4.2.1 Main Circuit Terminal
R/L 1
S/L 2
T/L 3
U/T 1
V/T 2
W/T 3
E
-
+
IM
Braking Unit (option)
MCCB MC
Fast Acting Fuse
R
S
T
Table 4.2.1 Main Circuit Terminals
Terminal Name
Terminal Description
R/L1, S/L2, T/L3
Power input terminal
U/T1, V/T2, W/T3
Power output terminal
+, -
Braking unit terminal. Select option as per the specifications.
E
Ground terminal
4.2.2 Main Circuit Wiring
4.2.2.1 Power Input Terminal
Install a molded case circuit breaker (MCCB) between three phase AC input power and
main circuit terminals R/L1, S/L2 and T/L3. A magnetic contactor (MC) in series
connection is also suggested so as to shut off the power by drive protection functions.
Install a R-C varistor on both ends of the MC.
Ensure main circuit terminal screws are tightened to avoid vibration loosening the screws
which could cause electric sparks.
4.2.2.2 Power Output Terminal
When connecting a noise filter at AC drive output terminals U/T1, V/T2 and W/T3, always
use an inductive L-filter. Do not install any power capacitor, L-C or R-C filter.
Connect AC drive output terminals U/T1, V/T2 and W/T3 to motor input terminals U, V