1
U10
Compressor power on delay time
1
~
100min
3
2
U11
Compressor MIN continuous work time
0
~
100min
3
3
U12
Compressor run frequency
0
~
8
0: Disable
5
4
U20
Room temperature sensor calibration
-9.9
~
+9.9
0
5
U21
Defrosting sensor calibration
-9.9~+9.9
0
6
U22
Temperature difference
0.1
~
+10.0
℃
Control
the
temperature
hysteresis
1.0
7
U30
Defrosting cycle
0~180 hour
0: Not defrost
12
8
U31
Defrosting
﹙
end
﹚
time
1
~
180min
30
9
U32
Defrosting end temperature
0.5
~
5
0
℃
15
10
U33
Dropping water time
0
~
180min
5
11
U34
Over temperature warning delay time
after defrost ends
0~180 hour
0: Disable
2
12
U35
Defrost when the device starts
0~1
0: Disable
1:Enable
0
13
U36
Defrost delay time when the device start
0
~
180min
0: Disable
0
14
U41
Fan start temperature
-45
~
+120
℃
-10
15
U42
Fan start-up delay
0
~
600sec
60
16
U43
Fan stop delay
0
~
600sec
0
17
U44
Fan mode
0
~
1
0: Controlled
1:
Free mode
0
18
U50
High-temperature warning deviation
value to Max Temp
0~6
0℃
0: Disable
0
19
U51
Low-temperature warning deviation
value to Min Temp
0~6
0℃
0: Disable
0
20
U52
Over-temperature warning delay time
1
~
180min
30
21
U53
First over-temperature warning delay
time after power supply
0~180 hour
0: Disable
2
22
U60
External input warning
0~1
0:Warning off
1:
On, Lock
2:On, Unlock
3:Off, Lock
4:Off, Unlock
0
23
U61
External warning input delay
0~120min
0
24
U62
Buzzer warning
0~1
0:Warning off
1:Warning on
25
U99
Password
0~99
11
5. Control Function Description