Chapter 7: Trouble Shooting Steps
Positive Busbar Negative Busbar
3) Communication connecting line between system and inverter (Optional)
6.2.
Installation Location
Make sure that the installation location meets the following conditions:
1.
The location drains properly, there are no puddles.
2.
The floor is flat and level, and capable of supporting the weight of the system. (See
Section 2.3)
3.
There are no flammable or explosive materials nearby.
4.
The ambient temperature is between 0°C and 50°C.
5.
The temperature and humidity are maintained at a constant level.
6.
There is minimal dust and dirt in the area.
7.
Any heat source is at least 2 meters away.
8.
The distance from the exhaust air of the inverter is at least .5 meters.
9.
The installation must be protected from the environment.
10.
Do not cover or wrap the battery case or cabinet.
11.
Do not place where there are children or pets.
12.
Do not install in direct sunlight.
There is no ventilation required for the ESS, but due to the heat given off from the battery and
inverters take note when installation in a small space or closed off area. Avoid areas of high
salinity, humidity, or temperature.
If the ambient temperature is outside the operating range the battery pack will stop operating to
protect itself. The optimal temperature range for the battery pack to operate is 0°C to 55°C.
Frequent exposure, to harsh temperatures may reduce the performance and life of the battery
pack.
6.3.
Installation
A. Stack the entire system. The modules are heavy and require at least two people to lift.