Page 20 

 SE-330 

Neutral-Grounding-Resistor 

Monitor

 Rev. 

9-A-112913 

 
 

 

3.3  G

ROUND

-F

AULT

 CT 

  Select and install a ground-fault CT that will provide 
the desired trip level.  Typically, the CT-primary rating 
should approximately equal the NGR let-through-current 
rating.  This provides an appropriate GF TRIP LEVEL 
setting range and analog-output scaling.  See 

 

Section 2.1.2 and 2.9. 
  Outline and mounting details for the sensitive EFCT- 
and SE-CS30-series current sensors are shown in Figs. 
16, 17, and 18.  Ground-fault-CT connections and the 
typical ground-fault-CT location are shown in Fig. 3. 
  For SE-325 replacement applications, the existing  
CT200 current transformer will typically have to be 
replaced.  However, where replacement is not necessary 
or possible, the CT200 can be connected to either the 1- 
or 5-A input.  This CT has a 200:5 current ratio.  If 
connected to the 1-A input, the ground-fault trip level 
will be a percentage of 40 A.  See Section 2.1.2. 
  The accuracy of a typical current transformer, 
including the CT200, decreases below 5% of its current 
rating.  CT-primary current injection testing is 
recommended to verify trip levels below 5% of the  
CT-primary rating.  See Section 9.4.  Littelfuse Startco 
sensitive current sensors are designed for use at low 
levels and respond linearly to 2% current rating. 
 

N

OTE

:

  The current-transformer insulation class is of no 

consequence if its secondary is grounded and the 
conductors through its window are insulated for the 
system voltage.  Medium-voltage systems may require a 
bushing-type CT. 

 
 

Содержание SE-330 Series

Страница 1: ...4 1 6 1 8 2 0 2 2 2 4 2 6 2 8 3 0 SE 330 NEUTRAL GROUNDING RESISTOR MONITOR 0 2 0 3 0 4 CAL RESET GF TRIP TIME s PULSE PERIOD s GF TRIP LEVEL CT RATING LITTELFUSE STARTCO TRIP GROUND FAULT POWER RELA...

Страница 2: ...31 9 1 Resistor Fault Tests 31 9 1 1 Calibration and Open Test 31 9 1 2 Voltage Test 31 9 2 Sensing Resistor Test 31 9 3 Analog Output Test 31 9 4 Ground Fault Performance Test 32 LIST OF FIGURES FIG...

Страница 3: ...it difficult to monitor NGR continuity A transformer can provide the inductance necessary to cause ferroresonance if the NGR opens Following these guidelines will reduce the flash hazard reduce point...

Страница 4: ...s greater than the time for fault current below the trip level 2 1 2 GF TRIP LEVEL The SE 330 uses a Discrete Fourier Transform DFT algorithm to measure the fundamental component of NGR current Choose...

Страница 5: ...200 5 Amperes 400 1 400 5 Amperes 2 4 6 8 10 15 20 40 60 80 100 0 10 0 20 0 30 0 40 0 50 0 75 1 00 2 00 3 00 4 00 5 00 0 60 1 20 1 80 2 40 3 00 4 50 6 00 12 0 18 0 24 0 30 0 5 7 5 10 20 30 40 50 8 10...

Страница 6: ...cycled with S8 in the UPGRADE position See Section 4 1 3 2 2 CALIBRATION The SE 330 measures the resistance change of the NGR relative to the NGR resistance value determined at the time of calibration...

Страница 7: ...s are shown in Fig 19 Connect them as shown in Fig 3 RK 332 components are not polarity sensitive Network enabled SE 330 s can be remotely tripped and reset by the network master The red DIAGNOSTIC LE...

Страница 8: ...erminal blocks Each plug in terminal block can be secured to the monitor by two captive screws for reliable connections Outline dimensions and mounting details for surface mounting the SE 330 are show...

Страница 9: ...E SEPARATE LUGTO CONNECT SENSING RESISTORTERMINAL NTO NEUTRAL 2 LOCATETHESE COMPONENTS NEAR TRANSFORMER OR GENERATOR 3 ALTERNATE SENSING RESISTOR TERMINAL N CONNECTION THE NEUTRAL CONNECTION IS NOT MO...

