background image

RJ5210155

01/06

Tools required: 3/4" socket w/extension, Philips-head screw driver, 5/16" nut driver (bridge
mount), slotted screw driver

INSTALLATION

Mounting the fixture (Arm mount and Post-Top Instructions):

1. Remove reflector by loosening the 2 captive door frame screws and slowly open the

fixture.  The reflector can be removed by gently prying and pulling the reflector loose.
Once loose, disengage the socket quick disconnect and remove from the fixture housing.
This will give you access for mounting and wiring the fixture.

2.  For arm mount fixtures, remove the top cap from pole, if in place. Insert the mounting plate

inside pole or tenon adaptor, aligning the three (3) mounting holes in plate with the three
(3) mounting holes provided on the pole. Slide the two threaded rods through the top and
bottom mounting holes in the pole and start to thread the rods into the matching holes in
the mounting plate (three turns are sufficient). Place one of the gaskets over the threaded
rods and against the pole.

3. To mount the arm, slide arm over threaded rod using the bolt guides inside the arm. Place

remaining gasket over the threaded rods and against the mounting arm.

4. Position the housing at the end of the arm

and feed fixture wires through arm, pole backing
plate, and out pole top.  Align the holes with
the threaded rods and insert the threaded rods
into the fixture. Install split lockwashers
and hex nuts (furnished) on the ends of the
threaded rods that are inside the fixture and
tighten securely. Make sure fixture is mounted
straight and square with pole before
raising pole.

5.  Make wire connections observing voltage

and polarity. Connect  green ground wire
from the fixture to field ground wire.

Pole Top Mount

1. The KVF mounts to a 4, 4-1/2, 5, or 6" diameter pole

 top determined by the option ordered).

2. Remove the top plate of the wiring compartment.

Make wire connections, replace the top plate.

3. Secure the fixture by slipping into the pole top and

tightening (1) internal fitter device.

Lamp Installation

1. Re-install reflector by plugging the lamp lead disconnect back in, line up the reflector to its

appropriate direction and gently push or pop back into place being sure to align the four pop
balls with their receptacles.  Check to insure reflector is seated properly and secure before
installing lamp.

2. Prior to installing the lamp (not included) in the fixture, verify that the lamp source and wattage

corresponds with the fixture label. Screw the lamp securely into the socket, back it out one
or two turns, and tighten it securely again. This procedure properly seats the lamp in the
socket.  Reconnect secondary disconnect plug and secure door assembly.

WTB (Terminal Block option)

Tools Required:  Slotted screwdrive    (WTB will accept 16 AWG - 4 AWG)

1. Insert correct ballast leads to one side of WTB.  Secure by tightening the appropiate screws.

Place the corresponding incoming line voltage leads, being sure to observe proper polarity and
voltage.  Secure by tightening screws.

2. Cap off any unused tap ballast taps with wire nuts and secure away from any exposure to the

WTB.  (See below for TB option)

Prior to Installation

Read  carefully before installing light fixtures. If you do not understand these instructions, please
contact your local Lithonia Lighting distributor before installing.

KVF

 KVF Series

 Area Lighting / Post-Top Mounting

SAVE THESE INSTRUCTIONS

INSTALLATION

INSTRUCTIONS

• This fixture must be wired in accordance with the National

Electrical Code and applicable local codes and ordinances.

• Proper grounding is required.

• Use approved connectors for all electrical connections.

• Be certain the green lead from the fixture is secured to

ground.

• ALL work should be performed by a qualified electrician.

IMPORTANT SAFETY

INSTRUCTIONS

(For Your Protection, Read Carefully)

WARNING 

Verify the proper fixture voltage lead has been

selected to match the supply voltage before energizing.
Improper wiring may result in ballast failure and void all
warranties. NEVER disconnect any component while power
supply is engaged.

Upon receipt of fixture and accessories (packaged separately)
thoroughly inspect for any freight damage which should be
brought to the attention of the delivery carrier. Compare the
catalog description listed on the packing slip with the fixture
label on the outside of the ballast box  to be sure you have
received the correct merchandise.

Internal

Fitter

Arm Mount (SP09)

Отзывы: