Service & maintenance          Atrium Plana

Push-on valve

  

Notice!

 The connection pipes are internally soft-welded why it’s not allowed to solder 

the panel to the pipes.

1.4.2  Compression fitting

 

– Please ensure that all pipes and fittings are undamaged, as even small dents and 

scratches potentially pose a risk of leakage in the system. Always remember to do 
a pressure test after assembly of the pipe work.

 

– While mounting a compression fitting, the pipe will be exposed to a big amount 

of force, creating a risk of crushing the pipe. To ensure that the pipe won’t be 
crushed when mounting the compression fitting, a copper insert should be 
inserted into the pipe.

 

– Both flow and return pipe is covered by a plastic or rubber protection cover during 

transport, which must be removed before installation.

 

– After removing the protection cover, make sure that the pipe is intact and undam-

aged, especially at the pipe end. Crocked or in other ways imperfect pipe ends will 
result in leaks. Deburr the pipe on the inside and the outside, using a deburring 
tool before installation 

Содержание Atrium Plana 40

Страница 1: ...lindab we simplify construction Atrium Plana Service maintenance...

Страница 2: ...ustain dents scratches or bends during installation Always seek to lift the panel at multiple points Do not lift in pipes Do not lift in edges Each panel is equipped with protective film to avoid any...

Страница 3: ...e is covered by a plastic or rubber protection cover which should be removed before installation After removing the protection cover make sure that the pipe is intact and undamaged especially at the p...

Страница 4: ...ipe work While mounting a compression fitting the pipe will be exposed to a big amount of force creating a risk of crushing the pipe To ensure that the pipe won t be crushed when mounting the compress...

Страница 5: ...e connection pipes are internally soft welded why it s not allowed to solder the panel to the pipes 1 4 3 Flex hoses Our flexible hoses can be used with both compression and Tectite fitting We recom m...

Страница 6: ...ide and the outside using a deburring tool before installation Mount a push on fitting to the pipe Make sure to press the fitting all the way onto the pipe After mounting the push on fitting mount the...

Страница 7: ...ion above water connection Label location interior Under insulation above water connection On the label you ll find Order Order identification number Pos Order position Product Product configuration P...

Страница 8: ...ty EN12735 2 CU DHP EN12735 2 CU DHP Pressure class PN10 PN10 4 2 Environmental declaration Please visit www lindqst com Select Documentation Finder Select Atrium Plana Select Environmental declaratio...

Страница 9: ...ld up air in the system The water should be oxygen free to prevent corrosion The water system must be filled with potable water that complies with the EC directive 98 83 EC pH value of water must be b...

Страница 10: ...usohjeet sek tuotetuen yhteystiedot www lindab fi Oikeus muutoksiin pid tet n DE Hier finden Sie aktuelle Produktinformationen Mon tageanleitungen und Telefonnummer E Mail Adressen der Ansprechpartner...

Отзывы: