Littelfuse Startco SE-325 Скачать руководство пользователя страница 5

 

Startco Engineering Ltd.  

Page 1 

 

SE-325 Neutral-Grounding-Resistor Monitor 

Rev. 8 

 
 

Pub. SE-325-M, May 6, 2008. 

1.  G

ENERAL 

1.1  M

ODERN 

R

ESISTANCE-

G

ROUNDED 

S

YSTEMS  

  A high-resistance-grounded system uses a neutral-
grounding resistor (NGR) with a low let-through current 
to limit ground-fault current.  High-resistance grounding 
is gaining popularity because a ground-fault flash hazard 
exists in low-resistance- or solidly grounded systems and 
a ground-fault can result in substantial point-of-fault 
damage.  High-resistance grounding eliminates these 
problems and modern ground-fault protection operates 
reliably at these levels.  Furthermore, the probability of an 
arc-flash incident is significantly reduced in a high-
resistance-grounded system. 
  NGR selection depends on system charging current and 
whether the system is an alarm-only or a tripping system.  
Alarm-only systems are usually restricted to system 
voltages up to 5 kV with NGR let-through currents of 5 A 
or less.  Occasionally, alarm-only systems up to 15 kV 
and up to 10 A are used; however, they are not common 
because a ground fault on such a system tends to escalate 
to a phase-to-phase fault before the ground fault can be 
located and cleared. 
  System charging current is the capacitive current that 
flows to ground when a bolted ground fault occurs.  This 
current can be calculated or measured.  For small systems, 
the magnitude of charging current is typically ½ A per 
1,000 kVA on low-voltage systems and 1 A per  
1,000 kVA on medium-voltage systems. 
  In an alarm-only system or in a tripping system without 
selective coordination, choose an NGR with a let-through 
current larger than the system charging current and set  
the pick-up current of ground-fault devices at or below 
50% of the NGR let-through current. 
  In a tripping system with selective coordination, use 
ground-fault devices with a definite-time characteristic to 
achieve time coordination.  Use the same pick-up current 
for all ground-fault devices—this value must be larger 
than the charging current of the largest feeder.  Select an 
NGR with a let-through current between five and ten 
times the pick-up current of the ground-fault devices. 
  Do not use a grounding transformer with a low-voltage 
resistor: 

 

The combined cost of a transformer and a low-

voltage resistor is more than the cost of a resistor 

rated for line-to-neutral voltage. 

 

A transformer saturated by a ground fault through a 

rectifier can make ground-fault protection 

inoperative. 

 

Transformer inrush current up to twelve times rated 

current can cause a ground-fault voltage larger than 

expected. 

 

A parallel transformer winding makes it difficult to 

monitor NGR continuity.

 

 

A transformer can provide the inductance necessary 

to cause ferroresonance if the NGR opens.

 

 

 

  Following these guidelines will reduce the flash 

hazard, reduce point-of-fault damage, achieve reliable 

ground-fault protection, and ensure a stable system not 

subject to ferroresonance.

 

 

1.2  SE-325 NGR M

ONITORING 

  The SE-325 is a neutral-grounding-resistor monitor for 
resistance-grounded systems up to 25 kVac.  It measures 
current in a transformer or generator neutral, neutral-to-
ground voltage, and continuity of the neutral-grounding 
resistor.  The SE-325 coordinates these three measurements 
to detect a failed NGR or a ground fault and provides one 
output contact for shunt or undervoltage operation in a 
main-breaker trip circuit.  Trips are latched and indicated by 
LED’s. 
  Ground-fault current is sensed by a CT200 window-type 
current transformer.  Either CT input can be grounded to 
meet electrical codes.  A trip level of 0.5, 2.0, or 4.0 A is 
switch selectable for use with a 5-, 15-, or 25-A grounding 
resistor.  Trip time is adjustable from 0.1 to 2.0 seconds. 
  Neutral-to-ground voltage and continuity of the neutral-
grounding resistor are continuously measured through an 
ER-series external sensing resistor connected to the neutral.  
A resistor fault will be detected if ground-fault current is not 
detected and neutral-to-ground voltage exceeds the trip-level 
setting, or if NGR resistance exceeds the trip resistance.  A 
resistor-fault hold-off circuit prevents nuisance trips in 
alarm-only systems. 
  For additional information on neutral-grounding-resistor 
monitoring, see “Monitoring Neutral-Grounding Resistors” 
at www.startco.ca. 
 

2.  O

PERATION

 

2.1  S

ETTINGS

 

2.1.1  GF T

RIP

 T

IME

 

  Ground-fault trip time is adjustable from 0.1 to 2.0 
seconds.  Time-coordinated ground-fault protection requires 
this setting to be longer than the trip times of downstream 
ground-fault devices. 
  For the extended trip-time option, trip time is adjustable 
from 0.1 to 5.0 seconds. 

 
2.1.2  GF

 

  The ground-fault-circuit trip level is 0.5, 2.0, or 4.0 A 
when current is sensed with a CT200 current transformer.  
Since the ground-fault-circuit trip level should not be greater 
than 20% of the grounding resistor let-through current, these 
levels are appropriate for use with 5-, 15-, or 25-A 
grounding resistors.  See Table 1.  For other applications, the 
trip level of the ground-fault circuit is 0.25, 1.0, or 2.0% of 
the primary rating of the 5-A-secondary current transformer. 

 

Содержание SE-325

Страница 1: ...s RESI STOR FAULT RES TRIP LEVEL VAC CT1 CT2 A B RI GI SW L1 R L2 G STARTCO E N G I N E E R I N G L T D NGR MONITOR SE 325 MODE RES GF 20 400 200 0 1 2 0 1 0 4 0 A 2 0 A 0 5 A SH UV 20K Copyright 200...

Страница 2: ...This page intentionally left blank...

Страница 3: ...ty 14 7 Test Procedures 15 7 1 Ground Fault Performance Test 15 7 2 Resistor Fault Tests 16 7 2 1 Open Test 16 7 2 2 Voltage Test 16 7 3 Sensing Resistor Test 16 LIST OF FIGURES FIGURE PAGE 1 Typical...

Страница 4: ...Startco Engineering Ltd Page ii SE 325 Neutral Grounding Resistor Monitor Rev 0 Pub SE 325 M May 6 2008 This page intentionally left blank...

Страница 5: ...otection inoperative Transformer inrush current up to twelve times rated current can cause a ground fault voltage larger than expected A parallel transformer winding makes it difficult to monitor NGR...

Страница 6: ...lue of the ground fault circuit Typical values for 5 15 and 25 A tripping systems are shown in Table 1 For others systems refer to the NGR Monitor Set Point Assistant at www startco ca 2 2 INDICATION...

Страница 7: ...GROUND FAULT INDICATOR RESET SWITCH REMOTE INDICATION AND RESET RED RED F1 RESET POWER GROUND FAULT GF TRIP TIME s RESI STOR FAULT RES TRIP LEVEL VAC CT1 CT2 A B RI GI SW L1 R L2 G STARTCO E N G I N...

Страница 8: ...AL BLOCK COVER REMOVED MINIMUM CLEARANCE FOR FUSE REMOVAL 109 0 4 29 3 50 5 50 5 90 88 9 139 7 150 0 4 8 0 19 DIA 100 0 3 93 3 06 77 8 F1 RESET POWER GROUND FAULT GF TRIP TIME s RESI STOR FAULT RES TR...

Страница 9: ...nection to the SE 325 is not polarity sensitive Ground one side of the CT secondary For electrically noisy environments or lead lengths in excess of 10 m 30 ft use shielded twisted pair cable D A E B...

Страница 10: ...resistor connection is not a neutral conductor as defined in Canadian Electrical Code Section 10 1108 and National Electrical Code Section 250 36 B It is not required to be 8 AWG or larger Since curre...

Страница 11: ...ON MAY BE REMOVED FOR DIELECTRIC STRENGTH TESTING ENSURE THAT THE JUMPER IS INSTALLED AFTER TESTING ON REV 0 1 UNITS SCREW IS NOT PRESENT AND BASE IS ELECTRICALLY CONNECTED TO TERMINAL G 316 0 G R 188...

Страница 12: ...0 0 90 0 5 67 8 46 3 53 11 00 3 94 3 53 FRONT MOUNTING DETAIL SIDE NOTES TOP 444 0 17 50 14 37 1 56 1 56 365 0 39 5 39 5 MINIMUM DISTANCE TO ADJACENT OBJECTS NOTE 3 1 DIMENSIONS IN MILLIMETRES INCHES...

Страница 13: ...ENTRY NOTE 3 MINIMUM DISTANCE TO ADJACENT OBJECTS 320 12 6 FRONT SIDE N STARTCO E N G I N E E R I N G L T D MADE IN SASKATOON CANADA VOLTAGE AT TERMINAL N RISES TO LINE TO NEUTRAL VOLTAGE WHEN A GROUN...

Страница 14: ...IGHTS 36 6 1 44 17 3 0 68 29 9 1 17 43 5 1 71 PUSH BUTTON 36 6 1 44 14 9 0 59 29 9 1 17 43 5 1 71 FIGURE 8 RK 302 Remote Indication and Reset NOTES 1 DIMENSIONS IN MILLIMETRES INCHES 2 NEMA 1 FRONT VI...

Страница 15: ...2 5 I 3 0 0 1 1 8 25 0 0 98 CI RI GI OUTLINE NOTES 1 DIMENSIONS IN MILLIMETRES INCHES 2 NEMA 1 FIGURE 10 RK 325I Remote Indication Assembly 60 2 31 0 47 5 21 0 2 37 1 22 1 87 0 83 R S 1 R S 2 C G I G...

Страница 16: ...he RK 302 RK 325 and RK 325I See Figs 1 and 11 Contact K1 closes when the Ground Fault LED is on and contact K2 closes when the Resistor Fault LED is on 3 7 GROUND FAULT TESTING Use CT primary current...

Страница 17: ...004 Operating Mode UV Fail Safe or SH Non Fail Safe Remote Indication 12 Vdc GI RI Current Sink 560 Internal Optional RK 13 Module Contact Ratings 100 mA 120 Vac Contact Configuration N O Form A Reset...

Страница 18: ...ation and Reset Assembly RK 325I Indication Assembly RK 13 Relay Interface Module 6 WARRANTY The SE 325 Neutral Grounding Resistor Monitor is warranted to be free from defects in material and workmans...

Страница 19: ...bridges can be used to determine the existence of alternate ground paths d Verify proper reaction of the circuit interrupting device in response to a simulated or controlled ground fault current To si...

Страница 20: ...LED should be off 7 2 2 VOLTAGE TEST Test Equipment 0 to 120 Vac voltage source and multimeter NOTE Applying the test voltage to the R and G terminals will damage the SE 325 and the ER sensing resist...

Отзывы: