AMM80 • SSI, BiSS, & RS-485

6.4 Implemented registers

Register (hex)

Function

11 … 17

Preset

40

Preset setting enable

44 … 47

Serial number

77

Command

78 … 7D

Device ID

7E - 7F

Manufacturer ID

All registers described in this section are listed as follows:

Function name
[Address, Attribute]

Description of the function and specification of the default value.

- Address: the register address is expressed in hexadecimal notation.
- Attribute:

ro = read only
rw = read and write
wo = write only

- Default parameter value is written in 

bold

.

Preset

[11 … 17, rw]

WARNING

You are allowed to enter a value next to the 

Preset

 registers only after having

set the value “01” next to the 

Preset setting enable

 register. As soon as you

have entered the desired preset value, you must set the value “00” next to the

Preset setting enable

 register and then save data.

These registers allow the operator to set the Preset value. The Preset function is
meant to assign a desired value to a physical position of the encoder. The
chosen physical position (i.e. the transmitted position value) will get the value
set next to these registers and all the previous and following positions will get a
value according to it. For instance, this can be useful for getting the zero point
of the encoder and the zero point of the application to match. The preset value
will be set for the position of the encoder in the moment when the command is
sent through the 

Activate Preset

 function of the 

Command

 register.

After having entered a value next to the 

Preset

 registers you can either save it

without activating the preset function or both save and activate it. Use the 

Save

parameters

 function (set “01” in the 

Command

 register) to save the new Preset

value without activating it.
If you want to activate the new Preset value, after saving use the  

Activate

Preset

 function (set “02” in the 

Command

 register).

MAN AMM80 SSI_BiSS_RS485 E 1.5.odt

6 - BiSS C-mode interface

38 of 60

Содержание AMM80

Страница 1: ...ation into robots motors and OEM applications Suitable for the following models AMM80xx xxxBG1 AMM80xx xxxSC1 AMM80xx xxxJP1 General contents Preliminary information 7 1 Safety summary 8 2 Identificat...

Страница 2: ...on herein is subject to change without notice and should not be construed as a commitment by Lika Electronic s r l Lika Electronic s r l reserves the right to make all modifications at any moments and...

Страница 3: ...onnection JP1 order code 20 4 1 4 RS 485 mating cable connection JP1 order code 21 4 2 Molex 53261 1271 male connector X2 order code 22 4 2 1 SSI and BiSS C mode connection BG1 and SC1 order codes 22...

Страница 4: ...l interface 44 7 1 RS 485 port settings 44 7 2 Frame format 44 7 2 1 Encoder data capture and reset 44 7 2 2 Write register 44 7 2 3 Read register 45 7 3 Field detail 45 7 3 1 Control Field 45 7 3 2 S...

Страница 5: ...vate Preset 42 C Command 42 CRC 36 37 D DATA 37 Device ID 42 E Error 35 M Manufacturer ID 42 P Position 35 Preset 38 Preset setting enable 41 R Register address 37 RW 37 S Save parameters 42 Serial nu...

Страница 6: ...t to highlight the parts of the text where information of great significance for the user can be found user must pay the greatest attention to them Instructions must be followed strictly in order to g...

Страница 7: ...e divided into some main sections In the first section some general information concerning the safety the mechanical installation and the electrical connection as well as tips for setting up and runni...

Страница 8: ...s section on page 19 in compliance with the 2014 30 EU norm on electromagnetic compatibility following precautions must be taken before handling and installing discharge electrical charge from your bo...

Страница 9: ...u are properly grounded before handling the kit encoder the operator must wear a wrist strap it must be worn on the hand and connected to ground through a 1 megohm resistor an ESD smock made of dissip...

Страница 10: ...AMM80 SSI BiSS RS 485 CAUTION Keep magnets away from the magnetic ring in the code disk it could be damaged by strong magnetic fields MAN AMM80 SSI_BiSS_RS485 E 1 5 odt 1 Safety summary 10 of 60...

Страница 11: ...code and the serial number when reaching Lika Electronic For any information on the technical characteristics of the product refer to the technical catalogue Warning encoders having order code ending...

Страница 12: ...in the 1 4 Specific handling and cleaning instructions and safety information against electrostatic discharges section on page 9 3 1 Mechanical characteristics of the mounting support This kit encode...

Страница 13: ...AMM80 SSI BiSS RS 485 Figure 2 Flange with pins MAN AMM80 SSI_BiSS_RS485 E 1 5 odt 3 Mounting instructions 13 of 60...

Страница 14: ...SS RS 485 3 2 Encumbrance sizes values are expressed in mm Figure 3 Encumbrance sizes of the encoder Figure 4 Encumbrance sizes of the code disk MAN AMM80 SSI_BiSS_RS485 E 1 5 odt 3 Mounting instructi...

