background image

LightAlarms

Tel: (888) 552-6467 

Fax: (800) 316-4515

www.lightalarms.com

06/18 750.1783 Rev. G

7/12

LMIU 125/250/400W Mini Inverter

   

Line 120Vac

Neutral 

120V

Neutral

120Vac

Ground

FIGURE 2C

WIRING DIAGRAM:

UN-SWITCHED

NORMALLY ON LOAD

Primary
Un-Switched

AC Input

Normally ON
Lighting Load

(see note 4)

Input Wiring

Output Wiring

Ground

Neutral

Line

Switched Line

Un-Switched Line

Neutral

Lighting Load
Fluorescent, LED,

Incandescent

(see note 4)

Notes:
1. Connect fixture supply and unit ground in accordance with local and national 

codes.

2. Single voltage wiring. Either 120V or 277V. Input and output voltage must be 

the same.

3. Unit jumper wire is preset for 120Vac. If the unit is to be wired for 277Vac, 

remove the jumper wire from the 120Vac INPUT POWER terminals and 
reinstall the jumper wire into the 277Vac INPUT POWER terminals. 

4.

DO NOT COMBINE THE INPUT POWER NEUTRAL WITH THE LOAD 
NEUTRAL.

(Un-Switched)

(see note 3)

Line 120Vac

Neutral 

120V

Neutral

120Vac

Ground

0-10V

FIGURE 2D

WIRING DIAGRAM:

UN-SWITCHED

NORMALLY ON LOAD

WITH LCO.

(REFER TO FIGURE 6)

 0-10V

LCO

Primary
Un-Switched
AC Input

Normally ON
Lighting Load

(see note 4)

Input Wiring

Output Wiring

Ground

Switched Line

Un-Switched Line

Neutral

Lighting Load
Fluorescent, LED,

Incandescent

(see note 4)

Notes:
1. Connect fixture supply and unit ground in accordance with local and national 

codes.

2. Single voltage wiring. Either 120V or 277V. Input and output voltage must be 

the same.

3. Unit jumper wire is preset for 120Vac. If the unit is to be wired for 277Vac, 

remove the jumper wire from the 120Vac INPUT POWER terminals and 
reinstall the jumper wire into the 277Vac INPUT POWER terminals. 

4.

DO NOT COMBINE THE INPUT POWER NEUTRAL WITH THE LOAD 
NEUTRAL.

(Un-Switched)

(see note 3)

Wire

LCO
Wire

Lighting Control

Wires to connect to

the Ballast / Driver

Line

Neutral

Содержание LMIU 125W

Страница 1: ...onal Electrical Code and local regulations 12 The LMIU contains potentially hazardous voltages Installation maintenance and service work should be performed by qualified and trained personnel 13 Elect...

Страница 2: ...TH NORMAL AND EMERGENCY SOURCES BY TURNING OFF THE A C BRANCH CIRCUIT AND BY DISCONNECTING THE BATTERY CAUTION BEFORE INSTALLING MAKE CERTAIN THE A C POWER IS OFF NOTE THE BATTERY S ARE SHIPPED SEPARA...

Страница 3: ...specting the operating voltage All remote circuitry is to be wired in accordance with Article 700 of the National Electric Code Do not exceed the total rating of the Mini Inverter Unit is rated at max...

Страница 4: ...e same color in each pole on the terminal block See Figure on side c Leave a minimum of one inch 25mm between the live voltage cabling and the unsheathed low voltage data cabling NOTE NO WIRING IS REQ...

Страница 5: ...e of 20 to 30 C 68 to 86 F their life expectancy is 8 to 10 years However as stated above the equipment must be tested for a minimum of 90 minutes once per year When the batteries will no longer opera...

Страница 6: ...tched Neutral Ground Line see note 3 see note 3 Wall Switch Normally ON Lighting Load Output Wiring Triac Dimmer Device Fluorescent LED Incandescent FIGURE 2A WIRING DIAGRAM SWITCHED NORMALLY ON LOAD...

Страница 7: ...PUT POWER terminals 4 DO NOT COMBINE THE INPUT POWER NEUTRAL WITH THE LOAD NEUTRAL Un Switched see note 3 Line 120Vac Neutral 120V Neutral 120Vac Ground 0 10V FIGURE 2D WIRING DIAGRAM UN SWITCHED NORM...

Страница 8: ...switch for at least 6 seconds The reset also initializes the main counter This renewal takes place to compensate for system variations when the unit ages Renewal is not allowed if there is a lighting...

Страница 9: ...isabled during a power failure in order for the load to provide a 100 level of lighting The circuit consists of a single pole dry contact relay that is normally closed in stand by operation In emergen...

Страница 10: ...not commissioned to the Nexus system Lamp load is OFF None if unit is in normally off mode Nexus option Unit is operating correctly Unit is not commissioned to the Nexus system LED flashing GREEN OFF...

Страница 11: ...the batteries LED Flashing RED 2 times every 6 seconds Charger Failure Error Charger not working Reset the unit see page 4 and if the same error is displayed replace the charger board LED Flashing RED...

Страница 12: ...CT CUSTOMER SERVICE FOR REPLACEMENT PARTS SERVICING MUST BE PERFORMED BY QUALIFIED PERSONNEL Consult Customer Service for current warranty information All information and specifications contained in t...

Отзывы: