SE-135 Ground-Fault Ground-Check Monitor

 

Rev. 3-D-090816 

 
 

 

8.5  G

ROUND-

F

AULT 

P

ERFORMANCE 

T

EST 

   

To  meet  the  requirements  of  the  National  Electrical 

Code  (NEC),  as  applicable,  the  overall  ground-fault 
protection  system  requires  a  performance  test  when  first 
installed.  A written record of the performance test is to be 
retained by those in charge of the electrical installation in 
order  to  make  it  available  to  the  authority  having 
jurisdiction.  A test-record form is provided for recording 
the date and the final results of the performance tests. 
The  following  ground-fault  system  tests  are  to  be 
conducted by qualified personnel: 
a)  Evaluate the interconnected system in accordance with 

the  overall  equipment  manufacturer’s  detailed 
instructions. 

b)  Verify  proper  location  of  the  ground-fault  current 

sensor.    Ensure  the  cables  pass  through  the  ground-
fault-current-sensor window.  This check can be done 
visually  with  knowledge  of  the  circuit.    The 
connection of the current-sensor secondary to the SE-
135 is not polarity sensitive. 

c)  Verify  that  the  system  is  correctly  grounded  and  that 

alternate  ground  paths  do  not  exist  that  bypass  the 
current  sensor.    High-voltage  testers  and  resistance 
bridges  can  be  used  to  determine  the  existence  of 
alternate ground paths. 

d)  Verify  proper  reaction  of  the  circuit-interrupting 

device  in  response  to  a  simulated  or  controlled 
ground-fault  current.    To  simulate  ground-fault 
current,  use  CT-primary  current  injection.  Fig.  14 
shows  a  test  circuit  using  Littelfuse  Startco  Ground-
Fault-Relay  Test  Units.    The  SE-400  has  a 
programmable output of 0.5 to 9.9 A for a duration of 
0.1 to 9.9 seconds.  Set the test current to 120% of GF 
TRIP LEVEL.  The SE-100T provides a test current of 
0.65  or  2.75  A  for  testing  0.5-  and  2.0-A  trip  levels.  
Inject  the  test  current  through  the  current-sensor 
window  for  at  least  2.5  seconds.    Verify  that  the 
circuit  under  test  has  reacted  properly.    Correct  any 
problems  and  re-test  until  the  proper  reaction  is 
verified.   

e)  Record  the  date  and  the  results  of  the  test  on  the 

attached test-record form.

   

TABLE 3.  G

ROUND

-F

AULT

-T

EST

 R

ECORD

 

D

ATE

 

T

EST

 R

ESULTS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Retain this record for the authority having jurisdiction. 
 

Содержание SE-135

Страница 1: ...SE 135 MANUAL GROUND FAULT GROUND CHECK MONITOR REVISION 3 D 090816 Copyright 2016 by Littelfuse Startco All rights reserved Document Number PM 1315 EN Printed in Canada...

Страница 2: ...Page i SE 135 Ground Fault Ground Check Monitor Rev 3 D 090816 This page intentionally left blank...

Страница 3: ...20 Appendix A SE 135 Revision History 23 LIST OF FIGURES FIGURE PAGE 1 SE 135 Typical Application 4 2 SE 135 Outline and Panel Mounting Details 5 3 SE 134 SMA Surface Mount Adapter and SE 135 Surface...

Страница 4: ...Page iii SE 135 Ground Fault Ground Check Monitor Rev 3 D 090816 This page intentionally left blank...

Страница 5: ...y passive characteristic that will satisfy the ground check circuit s multi level drive allow induced currents to circulate in the ground check loop survive a phase to ground check fault and clamp the...

Страница 6: ...e must be taken to ensure safe and correct operation during power up and power down Connect terminals 12 and 13 for non fail safe trip relay operation with shunt trip devices In this mode the normally...

Страница 7: ...packaged with both panel and surface mounting hardware Outline and panel cutout dimensions for the SE 135 are shown in Fig 2 To panel mount the SE 135 insert it through the panel cutout and secure it...

Страница 8: ...also eliminate inter machine arcing and prevent stray ac and dc currents from flowing in the monitored ground wire See Figs 10 and 11 See Technical Note GC 10 Parallel Path Isolator at www littelfuse...

Страница 9: ...Page 5 SE 135 Ground Fault Ground Check Monitor Rev 3 D 090816 FIGURE 2 SE 135 Outline and Panel Mounting Details...

