LEM Series Compatibility and Suitability of Use Guidelines

Addendum (Rev. A)

This product is suitable for field installation with suitable LED loads including LED luminaires, DC voltage driven LED 

replacements for fluorescent lamps and others. There are 4 checks to determine if your luminaire is eligible for field 

installation. 

1.  Ensure the LED load’s rated power is greater than or equal to the power output of this emergency LED driver. 

This is to ensure that this emergency product will not produce more power than the LED load can handle, thus 

ensuring that the LED load will not be damaged when the system is in the emergency mode. 

2.  Verify that the forward voltage of the luminaire’s LED array is within the limits of this emergency LED driver. The 

forward voltage of the LED array is commonly designated as Vf and should be found on the luminaire markings, 

in the luminaire specifications, or imprinted directly on the LED arrays. If multiple LED arrays are to be driven, 

verify that the total forward voltage is within the limits of this product. Using a voltage meter, it may be possible 

to directly measure the voltage across the LED arrays when operating from the AC driver.

3. 

UL Classified Emergency products can be paired with LED luminaires or retrofit kits if found in the Design Lights 

Consortium database. Go to the Design Lights Consortium website (http://www.designlights.org) and search for 

your LED system by model name or model number. If found in the database, these products are preapproved 

by UL to be installed together in the field or at a luminaire manufacturer, provided steps are taken to ensure 

there will be sufficient light output in the end application. 

4.  You can 

estimate

 the egress lighting illumination levels by doing the following:  

a. Find the efficacy of the LED load, which will be found in the Design Lights Consortium database. This number  

    will be given in lumens per watt (lm/w).  

b. Determine the approximate power output of the emergency LED driver. See TABLE A on page 2.

 

c. Approximate lumens can be calculated by multiplying the output power of the emergency LED driver by the  

   efficacy of the LED load. This number is only an approximation however it will provide a good estimate for  

   beginning the lighting design of the system. 

5.  Determining Adequacy of Means-of-Egress Lighting Levels
6.  While this model has been found compliant with the requirements of UL standard 924, it is ultimately the re-

sponsibility of the Designer/Specifier to assure the as-installed system delivers code-compliant path of egress 

illumination in accordance with Federal, State or local municipal requirements.

68LEM-000 

REV 2000

Содержание LEM04

Страница 1: ...mpering by unauthorized personnel 9 The LEM emergency driver will supply 20 50VDC output at the individual rated specification for 90 minutes 10 This product is suitable for use in damp locations where the ambient temperature is 0ºC minimum 50ºC maximum Product is also suitable for installation in sealed and gasketed fixtures Product is not suitable for heated air outlets and wet or hazardous loca...

Страница 2: ... For LEM04 B and LEM08 B Mount the LEM Emergency Driver in the driver lamp compartment or enclosed wireway so the wire leads are not exposed at least 1 2 away from the normal driver Refer to Illustrations 1 and 2 When battery packs are remote mounted consult Customer Service for the maximum allowable distance between the battery pack and the load Illustration 1 NOTE Position the Test Switch Indica...

Страница 3: ...y charging mode The Test Switch Charge Indicator will be lit providing a visual indication that the bat tery is being charged Emergency Mode The A C power fails The LEM Emergency Driver senses the A C power failure and automati cally switches to the Emergency Mode The designated LED array will illuminate for a minimum of 90 minutes When the A C power is restored the LEM Emergency Driver switches t...

Страница 4: ...ts can be paired with LED luminaires or retrofit kits if found in the Design Lights Consortium database Go to the Design Lights Consortium website http www designlights org and search for your LED system by model name or model number If found in the database these products are preapproved by UL to be installed together in the field or at a luminaire manufacturer provided steps are taken to ensure ...

Отзывы: