IF51
NOTE
•
Every time you change the value in the
are required to enter new values also in
and
registers.
•
Using the ROUND LOOP function it is also possible to change the
counting direction of the encoder, by setting the
correspondingly.
•
After any action concerning the
registers become necessary.
8192
0
360
180
degrees
Original encoder signal
Round-Loop signal
Encoder 13Bit
Direction = 0
SSI-Offset = 2048
Round-Loop = 8192
Volt
T-Min
T-Max
Analogue Output (Output Mode = 1)
2048
Output Mode
This register allows to select the format of the analogue outputs as shown in
the Figure hereafter:
V
Encoder
M in. M ax.
Output Mode = 0
-10V ... 0 ... +10V
Encoder
M in. Max.
V
Output Mode = 1
0 ... +10V
M in. Max.
mA
Encoder
Output Mode = 2
4 ... 20 mA
mA
Encoder
M ax.
M in.
Output Mode = 3
0 ... 20 mA
The range of the encoder where the analogue output should move between
minimum and maximum output must be set next to the parameters
respectively (see on page 41). If
= 0 (-10V … +10V) you must set a value that is half the maximum resolution of
the encoder next to the
parameter (value has to be always
positive); you must set the maximum resolution of the encoder next to the
parameter. In all other cases (
MAN IF51 I_E 1.1.odt
10 - Parameter settings
44 / 56