4. Install lamp (lamps) Install diffuser next.
5. For luminaries with emergency module: connect mains wires to L1, N1 according to polarity
shown (or directly to lamp base terminals). Connect to terminals L2, N2 power wires for constant
battery charging.
6. Check test by the means of TELEMANDO device.
It is possible to carry out the check test by connecting the TELEMANDO (TM) device: If the
power is present pressing the ON button
(on TELEMANDO device) will activate the luminaire’s emergency state which will continue until
the ON button is released.
Telemando device can service up to 35 luminaries (see connection diagram). The OFF button is
not used.
7. The connection of TELEMANDO remote emergency check and control device should be done
with solid wire 1-1.5 mm cross-section and maximal length 250 m. The connections must be
made according the polarity shown on wiring diagram. The «+» terminal on the TELEMANDO
device should be connected to the «+»ТМ terminal on emergency power module, the «-» terminal
on the TELEMANDO device should be connected to the «-»ТМ terminal on emergency power
module.
8. Place the luminaire into pre-made hole in suspended ceiling.
9. Install reflector (when available) and insert lamp (lamps).
10. Replace diffuser (frame) by clicking it into luminaire’s body with springs (external glass - by
screws or springs).
11. Internal electrical connection scheme can be found on ECG casing.
12. Between luminaire's body and top of ceiling recess air gap of at least 25 mm should be
provided.
Luminaire installation and connection should be done by an electrician of relevant
qualification.