Страница 10: ...Page 6 SE 135 Ground Fault Ground Check Monitor Rev 3 D 090816 FIGURE 3 SE 134 SMA Surface Mount Adapter and SE 135 Surface Mounting Details...

Страница 11: ...Page 7 SE 135 Ground Fault Ground Check Monitor Rev 3 D 090816 FIGURE 4 SE IP65CVR G Weatherproof Cover Outline...

Страница 12: ...Page 8 SE 135 Ground Fault Ground Check Monitor Rev 3 D 090816 FIGURE 5 SE IP65CVR G Weatherproof Cover Installation...

Страница 13: ...Page 9 SE 135 Ground Fault Ground Check Monitor Rev 3 D 090816 FIGURE 6 SE CS10 and SE CS40 Current Sensors...

Страница 14: ...Page 10 SE 135 Ground Fault Ground Check Monitor Rev 3 D 090816 FIGURE 7 SE TA12A and SE TA12A WL Termination Assemblies...

Страница 15: ...Page 11 SE 135 Ground Fault Ground Check Monitor Rev 3 D 090816 FIGURE 8 SE TA12ASF WL Small Format Wire Lead Termination Assembly FIGURE 9 RK 132 Remote Indication and Reset Kit...

Страница 16: ...Page 12 SE 135 Ground Fault Ground Check Monitor Rev 3 D 090816 FIGURE 10 PPI 600V Parallel Path Isolator...

Страница 17: ...Page 13 SE 135 Ground Fault Ground Check Monitor Rev 3 D 090816 FIGURE 11 PPI 600V Typical Installation...

Страница 18: ...Page 14 SE 135 Ground Fault Ground Check Monitor Rev 3 D 090816 FIGURE 12 SE 135 with Ferrites Installed FIGURE 13 Current Sensor Shield Connection...

Страница 19: ...3 kV 60 Hz 1 s Test Front Panel Button and Remote N O Contact Fuse Rating F1 1 5 A 500 Vac Time Delay Fuse Part Number FNQ 1 Buss Fusetron Trip Mode Latching or Non Latching Trip Relay CSA UL Contact...

Страница 20: ...Hz 30 A m and 300 A m Power Frequency IEC 60255 22 7 Zone A differential mode 150 Vrms Zone A common mode 300 Vrms 1 MHz Burst IEC 61000 4 18 1 kV differential mode line to line 2 5 kV common mode Ce...

Страница 21: ...57 x 1 63 Shipping Weight 300 g 0 7 lb SE TA12A WL Characteristic 12 V Zener Temperature Compensated Circuit Type High Current Shunt Regulator Reverse Voltage 12 0 03 Vdc 100 mA Forward Voltage 0 5 0...

Страница 22: ...sories RK 132 Remote Indication and Reset includes two 24 120 V pilot lights a reset push button and legend plates SE IP65CVR G Hinged transparent cover IP65 SE 134 SMA Surface Mount Adapter included...

Страница 23: ...be off and both the GROUND CHECK TRIP and the OPEN LED s will be on Reconnect the ground check loop The monitor will reset Short the ground check loop by connecting G to GC The monitor will trip The...

Страница 24: ...ndary to the SE 135 is not polarity sensitive c Verify that the system is correctly grounded and that alternate ground paths do not exist that bypass the current sensor High voltage testers and resist...

Страница 25: ...Page 21 SE 135 Ground Fault Ground Check Monitor Rev 3 D 090816 FIGURE 14 Trip Relay Maximum Switching Capacity FIGURE 15 Remote Indication Relays GC and GF Maximum Switching Capacity...

Страница 26: ...Page 22 SE 135 Ground Fault Ground Check Monitor Rev 3 D 090816 FIGURE 16 Ground Fault Test Circuit FIGURE 17 Termination Assembly Test Circuits...

Страница 27: ...igs 14 and 15 RCM certification added SECTION 6 RCM certification added REVISION 3 C 100314 SECTION 4 Figs 7 8 and 11 updated REVISION 3 B 111213 SECTION 2 Maximum trailing cable length added SECTION...

Страница 28: ...Page 24 SE 135 Ground Fault Ground Check Monitor Rev 3 D 090816 This page intentionally left blank...

Страница 29: ...Mouser Electronics Authorized Distributor Click to View Pricing Inventory Delivery Lifecycle Information Littelfuse SE 134 SMA...

Отзывы: