INSTALLATION INSTRUCTIONS
OPERATION
1. Apply AC power to the unit. The LED indicator will be GREEN.
2. After the battery has been left to charge for 2 hours, test the unit using the magnetic test switch. The LED indicator turns OFF, the LED board stays
ON and the lampheads should turn ON at this time.
3. When the magnet is removed, the LED indicator turns back to GREEN, the LED board stays ON and the lampheads should turn OFF at this time.
BATTERY
WET LOCATION COMBO PCBA
TRANSFORMER
WHITE COMM
BLACK 120VAC
RED 277VAC
LED INDICATOR
TEST SWITCH
LAMP HEAD
YELLOW
BLUE
YELLOW
BLUE
BATTERY CONNECTOR
LAMP HEAD
YELLOW
BLUE
YELLOW
BLUE
HEATING PAD
CONNECTOR
WET LOCATION COMBO PCBA
TRANSFORMER
BLACK 120VAC
WHITE COMM
RED 277VAC
CHOOSE INPUT
VOLTAGE
LED INDICATOR
TEST SWITCH
BATTERY
ASSEMBLY
BATTERY CONNECTOR
Standard
SD Option (Self Diagnostics)
Wiring Diagrams
CW Option (Cold Weather)
CW SD Options (Cold Weather,
Self Diagnostics)
(MAGNETIC)
(MAGNETIC)
Part No.
EMCSA00916, REV. A
2018.10.15
SAVE THESE INSTRUCTIONS
and deliver to owner after installation
One Lithonia Way, Conyers GA 30012
Phone: 800-334-8694
www.lithonia.com
PAGE:
3
of
3
LED STATUS INDICATOR KEY and TROUBLESHOOTING:
Visual Status Indica
�
on
Troubleshoo
�
ng/Ac
�
ons to Take
RED
GREEN
UNLIT
1.
Ba
�
ery connec
�
on is not made.
2.
Ba
�
ery has been diagnosed as dead or defec
�
ve a
�
er 24
hours of con
�
nuous charging with AC power supplied.
Ba
�
ery is connected, AC power has been supplied and
fi
xture is in
charging state.
AC power has not been supplied.
1.
Make connec
�
on; or if ba
�
ery is connected,
disconnect
ba
tt
ery for eight seconds and then reconnect.
2.
Replace the ba
tt
ery.
This is the normal state. No ac
�
on required.
Supply AC power.
MAINTENANCE
Caution: Always turn off AC power to the equipment before servicing. Servicing should be performed only by a quali
fi
ed service technician. Use only
MANUFACTURER supplied replacement parts.
BATTERY: The battery supplied requires no maintenance. However, it should be tested periodically and replaced when it no longer operates the
connected sign for the duration of a 30-second or 90-minute test.
TESTING:
National Electric Code (NEC) and NFPA 101
current
Life Safety code requirements require that routine tests need to be performed
as listed below:
Once every month, the unit needs to be tested for duration of 30 seconds. Push in and hold the test switch to
perform this test. Once every 12 months, a full 90 minute (per UL requirements) test needs to be performed on the unit. Disconnect
power to the unit and leave it in the emergency mode. The lamps should stay ON for at least 90 minutes. Written records of the
testing are to be kept for examination by the authority having jurisdiction.