Fig. 33
Fig. 34
Fig. 35
Run mode
Unit proceeds in run (
r
) mode after power is terminated on unit and
then switched on again. All devices selected display.
Running system (pump run)
Run (
r
) time displays when controller is switched on. Time appears
from actual time set and counts down to zero. Green LED indicates
minutes (
Fig. 34
). Green LED next to
PUMP
flashes to indicate pump
is turning or pumping.
Running system (pump pause)
Controller goes into pause time when required run time is reached.
Pause (
P
) time counts down from original setup time to zero and
then resumes run time (
Fig. 35
). Green LED next to
PUMP
is steady
to indicate pump is there by not turning while in pause mode.
Fig. 32
23 tSt
(test mode) appears in display. Press
Δ
for pump to start
turning (
Fig. 32
). Correct pump from turning in wrong direction
by changing polarity of wiring. Check other sensors by energizing
them manually and observing if green LED illuminates. If LED
does not illuminate, a problem exists with wiring or setup
procedure.
24
If all is correct, turn off power supply to controller
NOTE
tSt
must appear on display before switching off power to unit.
System does not save changes if power to unit is turned off
during any part of programming.
tSt
must appear on display for
changes to be confirmed.