Regula Combi Installation 

Set program on Regula Combi

To enter the parameter menu and change program the 
following steps should be followed:
1.  Simultaneously hold the INCREASE and DECREASE 

buttons depressed for about 5 seconds

2. The Service indication will be displayed. 
3. Then press the INCREASE button twice.
4.  The display will now show the parameter number 0 

(which chooses program).

5.  Press the Occupancy button to select the desired pa-

rameter. 

6.  The parameter number will be replaced by the param-

eter value. 

7.  The value can be changed using the INCREASE and 

DECREASE buttons. 

8.  To retrieve the original value, i.e. the value before 

change, press the INCREASE and DECREASE but-
tons at the same time. The original value is shown on 
the display. 

9.  To acknowledge and store a set parameter value, 

press the Occupancy button again, the display then 
returns to showing the parameter number. 

After a certain time, about 1 minute, or when the IN-
CREASE and DECREASE buttons are pressed at the 
same time while in the menu, the display returns to the 
normal view. Exit is shown on the display after the last 
parameter. The parameter menu is exited by pressing the 
Occupancy button while in Exit. 

The maximum number of actuators that can be connect-
ed to the digital output (ON/OFF) is 10 for cooling and 
heating, respectively. When more than 4 on/off actuators 
for cooling or heating are connected, terminal blocks 
10 and 20 must be connected with a cable because the 
Regula Combi print card can not handle the output pow-
er for more than 4 on/off actuators.

Electrical connections

Regula Combi connection terminals overview

10

 G+ Supply voltage 24 V A

11

 G0- Supply voltage 0 V

12-14

 No function.

20

 GDO 24 V AC out common for DO. Internally connected to terminal 10, G+.

21

 G0- 0 V common for UO. Internally connected to terminal 11, G0-.

22

 UO3 Control output forcing (cooling). For a 0-10 V DC actuator, max 5 mA. The actuator’s 0-10 V control signal 

terminal is connected to terminal 22 and its supply terminals to terminals 20 and 21. Make sure that the reference 
pole G0- is connected to the correct terminal on the actuator. Alternatively for a 24 V AC thermal actuator, max 2.0 
A. The thermal actuator is connected between terminals 22 and 20, GDO.

23

 UO1 Control output heating. For a 0-10 V DC actuator, max 5 mA. The actuator’s 0-10 V control signal terminal 

is connected to terminal 23 and its supply terminals to terminals 20 and 21. Make sure that the reference pole G0 
is connected to the correct terminal on the actuator. Alternatively for a 24 V AC thermal actuator, max 2.0 A. The 
thermal actuator is connected between terminals 23 and 20, GDO.

24

 UO2 Control output cooling. For a 0-10 V DC actuator, max 5 mA. The actuator’s 0-10 V control signal terminal 

is connected to terminal 24 and its supply terminals to terminals 20 and 21. Make sure that the reference pole G0- 
is connected to the correct terminal on the actuator. Alternatively for a 24 V AC thermal actuator, max 2.0 A. The 
thermal actuator is connected between terminals 24 and 20, GDO.

30

 AI1 For temperature sensor, PT1000. Measuring range 0-50°C. The sensor is connected between terminals 30 

and 41, AGnd.

31

 AI2 For a 0-10 V CO

2

 sensor. Alternatively for a 0-10 V Damper position.

32

 DI1 Presence sensor. A potential-free contact is connected between terminals 32 and 40, +C. Alternatively for a 

Window contact.

33

 DI2/CI Condensation detector. The sensor is connected between terminals 33 and 41, AGnd. Alternatively for a 

Change Over indicator, CO

2

 Relay sensor or CO

2

 Pulse sensor.

40

 +C 24 V DC out common for DI

41

 AGnd Analogue ground, reference for AI

42

 A RS485-communication 

43

 B RS485-communication B

Occupancy button

INCREASE button

DECREASE button

Display handling

Connecting actuators