Lindab WH45 Series Скачать руководство пользователя страница 5

5

/14

 

†

230 V AC magnet wiring

1.  230 V AC power supply

2.  Magnet

3.  Rectifier

 

†

24 V DC magnet wiring

1.  24 V DC power supply

2.  Magnet

 

†

WH45 - Motorized version

Belimo servomotor:

BFL24T, BFN24T, BF24T, BFL230T, BFN230T, BF230T.

Siemens servomotor:

GRA126, GNA126, GGA126.

Siemens servomotor:

GRA326, GNA326, GGA326.

Motorized fire dampers electical wiring

To connect the dampers to the power supply, proceed as follows:

•  Check that the voltage and electrical frequency are equivalent to 

those of the motor of the servomotor (check the motor's informa-

tion label);

•  Make the connections as shown in the below diagram.

1  Negative (DC) or neutral (AC)

2  Positive (DC) or phase (AC)

3 Phase

4 Neutral

S1  Common closed damper microswitch

S2  Normally closed, closed damper microswitch

S3  Normally opened, closed damper microswitch

S4  Common open damper microswitch

S5  Normally closed, open damper microswitch

S6  Normally opened, open damper microswitch

rev 20-10

5

We reserve the right to make changes without prior notice

Содержание WH45 Series

Страница 1: ...ww mp3 italia it 1MUBWH45EN rev 20 10 1MUBWH45EN WH45 WH45 l indab we simplify co nstruc tio n www lindab com Fire dampers are manufactured by MP3 Srl www mp3 italia it 1MUBWH45EN LIND rev 20 10 1MUBW...

Страница 2: ...cal light wall gypsum blocks wall Wall minimum thickness 70 mm Wall minimum density 995 kg m Plaster putty sealing ve i o W min 200 max 800 min 200 max 800 min 200 max 800 EI 120 S Installation within...

Страница 3: ...ade position open or closed Refer to Electrical connections paragraph for more details Closing by remote control With power supply input or interruption magnet WH45M version only Temperature calibrati...

Страница 4: ...sup plied to the motor Position indication microswitches The motorized versions are supplied with two microswitches to show the blade s position open or closed Refer to the section Electrical connect...

Страница 5: ...ollows Check that the voltage and electrical frequency are equivalent to those of the motor of the servomotor check the motor s informa tion label Make the connections as shown in the below diagram 1...

Страница 6: ...W Motor 230V AC WH45DPS WH45DSS Siemens GNA326 GRA326 Opening 4 5 W In stand by 3 5 W 24V AC DC motor WH45VGS Siemens GGA126 Opening 6 W In stand by 1 5 W 230V AC motor WH45DGS Siemens GGA326 Opening...

Страница 7: ...ance with national legislation For electrical and electronic parts also refer to EU Directive 2011 65 INSTALLATION The sizes shown are in mm It is recommended to perform a functional test before Insta...

Страница 8: ...echanism side 2 Mechanism opposite side 3 End cap with mesh L1 End cap length mechanism side L2 End cap length mechanism opposite side Fire damper nominal diameter Length of end cap with mesh dependin...

Страница 9: ...floor Installation a mm b mm c mm d mm Rigid wall EI 90 S Installation within vertical rigid wall Plasterboard and rock wool 100 kg m sealing 50 75 EI 120 S Installation within vertical rigid wall Mor...

Страница 10: ...pacing of 625 mm between each other vertical profile fixing with selfthreading screws or by clinching to the bottom horizontal profile and insertion in the top horizontal profile profiles fixed using...

Страница 11: ...ol lowing characteristics minimum thickness 100 or 150 mm according to the resistance class required minimum density 2200 kg m Installations within vertical rigid wall Refer to the section Constructio...

Страница 12: ...for further information Wall opening A opening must be provided in the wall as indicated in the table and in the drawing Damper positioning Position the damper in the opening so that the side of the...

Страница 13: ...l as indicated in the table and in the drawing Damper positioning Position the damper in the opening so that the side of the closing mechanism extends as indicated in the table and in the drawing Clos...