LinkAYL LK-CP711-30A Скачать руководство пользователя страница 2

Terminals

   

 

Symbol

 

Description

 

Symbol

 

Description

 

V+

 

DC24V+

 

FSO

 

Fire

 

feedback

 

COM

 

V

‐ 

DC24V

‐ 

FOO

 

Fire

 

feedback

 

NO

 

M+

 

Motor

 

DC24V+

 

FOC

 

Fire

 

feedback

 

NC

 

M

‐ 

Motor

 

DC24V

‐ 

24V

 

Output

 

DC24V+

 

MU

 

Manual

 

switch

 

up

 

FSI

 

Fire

 

signal

 

input

 

MS

 

Manual

 

switch

 

stop

 

COM

 

COM

 

signal

 

MD

 

Manual

 

switch

 

down

 

S+

 

Slave

 

control

 

up

 

MG

 

Manual

 

switch

 

GND

 

S

‐ 

Slave

 

control

 

down

 

T

 

T

 

sensor

 

signal

 

12V

 

Output

 

DC12V+

 

H

 

H

 

sensor

 

signal

 

WRD

 

Rain

 

sensor

 

down

 

 

 

Control

 

Mode

 

 

Controler

 

has

 

inching

 

mode

 

and

 

continued

run

 

mode

 

which

 

is

 

default

 

 

In

 

the

 

continued

run

 

mode,

 

press

 

the

 

up

 

/

 

down

 

key

 

less

 

than

 

1.5

 

seconds,

 

the

 

motor

 

will

 

run

 

continuously,

 

press

 

the

 

up

 

/

 

down

 

key

 

more

 

than

 

1.5

 

seconds,

 

the

 

motor

 

will

 

stop

 

after

 

running

 

a

 

very

 

short

 

moment

 

 

In

 

the

 

inching

 

mode,

 

press

 

the

 

up

 

/

 

down

 

key

 

less

 

than

 

1.5

 

seconds,

 

the

 

motor

 

will

 

stop

 

after

 

running

 

a

 

very

 

short

 

moment,

 

press

 

the

 

up

 

/

 

down

 

key

 

more

 

than

 

1.5

 

seconds,

 

the

 

motor

 

will

 

run

 

continuously

 

 

Only

 

the

 

manual

 

buttons

 

on

 

the

 

panel,

 

manual

 

switch,

 

remote

 

control

 

and

 

cascade

 

signal

 

have

 

inching

 

mode

 

 

Keep

 

pressing

 

both

 

of

 

UP

 

and

 

STOP

 

button

 

on

 

the

 

controler

 

for

 

5

 

seconds,

 

LEDs

 

flash

 

3

 

times

 

and

 

turn

 

off

 

it’s

 

inching

 

mode

 

for

 

the

 

controler,

 

repeat

 

the

 

operation

 

the

 

controler

 

turns

 

to

 

continued

run

 

mode

 

 

Manual

 

control

 

 

After

 

power

 

on

 

all

 

the

 

LEDs

 

light

 

for

 

1

 

second

 

and

 

turn

 

off,

 

the

 

power

 

indicator

 

LED

 

normally

 

on

   

 

Press

 

reset

 

button,

 

all

 

the

 

LEDs

 

light

 

for

 

1

 

second

 

and

 

turn

 

off,

 

reset

 

successfully

 

 

L2

 

will

 

be

 

explosion

flashing

 

after

 

controler

 

receives

 

fire

 

signal

 

 

External

 

manual

 

switch

 

is

 

equivalent

 

to

 

controler

 

panel

 

switch

 

 

The

 

maximum

 

running

 

time

 

of

 

the

 

motor

 

is

 

5

 

minutes

   

 

The

 

motor

 

up

 

/

 

down

 

switching

 

time

 

is

 

500ms

 

 

Press

 

UP

 

button,

 

the

 

windows

 

open,

 

LED

 

turns

 

on,

 

turns

 

off

 

after

 

5

 

seconds

 

 

Press

 

DOWN

 

button,

 

the

 

windows

 

close,

 

LED

 

turns

 

on,

 

turns

 

off

 

after

 

5

 

seconds

 

 

Press

 

STOP

 

button,

 

,the

 

motors

 

stop,

 

LED

 

turns

 

on,

 

LED

 

turns

 

off

 

after

 

1

 

second

 

 

Remote

 

control

 

 

The

 

controler

 

encodes

 

by

 

433MHz

 

learning

 

code,

 

can

 

store

 

10

 

sets

 

of

 

codes

 

Matching

 

Code

 

 

Power

 

controler

 

on,

 

press

 

STOP

 

button

 

on

 

the

 

controler

 

for

 

5

 

seconds,

 

LED

 