SMA1
- Access:
ro = read only
rw = read and write
wo = write only
- Default parameter values are written in
bold
.
Profile ID
[42 - 43, ro]
These registers contain the identification code of the used profile.
Register
42
43
Hex
28
14
See “Standard encoder profile”, “data format”, “Variant 0-24”.
Serial number
[44 … 47, ro]
These registers show the serial number of the device expressed in hexadecimal
notation.
Register 44
: year of production
Register 45
: week of production
Registers 46 and 47
: serial number in ascending order
Command
[48, wo]
Value
Function
00
Normal operation
01
Save parameters on EEPROM
02
Save and activate Preset / Offset
04
Load and save default parameters
After having set a new value in some register, use the
function in this register to store it. Set “01” in the register.
After having set a Preset / Offset value, use the
function in this register to both store and activate the preset / offset at
the same time. Set “02” in the register.
Load and save default parameters
: default parameters are set at the factory
by Lika Electronic engineers to allow the operator to run the device for standard
operation in a safe mode. As soon as the command is sent the default
parameters are uploaded and activated. All parameters which have been set
previously are overwritten, thus previously set values are lost. The complete list
of machine data and the relevant default parameters preset by Lika Electronic
engineers are available on page 46. Set “04” in the register.
MAN SMA1 E 2.9.odt
7 - BiSS C-mode interface
35 of 48