Lithonia Lighting WLTC Series Скачать руководство пользователя страница 3

INSTALLATION INSTRUCTIONS

OPERATION

1. Apply AC power to the unit. The LED indicator will be GREEN.
2. After the battery has been left to charge for 2 hours, test the unit using the magnetic test switch. The LED indicator turns OFF, the LED board stays

ON and the lampheads should turn ON at this time.

3. When the magnet is removed, the LED indicator turns back to GREEN, the LED board stays ON and the lampheads should turn OFF at this time.

BATTERY

WET LOCATION COMBO PCBA

TRANSFORMER

WHITE COMM

BLACK 120VAC

RED 277VAC

LED INDICATOR

TEST SWITCH

LAMP HEAD

YELLOW
BLUE

YELLOW
BLUE

BATTERY CONNECTOR

LAMP HEAD

YELLOW
BLUE
YELLOW
BLUE

HEATING PAD 

CONNECTOR

WET LOCATION COMBO PCBA

TRANSFORMER

BLACK 120VAC

WHITE COMM

RED 277VAC

CHOOSE INPUT 

VOLTAGE

LED INDICATOR

TEST SWITCH

BATTERY

ASSEMBLY

BATTERY CONNECTOR

Standard

SD Option (Self Diagnostics)

Wiring Diagrams

CW Option (Cold Weather)

CW SD Options (Cold Weather, 

Self Diagnostics)

(MAGNETIC)

(MAGNETIC)

Part No. 

EMCSA00916, REV. A

 

2018.10.15

SAVE THESE INSTRUCTIONS

and deliver to owner after installation

One Lithonia Way, Conyers GA 30012

Phone: 800-334-8694

www.lithonia.com

PAGE: 

3

 of 

3

LED STATUS INDICATOR KEY and TROUBLESHOOTING:

Visual Status  Indica

on 

Troubleshoo

ng/Ac

ons  to Take 

RED 

GREEN 

UNLIT 

1.

Ba

ery connec

on is not made. 

2.

Ba

ery has been diagnosed as dead or defec

ve a

er 24 

hours of con

nuous charging with AC power supplied.

Ba

ery is connected, AC power has been supplied and 

xture is in 

charging state. 

AC power has not been supplied. 

1.

Make connec

on; or if ba

ery is connected,

 

disconnect

ba

tt

ery for eight seconds and then reconnect.

2.

Replace the ba

tt

ery.

This is the normal state. No ac

on required. 

Supply AC power. 

MAINTENANCE

Caution: Always turn off AC power to the equipment before servicing. Servicing should be performed only by a quali

fi

 ed service technician. Use only 

MANUFACTURER supplied replacement parts.
BATTERY: The battery supplied requires no maintenance. However, it should be tested periodically and replaced when it no longer operates the 
connected sign for the duration of a 30-second or 90-minute test.

TESTING:

National Electric Code (NEC) and NFPA 101

 current 

Life Safety code requirements require that routine tests need to be performed 

as listed below:

 

Once every month, the unit needs to be tested for duration of 30 seconds. Push in and hold the test switch to 

perform this test. Once every 12 months, a full 90 minute (per UL requirements) test needs to be performed on the unit. Disconnect 
power to the unit and leave it in the emergency mode. The lamps should stay ON for at least 90 minutes. Written records of the 
testing are to be kept for examination by the authority having jurisdiction.