Страница 10: ...AR VIEW NOTE 2 92 7 3 65 76 2 3 00 8 2 0 32 186 0 7 32 200 0 7 87 7 0 0 28 R 4 8 0 19 MAXIMUM 4 75 0 187 DIA 4 LOCATIONS PANEL MOUNT CUTOUT NOTES 1 DIMENSIONS IN MILLIMETRES INCHES 2 SE 330 SHOWN WITH...

Страница 11: ...INSTALLATION 1 LOOSEN RETAINER SCREWS MOVE RETAINERS OUTWARD AND TIGHTEN RETAINER SCREWS 2 MATE MONITOR WITH ADAPTER PLUG INTERMINALS LOOSEN RETAINER SCREWSTO LET RETAINERS SNAP OVER MONITOR BACKPLAT...

Страница 12: ...00 NOTES 1 DIMENSIONS SHOWN IN MILLIMETRES INCHES 2 SHOWN WITH WEATHERPROOF SNAPS CLOSED 3 REFERTO PANEL MOUNTING CUTOUT FIGURE 4 FOR PANEL MOUNTING DETAIL TO PREVENT UNAUTHORIZED ENTRY 1 USE WIRE SEA...

Страница 13: ...MONITOR RELAY THROUGH OPENING OF THE WEATHERPROOF WINDOW UNTIL IT IS SECURELY NESTED TO THE BACK OF THE DARK GREY PVC PANEL INSTALL O RING INTOTHE GROOVE INTHE REAR OF WEATHERPROOF WINDOW ASSEMBLY INS...

Страница 14: ...GR s NOTE A parallel ground path created by moisture can result in a false resistor fault trip Sensing resistor terminal R and its connection to SE 330 terminal R including interposing terminal blocks...

Страница 15: ...EW 84 6 3 33 120 4 4 74 20 4 0 80 NOTES 1 DIMENSIONS IN MILLIMETRES INCHES 2 MOUNTING SCREWS M6 OR 0 25 20 120 4 4 74 122 0 4 80 ENCLOSURE TOP VIEW ENCLOSURE TOP VIEW COVER REMOVED 122 0 4 80 120 4 4...

Страница 16: ...STRUCTIONS 1 DRILL HOLE FOR ENCLOSURE WIRE ENTRY USE LIQUID TIGHT GLAND 3 ATTACH GROUND WIRE FROM ENCLOSURETO COVER ANDTO ER 600VC 2 REMOVE NYLON NUTS AND WASHERS INSERT ER 600VC INTO ENCLOSURE REPLAC...

Страница 17: ...E 254 0 10 00 127 0 5 00 254 0 10 00 355 6 14 00 457 0 18 00 50 7 2 00 MOUNTING DETAIL NOTES 1 DIMENSIONS IN MILLIMETRES INCHES 2 TERMINAL BLOCK SCREWS 6 32 x 0 25 3 MOUNTING SCREWS M6 OR 0 25 20 4 TH...

Страница 18: ...OTES 1 DIMENSIONS IN MILLIMETRES INCHES 2 TERMINAL BLOCK SCREWS 6 32 x 0 25 CABLE ACCESS OPENING IS 1 2 NPT USE A LIQUID TIGHT FITTING FOR CABLE ENTRY 3 MOUNTING SCREWS M6 OR 0 25 20 4 THIS DEVICE CAN...

Страница 19: ...4 mA RESISTANCE 100 k THERMAL 1 MINUTE ON 120 MINUTES OFF CONTINUOUS 215 0 8 46 FRONT SIDE 39 5 1 56 444 0 17 50 365 0 14 37 39 5 1 56 MINIMUM DISTANCE TO ADJACENT OBJECTS NOTE 3 MINIMUM CLEARANCE FRO...

Страница 20: ...0 Vac MAXIMUM CURRENT 144 mA RESISTANCE 100 k TOP 320 0 12 60 FRONT SIDE 60 0 2 40 800 0 31 50 340 0 13 38 340 0 13 38 534 0 21 00 217 0 8 50 100 0 3 94 NOTE 3 MINIMUM CLEARANCE FROM BASE 508 0 20 00...

Страница 21: ...TOP 459 0 18 10 FRONT SIDE 1600 0 63 00 800 0 31 50 MINIMUM CLEARANCE FROM BASE 685 0 27 00 350 0 13 80 400 0 15 70 400 0 15 70 NOTE 3 100 0 3 90 350 0 13 80 MINIMUM DISTANCE TO ADJACENT OBJECTS MOUNT...

Страница 22: ...ypically have to be replaced However where replacement is not necessary or possible the CT200 can be connected to either the 1 or 5 A input This CT has a 200 5 current ratio If connected to the 1 A in...

Страница 23: ...5 5 0 22 110 0 4 33 5 5 0 22 22 0 0 87 5 0 0 20 RECESSED FOR 8 mm HEX NUT 1 0 0 04 DEEP FRONT NOTES 1 DIMENSIONS IN MILLIMETRES INCHES 2 MOUNTING SCREWS M4 OR 8 32 3 PRESS MOUNTING FEET IN PLACE USIN...

Страница 24: ...5 0 22 5 5 0 22 110 0 4 33 FRONT SIDE 22 0 0 87 5 0 0 20 RECESSED FOR 8 mm HEX NUT 1 0 0 04 DEEP 30 0 1 18 126 0 4 96 56 0 2 21 MOUNTING FOOT INSTALLATION TOOL DETAIL A NOTES 1 DIMENSIONS IN MILLIMET...

Страница 25: ...2 5 0 0 20 5 0 0 20 58 0 2 28 FRONT 7 0 0 87 4 0 0 16 RECESSED FOR 7 mm HEX NUT 3 0 0 12 DEEP SIDE 26 5 1 04 52 5 2 07 MOUNTING FOOT INSTALLATION TOOL DETAIL A S 1 S 2 P 1 Ground Fault Sensing and Rel...

Страница 26: ...esistor and the SE 330 are connected to an isolated ground the SE 330 will be exposed to the GPR If the GPR is greater than the terminal block rating the SE 330 must be isolated from station ground an...

Страница 27: ...format of eight data bits and one stop bit The baud rate is fixed at 38 400 bits per second Use PC program SE MON330 to display the following data SE 330 settings and switch states Neutral voltage an...

Страница 28: ...RESET to clear the trip If the problem persists consult Littelfuse Startco A D Converter Error Trip DIAGNOSTIC LED flash code L S S S S L An A D converter error was detected Press RESET to clear the t...

Страница 29: ...90 Hz Maximum CT lead resistance EFCT SE CS30 5 Other CT s Consult CT Curve CT Input Burden 5 A Input 0 01 1 A Input 0 05 EFCT Input 10 Thermal Withstand 1 A and 5 A Input Continuous 2 x CT Rating 1...

Страница 30: ...LR 53428 US C R UL Listed Australia 1 CE European Union 1 1 See Ordering Information 6 2 SENSING RESISTORS ER 600VC Maximum Voltage 600 Vac Maximum Current 30 mA Resistance 20 k Thermal Continuous Shi...

Страница 31: ...dow Diameter 26 mm 1 0 Shipping Weight 0 45 kg 1 0 lb Certifications CSA UL CE Compliance RoHS IEC 60044 1 SE CS30 70 Current Ratio 30 0 05 A Insulation 600 V Class Window Diameter 70 mm 2 7 Shipping...

Страница 32: ...vailable at www littelfuse com relayscontrols 8 WARRANTY The SE 330 Neutral Grounding Resistor Monitor is warranted to be free from defects in material and workmanship for a period of five years from...

Страница 33: ...e trip voltage at terminal N not terminal R Procedure Check the ER sensing resistor connection to the SE 330 Disconnect the wire from sensing resistor terminal N A resistor fault trip will occur Set t...

Страница 34: ...alternate ground paths do not exist that bypass the current transformer High voltage testers and resistance bridges can be used to determine the existence of alternate ground paths d Verify proper rea...

Страница 35: ...11 12 OP1 OP2 3 L L1 5 N L2 1 SE 400 REMOTE INPUT 8 9 RMT1 RMT2 b USING SE 100T NEUTRAL TO SE 330 TO SENSING RESISTOR TERMINAL N NGR 0 65 A 2 75 A LO HI C L1 L2 L N REMOTE TEST RMT SE 100T FIGURE 22 G...

Страница 36: ...Page 34 SE 330 Neutral Grounding Resistor Monitor Rev 9 A 112913 This page intentionally left blank...