

HASE

 C

ONNECTIONS

 

  The load phases are marked Output A, B, and C on the 
base of the chassis as shown in Fig. 3.  Use a flat-blade 
screwdriver to tighten the output connections.  Torque the 
output  terminals  as  described  in  Section  6.    The  output 
terminals  will  accept  4  to  18  AWG  copper  wire 
conductors. 

2.4  G

ROUND 

C

ONNECTIONS

 

  Connect the supply and load ground conductors to the 
chassis bonding point 

( ) 

as shown in Fig. 3.  Use a flat-

blade  screwdriver  to  tighten  the  ground  connections.  
Torque  the  ground  terminals  as  described  in  Section  6.  
The ground terminals will accept 14 to 1/0 AWG (2.08 to 
53.5 mm

2

) conductors. 

 

2.5  L

OAD-

G

ROUND-

C

ONNECTION 

M

ONITOR  

  An insulated pilot wire from the SB5000 to the load, 
and a termination device located at the load are required 
to monitor the load-ground connection.  Total pilot wire 
and ground wire resistance must be less than 28 ohms (trip 
resistance is 38 ohms).  Outline dimensions and mounting 
details  for  compatible  termination  devices  are  shown  in 
Figs. 7, 8, and 9.   
  This  monitoring  function  is  required  for  Class  C  and 
Class D GFCI models installed in NEC applications, and 
can  be  implemented  if  desired  for  Class  A  GFCI  or 
EGFPD models. 
  Use only a Littelfuse termination device as others may 
not meet performance requirements.  Each SB5000 GFCI 
is  supplied with  a  1N5339B termination device.   Install 
the termination device at the load to complete the ground-
connection loop as shown in Fig. 2.  Connect terminal G 
of the termination device to the equipment frame so that 
the  ground-conductor-to-equipment-frame  connection 
will be included in the monitored loop.  Connect terminal 
GC of the termination device to the pilot wire, and connect 

Содержание Industrial Shock Block SB5000 Series

Страница 1: ...Tel 1 800 832 3873 E mail relays littelfuse com www littelfuse com SB5000 SB5000 MANUAL INDUSTRIAL SHOCK BLOCK REVISION 1 B 101821 Copyright 2021 by Littelfuse Inc All rights reserved...

Страница 2: ...SB5000 Industrial Shock Block Page i Rev 1 B 101821 This page intentionally left blank...

Страница 3: ...irements 11 4 UL 943C Requirements 12 4 1 Trip Time 12 4 2 Grounding Circuit 12 4 3 Grounding Monitor Interrupter 12 5 Troubleshooting 13 6 Technical Specifications 14 6 1 SB5032 Series 14 6 2 SB5060...

Страница 4: ...SB5000 Industrial Shock Block Page iii Rev 1 B 101821 This page intentionally left blank...

Страница 5: ...priate for many industrial and commercial applications Special purpose SB5000 GFCIs Class C or Class D can be used in the following applications 3 Phase Grounded neutral systems where voltage to groun...

Страница 6: ...y points predrilled Appropriate holes must be made in the enclosure and fitted with NEMA 4X rated and IP69K rated when required fittings for the installation of all conductors Space is left near the b...

Страница 7: ...d at the GC and REF terminals The termination device should remain installed at the GC and REF terminals if the load ground connection monitoring feature is not required See Fig 3 2 6 Trip Status Term...

Страница 8: ...SB5000 Industrial Shock Block Page 4 Rev 1 B 101821 FIGURE 3 SB5060 x11 0 Model Lid not shown...

Страница 9: ...SB5000 Industrial Shock Block Page 5 Rev 1 B 101821 FIGURE 4 SB50xx Lid closed...

Страница 10: ...SB5000 Industrial Shock Block Page 6 Rev 1 B 101821 FIGURE 5 SB50xx Outline and Mounting Details...

Страница 11: ...tions FIGURE 7 1N5339B Zener Diode and SE TA6 SM Termination Devices 69 9 2 75 G GC TERMINATION MUST BE INSTALLED AT LOAD G 1N5339B 0 25 28 UNF SE TA6 SM G GC 35 0 1 38 250 9 84 LENGTH OF 14 AWG YELLO...

Страница 12: ...DIMENSIONS IN MILLIMETRES INCHES 2 TERMINAL BLOCK SCREWS 6 32 x 0 25 3 MOUNTING SCREWS M4 OR 8 32 4 ENCLOSURE IS ELECTRICALLY CONNECTED TOTERMINAL G 5 CAN BE IMMERSED IN GLYCOL NOTE 2 4 0 0 16 50 8 2...

Страница 13: ...more conditions may have caused a trip If the GF TRIP LED is flashing the SB5000 has detected an undervoltage overvoltage chatter or temperature limit condition See Table 1 and Sections 3 5 and 3 6 3...

Страница 14: ...tter Detection trip Undervoltage trip or Overvoltage trip will require a manual reset after returning to a normal state 3 4 INPUT CONNECTION The SB5000 electronics are supplied from input phases A and...

Страница 15: ...43C load ground monitor requirements For EGFPD and GFCI Class A models load ground connection monitoring is optional 3 10 UL 943 SELF TEST AND UL 1998 REQUIREMENTS The 2015 revision to the UL 943 stan...

Страница 16: ...5 to 20 mA non adjustable See Fig 15 The SB5000 EFGPDs described in this manual also operate within the Class A formula but have a 6 to 100 mA threshold setting range 4 2 GROUNDING CIRCUIT The equipme...

Страница 17: ...s within acceptable limits and press RESET ON OFF OFF ON RED Load Ground Connection Open Check load ground pilot wire and termination device 1 ON OFF OFF FLASH RED 1 S 1 L GC Short detected Check resi...

Страница 18: ...c Option Voltage 3 PH 3 wire no neutral 60 Hz 2 480 Vac 10 15 Current AC 1 60 A AC 3 60 A Breaking Capacity 5 x 60 A Making Capacity 5 x 60 A Power AC 3 40 hp 600 Vac Option Voltage 3 PH 3 wire no neu...

Страница 19: ...9K Polycarbonate Lockable Dimensions Height 285 7 mm 11 2 in Width 244 3 mm 9 6 in Depth 119 6 mm 4 7 in Shipping Weight All Models 4 5 kg 10 lb Environment Operating Temperature UL Rating 35 to 66 C...

Страница 20: ...ermination Assemblies 1 1N5339B 5 W Axial Lead Termination Device SE TA6 50 W Termination Assembly SE TA6 SM 50 W Stud Mount Termination Assembly SE TA6ASF WL 12 W Small Format Termination Assembly wi...

Страница 21: ...ctober 18 2021 1 B 101821 02 01 1 23 May 28 2021 1 A 052821 00 MANUAL REVISION HISTORY REVISION 1 B 101821 UL approval for Class A and EGFPD models REVISION 1 A 052821 Initial release PRODUCT REVISION...

Отзывы: