background image

3"

6"

12"

Wall

Bed

12"

NIGHT LIGHT 

(Optional)

Indirect 9 or 7 watt PL lamp shielded by perforated mesh with
internal white acrylic overlay.
No glare to any patient.
Wired for independent switching.

OPTIONS 

3

4

3

3

2

2

1

3

4

3

3

2

2

1

3

4

3

3

2

2

1

Sequential switch (SW)

Pillow speaker (by others)

MD*Coffer’s optional low voltage (1-3 volts) sequential switch mounted in the fixture is listed in compliance

with UL 544 for medical and dental equipment.

SW Option

(sequential switch): One red wire with black stripes and one yellow wire from the fixture can be

wired to a wall receptacle (by others) for use with that manufacturers pillow speaker. The pillow speaker is
used to control the television, call the nurse and control the lighting. To control the lighting it should be speci-
fied to have a normally open momentary contact switch.
Pressing this switch on the pillow speaker the first time, turns the ambient light on; pressed a second time,
turns the reading light on and the ambient light off; pressed a third time, turns both the ambient and reading
lights on; pressed a fourth time turns both lights off. Pressing the button again repeats the cycle.

DP Option

(individual switches): One red wire, one red wire with black stripes and one yellow wire from the

fixture can be wired to a wall receptacle (by others) for use with manufacturers control systems (such as Hill-
Rom Side Com System). To control the lighting, it should be specified to have a normally open momentary
contact switch.
Pressing the first switch turns the ambient light on; pressed a second time, turns the ambient light off.
Pressing the second switch the first time, turns the reading light on; pressed a second time, turns the reading
light off. 

TAMPER RESISTANT/GERM SHIELD
Germ Shield

: Ideal for psychiatric wards and germ free environments. Fits lay-in grid

ceiling systems with 15/16" maximum ceiling tee face. The heavy duty welded extruded aluminum frame with
clear 1/8" thick polycarbonate lens is fixture to ceiling system sealed with a heavy duty gasket. Request Folio
R40-15 REV. A.

FOOTCANDLES ON BED

PL9 or PL7 Night Light (PL)

(Lamps not included)

Night Light

MD*COFFER

MDCG2BX

Page 3 of 4

2'x2' RECESSED OR SURFACE, MULTI-FUNCTION PATIENT LIGHTING

INDIRECT AMBIENT LIGHT WITH PERFORATED MESH SHIELD

Lightolier 

a Genlyte Thomas Company

www.lightolier.com

Technical Information: (978) 657-7600 • Fax (978) 658-0595
631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710
We reserve the right to change details of design, materials and finish.
© 2002 Genlyte Thomas Group LLC (Lightolier Division)
A0902

SECTION 8/Folio R40-22

Job Information

Type:

Содержание MD*COFFER MDCG2BX

Страница 1: ...ECT AMBIENT LIGHT WITH PERFORATED MESH SHIELD Job Information Type Job Name Cat No Lamp s Volts Ballast Lightolier a Genlyte Thomas Company www lightolier com Technical Information 978 657 7600 Fax 978 658 0595 631 Airport Road Fall River MA 02720 508 679 8131 Fax 508 674 4710 We reserve the right to change details of design materials and finish 2002 Genlyte Thomas Group LLC Lightolier Division A0...

Страница 2: ...o patient or visitors Controls light directly onto patients bed 17 21 23 28 33 6 5 18 22 24 29 35 6 5 17 21 23 28 33 6 5 Lighted Zone Illumination at the reading task ranges 45 50 footcandles MD COFFER MDCG2BX Page 2 of 4 2 x2 RECESSED OR SURFACE MULTI FUNCTION PATIENT LIGHTING INDIRECT AMBIENT LIGHT WITH PERFORATED MESH SHIELD Lightolier a Genlyte Thomas Company www lightolier com Technical Infor...

Страница 3: ...ith black stripes and one yellow wire from the fixture can be wired to a wall receptacle by others for use with manufacturers control systems such as Hill Rom Side Com System To control the lighting it should be specified to have a normally open momentary contact switch Pressing the first switch turns the ambient light on pressed a second time turns the ambient light off Pressing the second switch...

Страница 4: ... GLR Internal slow blow fusing SUFFIX GMF RADIO INTERFERENCE FILTER 120 or 277 volt 50 or 60 Hz One per fixture is standard SUFFIX RF GERM SHIELD Order Catalog Number MD4CLGS22 ELECTRICAL WIRING OPTIONS Consult factory SPECIFICATIONS MATERIALS Chassis parts are die formed 20 gauge steel Reading light low iridescence anodized 95 reflective semi specular reflector Ambient light flat white acrylic co...

Отзывы: