ANNOUNCEMENTS

 

ON

 

THE

 

REPEATER

 

PANEL 

3.1.1

 

THE REPEATER PANEL IS AT REST 

 

No alarm or fault indicator has been activated. All LEDs are off and the built-in buzzer is not 
activated. 

 

The LCD will display the standard screen (see “4. Display information). 

 

The MD2400 repeater panel is in rest as long as the MD2400 fire detection control panel is in 
the quiescent position. 

3.1.2

 

ANNOUNCEMENTS IN CASE OF A FAILURE 

 

The built-in buzzer is activated. 

 

The yellow LED “FAULT” lights up. 

 

The name of the group to which the detector belongs, together with the detector name and 
the message sequence number, appear on the LCD. The detector name is a description of a 
maximum of 28 characters related to the location of the fire detector. The sequence number 
indicates the chronology of the reported failure. 

 

Alarm  announcements  have  priority  over  fault  announcements.  If  one  or  more  alarms  are 
already on the LCD, an incoming fault message will initially be suppressed. With the help of the 
scroll buttons “

” and “

”, the information relating to the fault messages can still be displayed 

on the LCD. 

 

General failures, such as a siren error, a power failure,  a loop error and a printer  error are 
reported in the same way. 

3.1.3

 

ANNOUNCEMENTS IN CASE OF A FIRE ALARM 

 

The built-in buzzer is activated. 

 

The red LED “ALARM” lights up. 

 

The name of the group to which the detector belongs, together with the detector name and 
the message sequence number, appear on the LCD. 

 

The red LED “EVACUATION” lights up as soon as the set delay time has elapsed. 

 

If the Yellow LED “EVAC. DELAYED” lights up, the delay function is active. In this case, a specific 
relay  (usually  used  to  control  a  telephone  transmitter  to  report  the  fire  alarm  to  the  fire 
brigade)  is  only  activated  for  a  set  time  after  the  fire  alarm  has  been  triggered.  The  delay 
function is only activated during presence (permanent presence).  

 

If the delay function is deactivated (yellow LED “EVAC. DELAYED is switched off), then this relay 
is  activated  immediately  after  each  fire  alarm  (if  this  relay  is  connected  to  a  telephone 
transmitter, the fire brigade is called immediately). The delay function is deactivated for the 
duration of the absence
 (no permanent presence). 

 

 

Содержание MD2400

Страница 1: ...www limotec be HG2400E02C 1 USER MANUAL MD2400 repeater panel 01 07 2018 LIMOTEC bvba Bosstraat 21 B 8570 Vichte Tel 32 0 56 650 660 www limotec be ...

Страница 2: ...ANNOUNCEMENTS IN CASE OF A FAILURE 4 3 1 3 ANNOUNCEMENTS IN CASE OF A FIRE ALARM 4 3 2 CONTROLS ON THE REPEATER PANEL 5 3 2 1 KEY SWITCH OPERATION 5 3 2 2 GREEN CONTROL BUTTON SILENCE 5 3 2 3 GREEN CONTROL BUTTON TEST LED 5 3 2 4 ORANGE CONTROL BUTTON RESET 5 3 2 5 ORANGE CONTROL BUTTON EVAC DELAYED 5 3 2 6 KEY SWITCH EVACUATION 6 3 2 7 SCROLL BUTTONS AND 6 4 DISPLAY INFORMATION 7 ...

Страница 3: ...tandard with an LCD 4x40 characters a number of general visual indications LED for fire alarm and failure a number of control buttons Silence Test LED Reset Evacuation Delayed and scroll buttons a key switch for setting the 2 control levels and with a key switch for evacuation Communication between the MD2400 fire detection control panel and the MD2400 repeater panel is serially by means of an RS4...

Страница 4: ...the help of the scroll buttons and the information relating to the fault messages can still be displayed on the LCD General failures such as a siren error a power failure a loop error and a printer error are reported in the same way 3 1 3 ANNOUNCEMENTS IN CASE OF A FIRE ALARM The built in buzzer is activated The red LED ALARM lights up The name of the group to which the detector belongs together w...

Страница 5: ...he built in warning buzzer of the respective MD2400 repeater panel stops The warning buzzers of the other MD2400 operator consoles and repeater panels continue to be activated The relay contacts connected to the silent function do not switch back to the resting position Only the yellow LED Silence of the respective MD2400 repeater panel lights up This LED is switched off in case of a new message o...

Страница 6: ...em will immediately switch to evacuation the red LED Evacuation on the MD2400 operator consoles and repeater panels and the programmed outputs during evacuation will be activated immediately 3 2 7 SCROLL BUTTONS AND These control buttons are available at any time If several messages are present on the MD2400 fire detection control panel these buttons allow you to request the intermediate messages ...

Страница 7: ... line shows In operation No messages The scroll key can be used to request the software version number the address of the repeater panel software version x xx address x and the setting of the Silence function general or local The LCD is divided into a number of fields As soon as a message is present on the MD2400 fire detection control panel the LCD takes the form described below Line 1 Line 2 Lin...

Страница 8: ...help of the scroll keys all intermediate information can be displayed on the 2 upper text lines The alarm information always has priority over the fault information That is why all alarms are shown first followed by the pre alarms with a new sequence of numbers box d and then the faults again with a separate numbering for the order The LCD is equipped with a backlight which lights up automatically...

Отзывы: