AT SERIES ARCHITECTURAL DIMMER   

 

 

 Revision 0.3   

 

 

 

 

 

 

OWNERS MANUAL

 

 

 

 

 

 

      03/16/2020 

www.lightronics.com 

Lightronics Inc. 

 

 

 

 

 

509 Central Drive Virginia Beach, VA  23454 

 

 

 

 

    Tel 757 486 3588 

POWER REQUIREMENTS 

 

The AT Series dimmer requires a 120 or 230VAC hot power feed line for each lighting circuit (channel), a common 
neutral, and an earth ground.  Each of these feeds must powered by a circuit providing a minimum of 20 Amps and 
supplies only one of the AT Series dimmer lighting circuits. The power feed for channel 1 also powers the unit's 
internal electronic circuitry. The internal circuitry is protected by a replaceable 1/2 Amp, 250 Volt, fast acting fuse. 
The AT dimmer may be operated from either single phase or three phase power and may be switched between 
these power types by the user. 

 

INSTALLATION 

 

LOCATION AND MOUNTING 

 

The unit is to be wall mounted using the mounting holes provided in the chassis.  Orient the unit such that the circuit 
board  is in  the  lower left area of the chassis.  The unit may (but  is not required to be) spaced out from the wall 
approximately 1 inch. This may be desirable if the unit must be used in a location with a high ambient temperature.  
Standard sized knockout holes are provided in the top, bottom and right side of the chassis for wiring.  Be sure that 
the vent holes in the chassis and cover are not obstructed since they are needed for proper cooling. 

 

INPUT POWER CONNECTIONS 

 
WARNING 

Make sure that all power is removed from feed circuits before proceeding with wiring. 

 

Connect power input leads to the lower terminal strip positions as indicated on the terminal strip labels.  A hot feed 
line is needed for each channel. Associated NEUTRALS are to be connected to the NEUTRAL bar provided.  An 
earth ground is also needed. A ground lug is provided.  The terminal strip connection torque specification is 16 lb.-
in. max.  The minimum wire size is AWG#12.  Consult the applicable electrical codes for your location for exact wire 
specifications.    The  power  terminal  connections  are  intended  for  copper  wire  only.    This  unit  will  work  on  either 
single or three phase power. Any dimmer channel may get power from any phase. 

 

LOAD CONNECTIONS 

 

The AT Series dimmer is a triac based dimmer meant for forward phase loads.  You can connect up to 2400 Watts 
of lighting to each channel.  Connect lighting loads to the upper terminal strip positions as indicated by the label in 
the unit (see page 1).  The neutral bar and ground lug may be used for lighting loads. The terminal strip connection 
torque specification is 16 lb.-in. max.  

 

Содержание AT SERIES

Страница 1: ...applications It can be supplied with up to four 2400 Watt lighting circuits channels and be remotely controlled by a DMX lighting console The AT series dimmers are provided with a fast acting 20 Amp...

Страница 2: ...Standard sized knockout holes are provided in the top bottom and right side of the chassis for wiring Be sure that the vent holes in the chassis and cover are not obstructed since they are needed for...

Страница 3: ...up of the AT Series dimmer is done using the 2 LED indicators and the 3 push buttons located at the bottom left of the low voltage section of the circuit board inside of the unit Use these controls t...

Страница 4: ...abeled on the unit If a circuit breaker will not remain closed then there is an overload at the lamps for that channel which MUST be corrected before operation can continue INDICATORS There is an LED...

Страница 5: ...hting is controlled by external momentary switch closures either manually or by automated equipment The AT 402 dimmer is designed to activate preset lighting conditions in response to these controls A...

Страница 6: ...tched channel controls and DMX input It sets all channels to maximum intensity and remains in effect until the button is pushed again At that time the unit will Resume normal operation return to the i...

Страница 7: ...n the SYMBOL channel preset level and preset fade and its VALUE intensity and fade time There are 2 digits and 3 buttons to control everything Press the NEXT button to advance through each SYMBOL Pres...