Lilytech ZL-660A-R Скачать руководство пользователя страница 3

 

once and enters into the mode. Digital will    display a parameter code

U10

. Press 

 

or 

  to select the parameter code. Press 

S

  to show its value. Press 

  or 

 

to set the value. Press

S

  to return parameter code display status. 

Exit the Mode 

Keep depressing 

P

  for 3 seconds, the set parameters will be saved, the mode exits. 

If do not press any key for 30 seconds, the mode will exit without saving all the set data. 

 

6.3 Parameter Code and Description Table: 

   

No 

Parameter 

code 

Function 

Range 

Note 

Factory 

setting 

U10 

Load power on delay time 

1

100min 

 

U11 

Load MIN continuous work time 

0

100min 

 

U12 

Load run frequency 

0

0: Disable 

U20 

Room temperature sensor calibration 

-9.9

+9.9 

 

U22 

Temperature difference 

0.1

+10.0

 

The  hysteresis 

of control 

1.0 

U50 

High-temperature  warning  deviation 

value to Max Temp 

0~60

 

0: Disable 

U51 

Low-temperature  warning  deviation 

value to Min Temp 

0~60

 

0: Disable 

U52 

Over-temperature  warning  delay 

time

 

1

180min 

 

30 

U53 

First 

over-temperature 

warning 

delay time after power supply

 

0~180 hour 

0: Disable 

10 

U60 

External input warning mode 

0~4 

0:Warning off 

1:

On, Lock

 

2:On, Unlock 

3:Off, Lock 

4:Off, Unlock 

11 

U61 

External warning input delay 

0~120min 

 

12 

U62 

Buzzer warning 

0~1 

0:Warning off 

1:Warning on 

 

13 

U90 

Working mode

 

CO: Cool;   

HE: Heat

 

 

CO

 

14 

U97 

Baud rate setting 

0 ~ 3 

0: 2400bps 

1: 4800bps 

2: 9600bps 

3: 19200bps 

15 

U98 

Device address 

1 ~ 99 

---- 

16 

U99 

Password 

0000~9999 

 

1111 

17 

End 

Finished setting 

Содержание ZL-660A-R

Страница 1: ...Buzzer alarm output Max high temperature or min low temperature exceed warning Sensor failure warning External warning input Dry contact alarm output RS 485 3 Size Specification 1 Front panel dimension 78 34 5mm 2 Drilling template 71 29mm 3 Whole machines dimension 78 34 5 71mm 4 Length of sensor s 3m including the sensor probe 4 Technical Specification Temperature Sensor NTC Setting Range 40 120...

Страница 2: ...at temperature Keeping S pressed for 3 seconds to enter temperature setting mode The indicator or HACCP is on and the digital shows the set temperature Press key or to change the set temperature Keeping or pressed it will be adjusted quickly Press S the set temperature will be saved and leave the setting mode Or do not press any key for 30 seconds the device will leave the set mode without saving ...

Страница 3: ...le 5 4 U20 Room temperature sensor calibration 9 9 9 9 0 5 U22 Temperature difference 0 1 10 0 The hysteresis of control 1 0 6 U50 High temperature warning deviation value to Max Temp 0 60 0 Disable 0 7 U51 Low temperature warning deviation value to Min Temp 0 60 0 Disable 0 8 U52 Over temperature warning delay time 1 180min 30 9 U53 First over temperature warning delay time after power supply 0 1...

Страница 4: ...ture Sensor Fails When the room temperature sensor fails the system will automatically run into the protected running mode In this mode the compressor will run and stop with the period of 30 minutes Compressor works for U12 3 minutes stops for 30 U12 3 minutes For example Set U12 is 3 when the temperature sensor fails compressor runs for 9 minutes and then stops 21 minutes move in circles If U12 0...

Страница 5: ... and Password Keep P and keys pressed for 5 seconds the device displays UnL press twice buzzer sounds system auto restores the default parameters and password 1111 8 Controller Installation 8 1 Warning Avoid installing the device in the following environment Relative humidity is greater than 90 or possibly dewing Strong vibration Possibility be dropped or within fog Exposed to eroding and pollutin...

Страница 6: ...power devices Avoid direct contact with the internal electronic components After finish and check the electrical wiring layout before connect them to the device please follow this instruction Pay attention the electrical wiring diagram below wrong connection possibly damages the device and the system and may be dangerous to the user All security and protecting device for the equipments are necessa...

Страница 7: ......

Отзывы: