LifeSource 810 Series Скачать руководство пользователя страница 3

Cautions And Requirements For Installing 

810 Commercial Water System  

Pre Installation 

Instructions 

All installations are to be done in accordance with any local codes.
LifeSource Water Systems are attached to the main water line 

going into the building. 

The pipe connection is made after the pressure regulator, if present, and after the 

sprinkler supply line. Attaching irrigation or sprinkler lines to the LifeSource Water 

System is not recommended. Make sure facility water is on the main line. 

(Some kitchen cold water lines have been plumbed separately if previously 

plumbed for soft water.)

CHECK WATER PRESSURE:

 The system is rated for l00psi. Water pressure measuring 

80psi during the day may surge to over l00psi at night when self-cleaning occurs. 

If daytime water pressure on main line is above 80 psi, a pressure regulator 

[See Figure 1]

 

is required.

Both tanks come with a 1” connected bypass.

 Arrows on top of the bypass valve indicate 

the incoming and outgoing water flow. 

All systems have a rinse drain line with a restrictive washer determining the g.p.m. (gallon per 

minute) flow rate.

 The 1620 Series systems require either a ½” O.D. (outside diameter) 

flexible tubing clamp in place or ½” PVC pipe. 

REMOVE OR CHANGE ANY EXISTING FILTERS 

on the refrigerator water line, beneath the 

sink and on any other water lines in the building. Any such filters, if retained, should 

be routinely changed per manufacturers’ recommendations. 

A suitable outlet to drain the rinse water must be made available for filter. 

That outlet can 

either be a ground location that has a sufficient percolation, a driveway or a drain. 

DO NOT CONNECT THE FILTER RINSE LINE TO AN AIR CONDITIONER DRAIN LINE.

An air gap must be used in connecting to a drain line to prevent possible back 

siphoning into the tank

 

(see Air Gap Illustration Figure 4). 

Filters delivered without the valve head installed:

 PRE-FILL the tank with water after the 

tank has been placed at the installation site. This will allow the water to assimilate 

into the carbon and any air to escape prior to operation. 

*If the system was delivered 

with the valve head pre-installed on the tank, DO NOT ATTEMPT TO REMOVE THE VALVE HEAD.

The ScaleSolver unit operates in the UPFLOW mode which is opposite of a 

conventional softener.

 Both the inlet and outlets are clearly marked on tank. 

This system requires a full bypass 

to allow for a service flow to be routed around the 

system as needed for servicing. 

[See Figures 2 & 3]

Copper and other metals must not be above EPA standards for municipal water. 

    

!

CAUTIONS & REQUIREMENTS

Read Before Installing System

Figure 1

 -  Water Pressure Gauge

Figure 2

 -  Filter Valve IN Bypass Position

Figure 3 

-

 

ScaleSolver Valve IN Bypass Position

Содержание 810 Series

Страница 1: ...c 787179 NV Lic 059578 LifeSource Water Systems Inc 523 S Fair Oaks Ave Pasadena CA 91105 LifeSourceWater com Customer Service 626 792 9996 Model 810 Commercial Water System Installation and Operations Guide ...

Страница 2: ... In Service Weight 90 lbs Chlorine must not be above 3 0 PPM The 810 Commercial Water Filter is a no maintenance whole facility water filtration system This system includes a fully automatic valve head that runs a self rinsing cycle every 14 days Inlet Connection 1 Outlet Connection 1 Max Dimensions 52 x 8 Max Flow Rate 10 gpm Max Temperature 140 F In areas where outside temperatures are less than...

Страница 3: ...efrigerator water line beneath the sink and on any other water lines in the building Any such filters if retained should be routinely changed per manufacturers recommendations A suitable outlet to drain the rinse water must be made available for filter That outlet can either be a ground location that has a sufficient percolation a driveway or a drain DO NOT CONNECT THE FILTER RINSE LINE TO AN AIR ...

Страница 4: ... close attention to the direction of the arrows on each valve head 2 First begin with the ScaleSolver by opening up the inlet valve first and then the outlet valve NOTE The ScaleSolver unit operates in the UPFLOW mode which is opposite of a conventional softener Both the inlet and outlets are clearly marked on tank 3 As the ScaleSolver fills with water allow cold water to run through a faucet or h...

Страница 5: ...illed about 4 apart along the pipe lying on the ground to better distribute the water in a garden area DO NOT cap the end of the pipe or connect the end of the pipe to a drip line NOTE If using the 24 volt transformer run wire and make connections but do not plug in 9 Turn on the main water supply and check all connections for leaks NOTE After installing the filtration tank it is extremely importa...

Страница 6: ...ver to the SERVICE position The water will continue the self cleaning cycle Leave the bypass lever in the SERVICE position MANUAL RINSE CYCLE INSTRUCTIONS 4 Rotate the control knob at the top of the tank SLOWLY clockwise to RAPID RINSE between 4 and 5 o clock Stop and leave it on RAPID RINSE for 2 to 3 minutes Water will be running out the rinse line during this time See Figure 5 5 Then turn the c...

Страница 7: ...grammed to self rinse once every 14 days for 30 minutes between 2 a m and 3 a m Water pulled into the building at this time will not be filtered by the system If you would like self rinsing to occur at a time other than 2 a m you must adjust the TIME OF DAY For example if you would like self cleaning to occur between 12 a m and 3 a m which is two hours earlier than programmed you must set the TIME...

Страница 8: ...water to run until it is fairly cool Consult your manufacturer instruction manual for draining tankless water heaters Immediately After Installation Traditional Water Heaters Boilers Tankless Water Heater Water Doesn t Taste Right Check Bypass See if the bypass on BOTH TANKS are in the service position See Figure 10 11 Check Electrical Make sure power plug on the WATER FILTER is plugged into elect...

Страница 9: ...o use single use dishwasher detergents Pods Packs or Tabs These will overwhelm your dishwasher with excess soap Excess soap will cause excess water spots and glazing We recommend Cascade Complete One teaspoon of Cascade Complete detergent and 1 teaspoon of Sour Salt Citric Acid or Glass Magic as a rinsing agent will produce excellent results Lime or Soap Scum Buildup If you currently have lime bui...

Страница 10: ...rees F 3 That failure has not resulted from misuse alteration freezing accident fire or neglect The automatic timer valve used by LifeSource Water Systems has a three year warranty on parts if installed as required by the manufacturer There will be no service charge for the first 90 days if installed by the factory WATER PRESSURE EXCEEDING 100 PSI CAN DESTROY THE INNER WORKINGS OF THE TANK AND VAL...

Страница 11: ...tion for Gas and Water The ScaleSolver system including the tank media and valve head is warranted for performance for a period of three years from the date of the original installation The ScaleSolver warranty is four years when installed in conjunction with a LifeSource Water System in the proper configuration LifeSource Water Systems Inc warrants the ScaleSolver system as follows Our obligation...

Отзывы: