4.2 Keypad Operation 

Set Max and Min Temperature

 

  Press 

SET

, MAX TEMP LED will be on, and the digits will show the current max temperature. 

Press key 

  or 

  to change the max temperature setting.   

Press 

SET

  again, we can set the min temperature limit.   

Keeping depressing 

SET

  for 3 seconds, or do not press any key for 30 seconds, the device will leave 

the temperature testing mode.   

 

  The factory setting: max temperature is -15

, min temperature is 

-18

.

 

  The MAX TEMP must be higher than the MIN TEMP 

1℃,

otherwise could not be saved.   

Note: Only after the

SET

being depressed for three seconds, will the set data be confirmed and saved. 

4.3 Set System Parameters   

Enter Into System Parameter Setting Mode 

Keep depressing 

SET

  for three seconds, digits show “POO”. Input pa 

SET

. If correct, 

enter into the mode, else return. 

After enter into the mode, the display shows “U01”. Press 

  or 

  to select the parameter code.   

Press

SET

  will show the parameter value. Then press 

  or 

  to set this parameters, and 

press

SET

  to return. 

The factory setting: password is “11”. 

Exit the Mode 

Keep depressing “SET” for three seconds, the set parameters will be saved, the mode exits. 

Or do not press any key for 30 seconds, the mode exits, and the set parameters are not saved. 

Parameter Code and Description Table: 

N

o. 

Parameter code 

Function 

Range 

Explain 

Factory 

setting 

U10 

Compressor power on delay time 

1

100min 

 

U11 

Compressor MIN continuous work time 

0

100min 

 

U12 

Compressor run frequency 

0

0: Disable 

U20 

Room temperature sensor calibration 

-9.9

+9.9 

 

U50 

High-temperature warning deviation 

value to Max Temp 

0~6

0℃

 

0: Disable 

U51 

Low-temperature warning deviation 

value to Min Temp 

0~6

0℃

 

0: Disable 

U52 

Over-temperature warning delay time

 

1

180min 

 

30 

U53 

First  over-temperature  warning  delay 

time after power supply

 

0~180 hour 

0: Disable 

 

 

 

 

U60 

 

 

External input warning   

 

 

0~1 

0:Warning off 

1:

On, Lock

 

2:On, Unlock 

3:Off, Lock 

4:Off, Unlock 

 

 

10 

U61 

External warning input delay 

0~120min 

 

11 

U62 

Buzzer warning 

0~1 

0:Warning off 

1:Warning on 

 

12 

U99 

Password 

0~99 

 

11 

Содержание ZL-310A

Страница 1: ... Power Supply 185 245VAC 50 60HZ Terminal Wire 2 1 5mm2 or 1 2 5mm2 Load Current 3A 250Vac Resistive load Case PC ABS Fire Proof Protection Degree IP30 4 Operation Instruction 4 1 Display Indication Panel LED Indication LED On Off Blinking MAX TEMP Set max temperature Set max temperature to be set MIN TEMP Set min temperature Set min temperature to be set COOL Compressor on Compressor off Delay pr...

Страница 2: ...he parameter code Press SET will show the parameter value Then press or to set this parameters and press SET to return The factory setting password is 11 Exit the Mode Keep depressing SET for three seconds the set parameters will be saved the mode exits Or do not press any key for 30 seconds the mode exits and the set parameters are not saved Parameter Code and Description Table N o Parameter code...

Страница 3: ...or U12 3 minutes stop for 30 U12 3 minutes Note If U12 0 system stops when sensor fails 5 4 High temperature and Low temperature warning When the test temperature MAX TEMP U50 and the time reaches to U52 or U53 high temperature warning starts When the test temperature MIN TEMP U51 and the time reaches to U52 or U53 low temperature warning starts 5 5 External input warning There are several ways fo...

Страница 4: ...cian Wrong power supply may damage the device and system seriously Try with effort to layout the sensors and switches line apart from inductive load lines and power supply lines The sensors and switches lines are not allowed go with the power supply lines and inductive load lines in a same pipeline and are not allowed to pass near the contactor breaker and the similar Reduce the length of sensors ...

Отзывы: