EBX82 Instructions Rev04 

 

EBX82 

Surface 3 hour 8 Watt Maintained Exit Box 

 

We are delighted that you have purchased this Light fitting. Please read this instruction manual before installation and retain 
for the user/maintenance engineer for future reference.  

 
Our  products  are  designed  to  comply  with  the  recommendations  of  BS  EN  60598-1:2008  code  of  practice  for  emergency 
lighting of premises and be installed by a competent person in accordance with the relevant wiring regulations. 

 

IMPORTANT NOTE:

  

Installation  must  be  carried  out  by  a  skilled/competent  electrician  who  is  familiar  with  the  appropriate  standards  and 
technical requirements of the appliance and also taking in to consideration the latest building regulations. 

 
Not suitable for use with dimmer switches, Install in accordance with I.E.E. Wiring Regulations. 

 
This product 

must be

 earthed and 

NOT

 be subject to an electrical insulation test (500/1000v) 

 
For Maintained Operation-For lamp always on,link S1 and S2(Switched Live).If S1 and S2 not connected, fitting works as non-
maintained.  
 
For component protection in transit and user safety the luminaire battery fuse is supplied separately in the fitting please do 
not discard.  

                                                     

 

 

INSTALLATION

 

1. Remove the diffuser from the body by removing the two screws on the right hand side of the fittings and slide 
the Perspex legend from the fitting. 
2. Loosen the two gear tray screws and remove the gear tray, ensure the LED cable is not snagged. 
3. Disconnect the LED connector and earth on back box.  
4. Fix base to the wall.  
5. Ensure the mains supply is isolated.   
6.  For  non-maintained  operation  a  permanent  230v  AC  supply  is  required  to  the  live  (L),  Earth  and  neutral  (N) 
terminals on the PCB.  This would be as per non-maintained mode to charge the batteries.   
5. For maintained operation for continuous illumination this can be achieved by connecting a link between S1 and 
S2 (link supplied) or to have a switch S1 connection through a remote switch to the S2 connection.  
6. Ensure ALL electrical connections are tight with no loose strands. 
7. Plug the battery lead into connector on the PCB, reconnect the LED and earth lead to the back box. 
8.  Re-secure  the  gear  tray  into  the  base  of  the  unit  making  sure  that  the  mains  cable  and  LED  cable  are  not 
trapped. 
9. Slide the Perspex legend and refit the cover and two securing screws. 
10. Restore the mains supply, the green charge LED should be illuminate 
11. Ensure the fitting is charged for a minimum of 24 hours prior to testing 
12. The date of the commissioning of the battery should be added to the label on the battery 
13.

 

Subsequent testing should be carried out in accordance with the British/European standards.

 

 

 