Страница 15: ...kerosene benzene or other solvents as they damage the disk the code disk must always be handled by grasping its outer edges or the magnetic ring protect the disk from scratching avoid flexing the dis...

Страница 16: ...ick out of their housing Make sure that they do not hit the encoder unit 5 they may damage the LEDs 3 4 Mounting the encoder WARNING Always handle the encoder unit by grasping the enclosure on the sid...

Страница 17: ...with the encoder unit 5 as shown in the Figure the mark 8 punched in the code disk 3 must be centred in the encoder unit 5 as shown in the Figure Max misalignment allowed 10 mechanical degrees WARNIN...

Страница 18: ...llation procedure is successful the LEDs will blink for a while and then go off If at the end of the operation a LED is still on please repeat the procedure again Refer also to the 9 Diagnostic LEDs s...

Страница 19: ...vice Thus they must be cut at different lengths and insulated singularly 4 1 Hirose DF19G 14S 1H 54 male connector X1 order code 4 1 1 SSI and BiSS C mode connection BG1 and SC1 order codes Function P...

Страница 20: ...cos Green B sin Black B sin Red Vb White 0Vb Blue 5Vdc 5 Brown_Green 0Vdc White_Green Only available with multiturn encoder versions 65K order code 4 1 3 RS 485 connection JP1 order code Function Pin...

Страница 21: ...not to be connected Brown not to be connected Green not to be connected Black not to be connected Red Vb White 0Vb Blue 5Vdc 5 Brown_Green 0Vdc White_Green Only available with multiturn encoder versi...

Страница 22: ...olution only 4 2 1 SSI and BiSS C mode connection BG1 and SC1 order codes Function Pin 0Vdc 1 5Vdc 5 2 Clock IN MA 3 Clock IN MA 4 Data OUT SLO 5 Data OUT SLO 6 B sin 7 B sin 8 A cos 9 A cos 10 Zero s...

Страница 23: ...O Pink B sin Red B sin Black A cos Green A cos Brown Zero setting Preset White Counting direction Blue 4 2 3 RS 485 connection JP1 order code Function Pin 0Vdc 1 5Vdc 5 2 not used 3 not used 4 A RS 48...

Страница 24: ...a slew rate larger than 50V s 4 3 TF12 cable specifications Model LIKA TF12 encoder cable Cross section 6 x 2 x 28AWG Jacket Special flame retardant PVC compound RZ TM2 quality Shield Tinned copper b...

Страница 25: ...typically 3 6V 4 5 1 Replacement of the battery No ERROR active NOTE Follow this procedure if at power on both LEDs are off and no BiSS alarm is active or if only the WARNING LED and the WARNING bit a...

Страница 26: ...positions are provided properly the position is exactly the same the encoder was in when you stopped it 8 if you turn the disk both WARNING and ERROR LEDs are off 4 5 2 Replacement of the battery ERRO...

Страница 27: ...ting the disk 13 remove the battery 14 short circuit the battery input terminals and discharge the residual voltage connect the WHITE and BLUE wires 15 switch the 5Vdc power supply off 16 install and...

Страница 28: ...ise the hardware function is disabled NOTE In the BiSS interface the preset can be activated also by using the Activate Preset function of the Command register For detailed information please refer to...

Страница 29: ...operation of the system Please mount the motor cap and protect the encoder from light sources before starting the system and checking its operation The encoder has been calibrated to perform at its b...

Страница 30: ...e main advantages in comparison with parallel or asynchronous data transmissions are less conductors are required for transmission less electronic components possibility of insulting the circuits galv...

Страница 31: ...t code can be Binary or Gray see the order code 5 2 MSB left aligned protocol MSB left aligned protocol allows to left align the bits beginning from MSB most significant bit to LSB least significant b...

Страница 32: ...transmission ranging between 100 kHz and 4 MHz CLOCK IN and DATA OUT signals comply with the EIA standard RS 422 The SSI clock frequency baud rate depends on the length of the cable and must comply w...

Страница 33: ...AMM80 SSI BiSS RS 485 5 4 Recommended SSI input circuit MAN AMM80 SSI_BiSS_RS485 E 1 5 odt 5 SSI interface 33 of 60...

Страница 34: ...ding to the EIA standard RS 422 WARNING Never install the encoder in a single Master multi Slave network 6 1 Communication The BiSS C mode protocol uses two types of data transmission protocols Single...

Страница 35: ...and ends with lsb least significant bit Nbitres is the resolution of the encoder expressed in bits bit Nbitres 7 8 value msb lsb Nbitres is the resolution of the encoder expressed in bits It is compr...

Страница 36: ...battery charge level is low You are required to replace the battery as soon as possible See the 4 5 1 Replacement of the battery No ERROR active section on page 25 nW 1 no active warning 0 warning st...

Страница 37: ...ritten in the register transmitted from the Master to the Slave When you need to read in a register RW 10 it shows the value read in the register transmitted from the Slave to the Master It is 8 bit l...

Страница 38: ...to set the Preset value The Preset function is meant to assign a desired value to a physical position of the encoder The chosen physical position i e the transmitted position value will get the value...

Страница 39: ...and bit 32 of byte 15 are used for singleturn information bit 32 of byte 15 is the msbit of the singleturn information and is kept fixed lsbit of the singleturn information changes according to the re...

Страница 40: ...te 12 Byte 13 Byte 14 Byte 15 7 6 5 4 3 2 1 0 15 14 13 12 11 10 9 8 23 22 21 20 19 18 17 16 31 30 29 28 27 26 25 24 39 38 37 36 35 34 33 32 0 0 0 0 0 0 0 0 0 1 1 0 0 0 0 0 0 1 0 0 1 0 0 0 1 1 1 0 1 0...

Страница 41: ...allowed to set a new preset value only after having entered the value 01 next to this Preset setting enable register As soon as you have entered the desired preset value you must set the value 00 next...

Страница 42: ...egister is set back to 00 automatically Wait 30 ms at least EPROM writing time before activating a new function Device ID 78 7D ro These registers contain the Device ID name and hardware software rele...

Страница 43: ...e clock Time out is self adaptable to the clock frequency It is 1 5 1 clock frequency If clock frequency 50 kHz then the time out is 30 s If clock frequency 200 kHz then the time out is 7 5 s If clock...

Страница 44: ...e 7 3 2 Status Field section on page 45 DF Data Field see the 7 4 Data Field section on page 46 ADF Address Field see the 7 5 Address Field and EEPROM Data Field section on page 49 EDF EEPROM data to...

Страница 45: ...lue 23h 92h Data ID 3 1Ah Writing the register Data ID 6 32h Reading the register Data ID D EAh Resetting data errors Data ID 7 singleturn value BAh Data ID 8 singleturn value C2h Data ID C singleturn...

Страница 46: ...from LS byte to MS byte in binary output code High bits that are not used have fixed value 0 ABS absolute value data within singleturn information ABS0 is the low byte ABS2 is the high byte ABM multi...

Страница 47: ...and the Multiturn counting It further warns about a counting error Detection timing upon normal operation Output Latch Turn on the main power twice or reset the error ID 7 ID C see the next section ST...

Страница 48: ...rror and MT error are reset at the same time All errors resetting Data ID 7 Data ID must be transmitted to the encoder 10 times in succession at transmission intervals of 40 s or more All latch errors...

Страница 49: ...ADD2 ADD1 ADD0 MEM BUSY ADD6 ADD0 EEPROM address MEM BUSY status access status to EEPROM can be judged by MEM BUSY status The relationship between MEM BUSY status and the transmission data from the e...

Страница 50: ...reading Data ID D EEPROM data field 8 bit data Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 MS bit LS bit 7 6 CRC Field Generation algorithm in accordance with G X X8 1 Data is configured in accor...

Страница 51: ...i strlen BitString i DoInvert 1 BitString i CRC 7 XOR required CRC 7 CRC 6 CRC 6 CRC 5 CRC 5 CRC 4 CRC 4 CRC 3 CRC 3 CRC 2 CRC 2 CRC 1 CRC 1 CRC 0 CRC 0 DoInvert for i 0 i 8 i CRC8 CRC i 1 i 0 return...

Страница 52: ...4 sinusoidal waves per mechanical revolution with amplitude 1Vpp 1Vpp output level results from differential signals detection The frequency of output signals is proportional to the rotational speed o...

Страница 53: ...AMM80 SSI BiSS RS 485 VREF 2 5V 0 5V VA 1Vpp Av Av R2 R1 MAN AMM80 SSI_BiSS_RS485 E 1 5 odt 8 Sine Cosine output signals 53 of 60...

Страница 54: ...p between the circuitry and the disk is out of tolerance the circuitry is not installed properly 2 The LED 1 lights up RED when the battery is spent The encoder cannot operate You are required to repl...

Страница 55: ...AMM80 SSI BiSS RS 485 Replacement of the battery No ERROR active section on page 25 See the Battery alarm on page 47 MAN AMM80 SSI_BiSS_RS485 E 1 5 odt 9 Diagnostic LEDs 55 of 60...

Страница 56: ...arameters list BiSS C mode interface Parameters list Default value Preset 00 00 00 00 00 Preset setting enable 00 All values are expressed in hexadecimal notation MAN AMM80 SSI_BiSS_RS485 E 1 5 odt 10...

Страница 57: ...This page intentionally left blank...

Страница 58: ...This page intentionally left blank...

Страница 59: ...This page intentionally left blank...

Страница 60: ...n register removed Command register updated 1 2 11 11 2019 Mechanical drawings updated 1 3 14 01 2020 Pin 1 connected to ground 1 4 22 04 2020 SSI and RS 485 version added Italian version 1 5 06 05 20...

Отзывы: