![Lindab Professor XP F-45 Скачать руководство пользователя страница 5](http://html1.mh-extra.com/html/lindab/professor-xp-f-45/professor-xp-f-45_quick-installation-manual_1919270005.webp)
5
Quick installations guide
Professor XP
Lindab reserves the right to make changes without prior notice
2021-03-08
lindab | we simplify construction
Material data
Material data
Specific measures for the water circuit
Type
Professor XP
Copper pipes, quality
EN-12735-2 CU-DHP
Pressure class
PN10
Performance value
Function
Batery
type
CC
HH
Dry
weight
[kg/m]
Water content
cooling
[l/m]
Water content
heating
[l/m]
Water content
total
[l/m]
Maximal cooling and maximal heating
4-pipe
12
06
14.2
1.1
0.6
1.7
Maximal cooling and minimal heating
4-pipe
12
02
13.7
1.1
0.3
1.4
Maximal cooling or maximal heating
2-pipe
12
00
13.5
1.1
1.1
High cooling and maximal heating
4-pipe
08
06
13.7
0.8
0.6
1.4
High cooling and minimal heating
4-pipe
08
02
13.2
0.8
0.3
1.1
High cooling or high heating
2-pipe
08
00
13.0
0.8
0.8
Medium cooling and maximal heating
4-pipe
06
06
12.4
0.6
0.6
1.2
Medium cooling and minimal heating
4-pipe
06
02
11.9
0.6
0.3
0.9
Medium cooling or medium heating
2-pipe
06
00
11.6
0.6
0.6
Minimal cooling and minimal heating
4-pipe
04
02
11.8
0.4
0.3
0.7
Minimal cooling or minimal heating
2-pipe
04
00
11.5
0.4
0.4
Environmental Declarations
Please follow the links below
•
•
•
Pressure Class
The waterborne products in Lindab, active chilled beams
(battery products), passive chilled beams (battery and strips
products), facade units (battery) and radiant panels (strips
and panels) are produced according to pressure class PN10
according to EN 1333: 2006.
This means the maximal working pressure for the products
at a water temperature of 20°C must not exceed 10 bar.