3. Switch mains power off.
4. Unpack the luminaire.
5. For Dagard PSM60 and similar sandwich panel ceilings – cut the hole according to fig. For
Albes AP600 AC and similar «clip-in» ceilings – remove one ceiling board.
6. Clip out decorative plates from the frame profile with flat screwdriver.
7. Connect luminaire to mains with sealed connector (IP65) according to connection scheme.
8. For luminaries with backup power supply. Check test by the means of TELEMANDO device It
is possible to carry out the check test by connecting the TELEMANDO (TM) device: if the power
is present pressing the ON button (on TELEMANDO device) will activate the luminaire’s
emergency state which will continue until the ON button is released. Telemando device can
service up to 35 luminaries (see connection diagram). The OFF button is not used. The
connection of TELEMANDO remote emergency check and control device should be done with
solid wire 1-1.5 mm cross-section and maximal length 250 m. The connections must be made
according the polarity shown on wiring diagram. The «+» terminal on the TELEMANDO device
should be connected to the «+»ТМ terminal on emergency power module, the «-» terminal on the
TELEMANDO device should be connected to the «-»ТМ terminal on emergency power module.
9. Place luminaire into recess.
10. Lock the luminaire in the recess by turning 4 adjustment screws clockwise as shown on fig.
Turn screws until stop, make sure that luminaire is tightly snuggled along perimeter.
Seal perimeter of the luminaire if needed.